TRANE R410A Split System Air Conditioner and Heat Pump Installation Guide

June 12, 2024
Trane

INSTALLATION INSTRUCTIONS
16 SEER
Split System Air Conditioner & Heat Pump
1.5-5 Tons
R410ATRANE R410A Split System Air Conditioner and Heat
Pump

NOTE : Appearance of unit may vary.

R410A Split System Air Conditioner and Heat Pump

RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION

WARNING
These instructions are intended as an aid to qualified licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death.

DO NOT DESTROY THIS MANUAL
Please read carefully and keep in a safe place for future reference by a serviceman.
All phases of this installation must comply with NATIONAL, STATE, AND LOCAL CODES.

Key to symbols and safety instructions

1.1 Key to symbols
Warnings in this document are identified by a warning triangle. Keywords at the start of a warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken.
This symbol indicates important information where there is no risk to people or property.
The following keywords are defined and can be used in this document:
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, could result in minor to moderate injury.
NOTICE is used to address practices not related to personal injury.

1.2 Safety
CAUTION:
This document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation.
Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
This document contains a wiring diagram and service information.
CAUTION:
This information is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and/or property damage.

WARNING: HAZARDOUS VOLTAGE
Failure to follow this warning could result in property damage, severe personal injury or death.
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized.
WARNING: REFRIGERANT OIL
These units use R-410A refrigerant which operates at 50% to 70% higher pressures than R-22. Use only R-410A approved service equipments. Refrigerant cylinders are painted a “Rose” color to indicate the type of refrigerant and may  contain a “dip” tube to allow for charging of liquid refrigerant into the system. All R-410A systems use a POE oil that readily absorbs moisture from the atmosphere. To limit this “hygroscopic” action, the system should remain sealed whenever possible. If a system has been opening to the atmosphere for more than 4 hours, the compressor oil must be replaced. Never break a vacuum with air and always change the driers when opening the system for component replacement.
CAUTION: HOT SURFACE
May cause minor to severe burning. Failure to follow this Caution could result in property damage or personal injury. Do not touch the top of compressor.
CAUTION: CONTAINS REFRIGERANT
Failure to follow proper procedures can result in personal illness or injury or severe equipment damage. System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening system.
CAUTION: GROUNDING REQUIRED
Failure to inspect or use proper service tools may result in equipment damage or personal injury. Reconnect all grounding devices. All parts of this product that are capable of conducting electrical current are grounded. If grounding wires, screws, straps, clips, nuts or washers used to complete a path to ground are removed for service, they must be returned to their original position and properly fastened.
WARNING: SERVICE VALVES
Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and/or property damage. Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn valve stem  counterclockwise only until the stem contacts the rolled edge. No torque is required.
WARNING: BRAZING REQUIRED
Failure to inspect lines or use proper service tools may result in equipment damage or personal injury. All outdoor unit and evaporator coil connections are copper-to-copper and should be brazed with a phosphorous’s-copper alloy material such as Silfos-5 or equivalent. Do not use soft solder.
WARNING: HIGH CURRENT LEAKAGE
Failure to follow this warning could result in property damage, severe personal injury or death. Grounding is essential before connecting electrical supply.

Unit location considerations

2.1 Unit dimensions

Unit Dimensions|
---|---
Model| H(Inchs)| W(Inchs)| L(Inchs)
AC| HP
18| 18/24| 24-15/16| 23-5/8| 23-5/8
24| 30| 24-15/16| 28| 28
30| 36| 24-15/16| 29-1/8| 29-1/8
/| 42| 33-3/16| 28| 28
36/42/48/60| 48/60| 33-3/16| 29-1/8| 29-1/8

Table 1
The unit’s weight value is on the cardboard box.
When mounting the outdoor unit on a roof, be sure the roof will support the unit’s weight. Properly selected isolation is recommended to prevent sound or vibration transmission to the building structure.TRANE R410A Split System
Air Conditioner and Heat Pump - Figure 1

2.2 Location restrictions
Ensure the top discharge area is unrestricted for at least 60 inches above the unit.
Do not locate outdoor unit near bedrooms since normal operational sounds may be objectionable.
Position unit to allow adequate space for unobstructed airflow, wiring, refrigerant lines, and serviceability.
Maintain a distance of 24 inches between units.
24 inches clearance must be provided in front of the control box (access panels) and any other side requiring service.
Position unit where water, snow or ice from roof or overhang cannot fall directly on unit.
Position the outdoor unit a minimum of 12’’ from any wall or surrounding shrubbery to ensure adequate airflow.
See Figure 2 and Figure 3.
Cold climate considerations (heat pump only)
Precautions must be taken for units being installed in areas where snow accumulation and prolonged below-freezing temperatures occur.
Units should be elevated 3-12 inches above the pad or rooftop, depending on local weather. This additional height will allow drainage of snow and ice melted during defrost cycle prior to its refreezing. Ensure that drain holes in unit base  pan are not obstructed, preventing drainage of defrost water (Figure 4).
If possible, avoid locations that are likely to accumulate snow drifts.
If not possible, a snow drift barrier should be installed around the unit to prevent a build-up of snow on the sides of the unit.TRANE R410A Split System
Air Conditioner and Heat Pump - Figure 2TRANE R410A Split System Air Conditioner and Heat Pump -
Figure 3TRANE R410A Split System
Air Conditioner and Heat Pump - Figure 4

Unit preparation

3.1 Pre-installation
STEP 1 – Check for damage and report promptly to the carrier any damage found to the unit (Figure 5).
STEP 2 – Instruments must be designed to install/serve R410A equipmens.

  • Gauge sets, hoses, refrigerant containers and recovery system must be designed to handle the POE type oils.
  • Manifold sets should be 800 PSIG high side and 250 PSIG low side.
  • All hoses must have a 700 PSIG service pressure rating.
  • Leak detectors should be disigned to detect R410A.
  • Recovery equipments (including refrigerant recovery containers) must be specifically designed to handle R410A.
  • Do not use an R22 TXV.
    TRANE R410A Split System Air Conditioner and Heat Pump - Figure
5

Setting up the unit

4.1 Pad installation
When installing the unit on a support pad, such as a concrete slab, consider the following:

  • The pad must be at least 1-2” larger than the unit on all sides.
  • The pad must be separate from any structure.
  • The pad must be level.
  • The pad must be high enough above grade to allow for drainage.
  • The pad location must comply with National, State and Local codes.

These instructions are intended to provide a method to tie-down system to concrete slab as a securing procedure for high wind areas. Check Local Codes for tie-down methods and protocols.TRANE R410A Split System Air Conditioner
and Heat Pump - Figure 6TRANE
R410A Split System Air Conditioner and Heat Pump - Figure
7

Refrigerant line considerations

5.1 Service valve connection sizes

Model Suction line connection Liquid line connection
AC HP
18 18 3/4
24 24 3/4
30 30 3/4
36 36 3/4
/ 42 3/4
42 / 7/8
48 48 7/8
60 60 7/8

5.2 Refrigerant line sizes

Model Suction line Liquid line
optional standard optional standard
18 5/8 3/4 5/16 3/8
24 5/8 3/4 5/16 3/8
30 5/8 3/4 5/16 3/8
36 5/8 3/4 5/16 3/8
42 3/4 7/8 5/16 3/8
48 7/8 1-1/8 1/2 3/8
60 7/8 1-1/8 1/2 3/8

5.3 Refrigerant piping limits and required refrigerant line length

Model Liquid line (Inches) Total equivalent length(Feet)
25 50 75

Maximum vertical length(Feet)
18| 5/16| 25| 50| 60| 58| 40| 30
3/8| 25| 50| 60| 60| 40| 30
24| 5/16| 25| 36| 29| 23| 16| 9
3/8| 25| 50| 60| 60| 40| 30
30| 5/16| 25| 49| 38| 27| 17| 6
3/8| 25| 50| 60| 60| 40| 30
36| 5/16| 25| 50| 37| 22| 7| N/A
3/8| 25| 50| 60| 60| 40| 30
42| 5/16| 25| 23| 4| N/A| N/A| N/A
3/8| 25| 50| 43| 36| 30| 24
48| 1/2| 25| 50| 56| 55| 40| 30
3/8| 25| 46| 38| 30| 22| 15
60| 1/2| 25| 50| 60| 60| 40| 30
3/8| 25| 50| 56| 44| 32| 20
Model| Suction line (Inches)| Total suction line length(Feet)
---|---|---
25| 50| 100| 150
Coefficient
18| 5/8| 1.00| 0.97| 0.94| 0.90
3/4| 1.00| 0.98| 0.95| 0.92
24| 5/8| 1.00| 0.97| 0.94| 0.90
3/4| 1.00| 0.98| 0.95| 0.92
30| 5/8| 1.00| 0.97| 0.94| 0.90
3/4| 1.00| 0.98| 0.96| 0.93
36| 5/8| 1.00| 0.97| 0.94| 0.90
3/4| 1.00| 0.99| 0.97| 0.96
42| 3/4| 1.00| 0.98| 0.97| 0.95
7/8| 1.00| 0.99| 0.98| 0.97
48| 7/8| 1.00| 0.98| 0.97| 0.96
1-1/8| 1.00| 0.99| 0.98| 0.97
60| 7/8| 0.99| 0.98| 0.94| 0.90
1-1/8| 1.00| 0.99| 0.98| 0.97

Table 5 Suction line length/size VS capacity multiplier
Using suction line larger than shown in chart will result in poor oil return and is not recommended.
For example: the system capacity published in AHRI is 17800 Btu/h. This data is based on the AHRI test condition and 25 feet line set with standard suction tube size (3/4″ tube). If you need to add the line set more than 25 feet or use the optional suction tube size, you need to recalculate the capacity with the coefficient in the table. For 50 feet line and 5/8″ suction tube, the capacity will be 17800*0.97=17266 Btu/h.
Determine required line length and lift. You will need this later in Section 14.
Total Line Length = __ Feet.
Total Vertical Change(Lift) = __ Feet.

5.4 Refrigerant line insulation
The suction line must always be insulated. DO NOT allow the Liquid Line and Suction Line to come in direct (metal to metal) contact.TRANE R410A Split
System Air Conditioner and Heat Pump - Figure 10

5.5 Reuse existing refrigerant lines

CAUTION:
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
For retrofit applications, where the existing refrigerant lines will be used, the following precautions should be taken:
Ensure that the refrigerant lines are the correct size. Refer to Section
5.1 listed and Table 3.
Ensure that the refrigerant lines are free of leaks, acid, and oil.
The manufacturer recommends installing only approved matched indoor and outdoor systems. All of the manufacturer’s split systems are AHRI certified. Some of the benefits of installing approved matched indoor and outdoor split systems are maximum efficiency, optimum performance and the best overall system reliability.

Refrigerant line routing

6.1 Precautions
Take precautions to prevent noise within the building structure due to vibration transmission from the refrigerant lines. For example:

  • When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type hangers.
  • Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
  • Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
  • Isolate the lines from all ductwork.
  • Minimize the number of 90º turns.
  • Use PVC piping as a conduit for all underground installations as shown in Figure 15. Buried lines should be keep as short as possible.
  • The lines should not obstruct service access to the coil, air handling system or filter.
  • Care must also be taken to isolate the refrigerant lines to minimize noise transmission from the equipment to the structure.

Comply with National, State, and Local Codes when isolating line sets from joists, rafters, walls or other structural elements.

TRANE R410A Split System Air Conditioner and Heat Pump - Figure
12TRANE R410A Split System Air
Conditioner and Heat Pump - Figure 13TRANE R410A Split System Air Conditioner and Heat Pump -
Figure 14TRANE R410A Split System
Air Conditioner and Heat Pump - Figure 15

Refrigerant line brazing

7.1 Braze the refrigerant lines

  1. Remove caps or plugs. Use a deburring tool to deburr the pipe ends.
    Clean both internal and external surfaces of the tubing using an emery cloth.

  2. Remove the pressure tap cap from both service valves.

  3. Purge the refrigerant lines and indoor coil with dry nitrogen.

  4. Wrap a wet rag around the valve body to avoid heat damage and continue the dry nitrogen purge (Figure 19).
    Braze the refrigerant lines to the service valves.
    Check liquid line filter drier’s directional flow arrow to confirm correct direction of refrigeration flow (away from outdoor unit and toward evaporator coil) as illustrated. Brazing the filter drier to the Liquid Line.
    Continue the dry nitrogen purge. Do not remove the wet rag until all brazing is completed.
    Remove the wet rag before stopping the dry nitrogen purge.

  5. Replace the pressure tap caps after the service valves have cooled.
    Note: Do not over tighten (between 40 and 60 inch-lbs. maximum).

Refrigerant line leak check

8.1 Check for leaks

  1. Pressurize the refrigerant lines and evaporator coil to 150 PSIG using dry nitrogen.TRANE R410A Split System Air Conditioner and Heat Pump - Figure 21
  2. Check for leaks by using a soapy solution or bubbles at each brazed location.

Remove nitrogen pressure and repair any leaks before continuing.

Evacuation

9.1 Evacuate the refrigerant lines and indoor coil
Do not open the service valves until the refrigerant lines and indoor coil leak check and evacuation are complete.

  1. Evacuate until the micron gauge reads no higher than 350 microns, then close off the valve to the vacuum pump.

  2. Observe the micron gauge. Evacuation is complete if the micron gauge does not rise above 500 microns in one (1) minute.
    Once evacuation is complete blank off the vacuum pump and micron gauge, and close the valves on the manifold gauge set.

Service valves

10.1 Open the service valves
WARNING:
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclock wise until the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in abrupt release  of system charge and may result in personal injury and /or property damage. Leak check and evacuation must be completed before opening the service valves.

  1. Remove service valve cap (Figure 25).
  2. Fully insert hex wrench into the stem and back out counterclockwise until valve stem just touches the rolled edge.
  3. Replace the valve stem cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn.

TRANE R410A Split System Air Conditioner and Heat Pump - Figure
25

Electrical – low voltage

11.1 Low Voltage Maximum Wire Length
Table 6 defines the maximum total length of low voltage wiring from the outdoor unit to the indoor unit and to the thermostat.

24 Volts – Wire size Max. wire length
18 AWG 150 Ft.
16 AWG 225 Ft.
14 AWG 300 Ft.

11.2 Low voltage hook-up diagrams

TRANE R410A Split System Air Conditioner and Heat Pump - Figure
26

Notes:
“ ” The electric auxiliary heat connection(optional).
W : Electric auxiliary heat signal.
W1 : The first Electric auxiliary heat signal.
W2 : The second Electric auxiliary heat signal.TRANE R410A Split System Air
Conditioner and Heat Pump - Figure 27

Notes:
“___ ” The electric auxiliary heat connection(option).
W : Electric auxiliary heat signal.
W1 : The first Electric auxiliary heat signal.
W2 : The second Electric auxiliary heat signal.
D signal is connect to the Electric auxiliary heat or the first Electric auxiliary heat.
“”: Outdoor unit signal. Only for single-stage compressor systems. TRANE
R410A Split System Air Conditioner and Heat Pump - Figure
28

Notes:
“ ” The electric auxiliary heat connection(option).
W : Electric auxiliary heat signal,connect to the Electric auxiliary heat or the first Electric auxiliary heat.
W1 : The first Electric auxiliary heat signal.
W2 : The second Electric auxiliary heat signal.

Electrical – high voltage

12.1 High voltage power supply
WARNING: LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and trouble shooting of this product, it may be necessary to work with live electrical components.
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
The high voltage power supply must agree with the equipment nameplate.
Power wiring must comply with National, State and Local Codes.
Follow instructions on unit wiring diagram located on the inside of the access panel.

12.2 High voltage disconnect switch
Install a separate disconnect switch at the outdoor unit.
Field provided flexible electrical conduit must be used for high voltage wiring.

12.3 High voltage ground
Ground the outdoor unit per National, State and Local Code requirements.

Start up

13.1 System start up

  1. Ensure Sections 7, 8, 9, 10, 11 and 12 have been completed.
  2. Set System Thermostat to OFF.
  3. Turn on disconnect to apply power to the indoor and outdoor units.
  4. Wait one (1) hour before starting the unit if compressor crankcase heater is used and the outdoor ambient temperature is below 70 ºF.
  5. Set system thermostat to ON.

System charge adjustment

14.1 Charging: Weigh-In Method
Weigh-In Method can be used for the initial installation, or anytime a system charge is being replaced. Weigh-In Method can also be used when power is not available to the equipment site or operating conditions (indoor/outdoor temperatures) are not in range to verify with the liquid line pressure charging method.

Model Factory Charge Charge multiplier for liquid line length
All models The data on nameplate 5/16″
0.4 oz/ft 0.6 oz/ft 1.2 oz/ft

The factory charge in the outdoor unit is sufficient for 15 feet of standard size interconnecting liquid line.
New Installations — Calculating additional charge for lineset greater than 15 feet.

  1. Total Line Length (ft)= (a)
  2. Standard Line set (ft)= 15 (b)(a) minus (b)
  3. Refrigerant Multiplier = (c)
  4.  Refrigerant Adder (cd) = (d)= (e)
  5. *If lineset is less than 15 feet, (e) = 0

Sealed-System Repairs — Calculating total system charge.

  1. Total Line Length (ft)=__ (a)
  2. Standard Line set (ft)= __15 (b)
  3. (a) minus (b)= (c)=__ (d)
  4. Refrigerant Multiplier= __(e*)
  5. Refrigerant Adder (c*d)= __(f)
  6. Factory Charge (nameplate)
  7. Total System Charge (e+f)

*If line set is less than 15 feet, (e) = 0

The only mode approved for validating system charge is while in Cooling Mode. Outdoor Temperature must be between 55°F and 115°F with Indoor Temperature kept between 70°F and 80°F.
14.2 Liquid line pressure charging and refrigerant adjustment in cooling (above 55°F outdoor temp.)
• For 5 TON AC unit,the Outdoor Temperature must be between 65°F and 105°F

  1. Check the outdoor ambient temperatures.
    Liquid line pressure (in cooling mode) is the only recommended method of charging above 55ºF outdoor ambient temperatures.
    For outdoor ambient temperatures below 55ºF , use weigh-in charge method.
    Note: It is important to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient temperature is above 55ºF. For best results the indoor temperature should be kept between 70ºF to 80ºF. Note: The temperature tolerance for actual approach is ± 3ºF.

  2. Ensure Sections 7, 8, 9, 10,11,12 and 13 have been completed.

  3. Stabilize the system by operating for a minimum of 20 minutes.
    At startup, or whenever charge is removed or added, the system must be operated for a minimum of 20 minutes to stabilize before accurate measurements can be made. Note:The pressure tolerance for actual approach is ± 5psig

  4. Calculate liquid line pressure (According to Refrigerant Charging Chart)
    • Measured Suction Line Pressure = ____PSIG
    • Outdoor Ambient Temperature = ___ ºF
    • Calculate Liquid Line Pressure = ____PSIG

REFRIGERANT CHARGING CHART FOR AC SYSTEM

Cooling Mode 16 SEER R410A AC Charge Chart 1.5 TON

Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value (psig)
Suction Pressure at Large Service Valve(psig)| 165| | | 252| 269| 286| 306| 326| 350| 373| 395| 419| 442| 467
161| | | 250| 267| 284| 304| 324| 348| 371| 393| 417| 440| 464
157| | | 248| 265| 282| 302| 322| 345| 368| 390| 414| 437| 461
153| | 228| 244| 262| 280| 300| 320| 342| 365| 387| 411| 435| 459
149| | 226| 242| 260| 277| 298| 318| 339| 362| 385| 409| 432| 457
145| | 224| 240| 258| 275| 296| 316| 337| 360| 382| 406| 430| 455
141| 205| 222| 238| 255| 272| 293| 314| 334| 357| 380| 404| 428| 453
137| 203| 220| 236| 253| 269| 291| 312| 332| 355| 377| 402| 426| 451
133| 201| 218| 234| 250| 266| 288| 310| 330| 353| 375| 400| 424| 449
129| 199| 216| 232| 248| 264| 286| 308| 328| 351| 374| 398| 422| 447
125| 198| 214| 230| 246| 262| 284| 306| 326| 349| 372| 396| 420| 445
121| 196| 212| 228| 244| 260| 282| 304| 324| 347| 370| 394| 418| 443
117| 194| 210| 226| 242| 258| 280| 302| 322| 345| 367| 392| 416| 441
113| 192| 208| 224| 240| 256| 278| 300| 320| 343| 365| 390| 414| 439
109| 190| 206| 222| 238| 254| 276| 298| 318| 340| 362| 387| 412| 437
105| 188| 204| 220| 236| 252| 273| 295| 316| 338| 360| 385| 410| 435
Cooling Mode| 16 SEER R410A AC Charge Chart 2 TON
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value(psig)
Suction Pressure

at Large Service Valve(psig)

| 165| | | 258| 277| 295| 316| 337| 358| 382| 405| 430| 454| 479
161| | | 256| 275| 293| 314| 335| 356| 380| 403| 428| 452| 477
157| | | 254| 273| 291| 312| 333| 354| 378| 401| 426| 450| 475
153| | 236| 252| 271| 289| 310| 331| 352| 376| 399| 424| 448| 473
149| | 234| 250| 269| 287| 308| 329| 350| 374| 397| 422| 446| 471
145| | 232| 248| 267| 285| 306| 327| 348| 372| 395| 419| 443| 469
141| 214| 230| 246| 265| 283| 304| 325| 346| 370| 393| 417| 441| 467
137| 212| 228| 244| 262| 280| 301| 322| 343| 367| 391| 415| 439| 465
133| 210| 226| 242| 260| 278| 299| 320| 341| 365| 389| 413| 437| 463
129| 208| 224| 240| 258| 276| 297| 318| 339| 363| 387| 411| 435| 461
125| 206| 222| 238| 256| 274| 295| 316| 337| 361| 385| 409| 433| 459
121| 204| 220| 236| 254| 272| 293| 314| 335| 359| 383| 407| 431| 457
117| 202| 218| 234| 252| 270| 291| 312| 333| 357| 381| 405| 429| 455
113| 199| 216| 232| 250| 268| 289| 310| 331| 355| 379| 403| 427| 453
109| 197| 214| 230| 248| 266| 287| 308| 329| 353| 377| 401| 425| 451
105| 195| 212| 228| 246| 264| 285| 306| 327| 351| 375| 399| 423| 449
Cooling Mode| 16 SEER R410A AC Charge Chart 2.5 TON
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value (psig)
165| | | 261| 280| 299| 319| 340| 360| 382| 404| 431| 457| 483|
161| | | 259| 278| 297| 317| 338| 358| 380| 401| 428| 455| 481|
157| | | 257| 276| 295| 315| 336| 356| 377| 398| 426| 453| 479|
153| | 240| 255| 274| 293| 313| 333| 353| 375| 396| 424| 451| 477|
149| | 238| 253| 272| 291| 311| 331| 351| 373| 394| 422| 449| 475|
145| | 236| 251| 270| 289| 309| 329| 349| 371| 392| 420| 447| 473|
141| 218| 234| 249| 268| 287| 307| 327| 347| 369| 390| 418| 445| 471|
137| 216| 232| 247| 266| 285| 305| 325| 345| 367| 388| 416| 443| 469|
133| 214| 230| 245| 264| 283| 303| 323| 343| 364| 385| 413| 441| 467|
129| 212| 228| 243| 262| 281| 301| 321| 341| 362| 383| 411| 439| 465|
125| 210| 226| 241| 260| 279| 299| 319| 339| 360| 381| 409| 437| 463|
121| 207| 223| 239| 258| 277| 297| 317| 337| 358| 379| 407| 435| 461|
117| 204| 221| 237| 256| 275| 295| 315| 335| 356| 377| 405| 433| 459|
113| 202| 219| 235| 254| 273| 293| 313| 333| 354| 375| 403| 431| 457|
109| 200| 217| 233| 252| 271| 291| 311| 331| 352| 373| 401| 429| 455|
105| 198| 215| 231| 250| 269| 289| 309| 329| 350| 371| 399| 427| 453|
Cooling Mode| 16 SEER R410A AC Charge Chart 3 TON
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value (psig)
165| | | 259| 277| 295| 316| 337| 358| 384| 410| 435| 460| 486|
161| | | 257| 275| 293| 314| 335| 356| 382| 408| 433| 458| 484|
157| | | 255| 273| 291| 312| 333| 354| 380| 406| 431| 456| 482|
153| | 235| 253| 271| 289| 310| 331| 352| 378| 404| 429| 454| 480|
149| | 233| 251| 269| 287| 308| 329| 350| 376| 402| 427| 452| 478|
145| | 231| 249| 267| 285| 306| 327| 348| 374| 400| 425| 450| 476|
141| 214| 229| 247| 265| 283| 304| 325| 346| 372| 398| 423| 448| 474|
137| 212| 227| 245| 263| 281| 302| 323| 344| 263| 396| 263| 446| 472|
133| 210| 225| 243| 261| 279| 300| 321| 342| 368| 394| 419| 444| 470|
129| 208| 223| 241| 259| 277| 298| 319| 340| 366| 392| 417| 442| 468|
125| 206| 221| 239| 257| 275| 296| 317| 338| 364| 390| 415| 440| 466|
121| 204| 219| 237| 255| 273| 294| 315| 336| 362| 388| 413| 438| 464|
117| 202| 217| 235| 253| 271| 292| 313| 334| 360| 386| 411| 436| 462|
113| 200| 215| 233| 251| 269| 290| 311| 332| 358| 384| 409| 434| 460|
109| 198| 213| 231| 249| 267| 288| 309| 330| 356| 382| 407| 432| 458|
105| 196| 211| 229| 247| 265| 286| 307| 328| 354| 380| 405| 430| 456|
Cooling Mode| 16 SEER R410A AC Charge Chart 3.5 TON
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value (psig)
Suction Pressure at Large Service Valve (psig)| 165| | | 258| 277| 296| 314| 332| 350| 376| 401| 427| 452| 478
161| | | 256| 275| 294| 312| 330| 348| 374| 399| 425| 450| 476
157| | | 254| 273| 292| 310| 328| 346| 372| 397| 423| 448| 474
153| | 237| 252| 271| 290| 308| 326| 344| 370| 395| 421| 446| 472
149| | 235| 250| 269| 288| 306| 324| 342| 368| 393| 419| 444| 470
145| | 233| 248| 267| 286| 304| 322| 340| 366| 391| 417| 442| 468
141| 215| 231| 246| 265| 284| 302| 320| 338| 364| 389| 415| 440| 466
137| 213| 229| 244| 263| 281| 299| 318| 336| 362| 387| 413| 438| 464
133| 211| 227| 242| 260| 278| 297| 315| 334| 360| 385| 411| 436| 462
129| 209| 225| 240| 258| 275| 294| 313| 332| 358| 383| 409| 434| 460
125| 207| 223| 238| 256| 273| 292| 311| 330| 356| 381| 407| 432| 458
121| 205| 221| 236| 254| 271| 290| 309| 328| 354| 379| 405| 430| 456
117| 202| 218| 234| 252| 269| 288| 307| 326| 352| 377| 403| 428| 454
113| 199| 216| 232| 250| 267| 286| 305| 324| 350| 375| 401| 426| 452
109| 197| 214| 230| 248| 265| 284| 303| 322| 348| 373| 399| 424| 450
105| 195| 212| 228| 246| 263| 282| 301| 320| 346| 371| 397| 422| 448
Cooling Mode| 16 SEER R410A AC Charge Chart 4 TON
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value (psig)
Suction Pressure at Large Service Valve (psig)| 165| | | 264| 282| 300| 322| 343| 364| 388| 412| 437| 464| 491
161| | | 262| 280| 298| 320| 341| 362| 386| 410| 435| 462| 489
157| | | 260| 278| 296| 318| 339| 360| 384| 408| 433| 460| 487
153| | 239| 258| 276| 294| 316| 337| 358| 382| 406| 431| 458| 485
149| | 237| 256| 274| 292| 314| 335| 356| 380| 404| 429| 456| 483
145| | 235| 254| 272| 290| 312| 333| 354| 378| 402| 427| 454| 481
141| 215| 233| 252| 270| 288| 310| 331| 352| 376| 400| 425| 452| 479
137| 213| 231| 250| 268| 286| 308| 329| 350| 374| 398| 423| 450| 477
133| 211| 229| 248| 266| 284| 306| 327| 348| 372| 396| 421| 448| 475
129| 209| 227| 246| 264| 282| 304| 325| 346| 370| 394| 419| 446| 473
125| 207| 225| 244| 262| 280| 302| 323| 344| 368| 392| 417| 444| 471
121| 205| 223| 242| 260| 278| 300| 321| 342| 366| 390| 415| 442| 469
117| 203| 221| 240| 258| 276| 298| 319| 340| 364| 388| 413| 440| 467
113| 201| 219| 238| 256| 274| 296| 317| 338| 362| 386| 411| 438| 465
109| 199| 217| 236| 254| 272| 294| 315| 336| 360| 384| 409| 436| 463
105| 197| 215| 234| 252| 270| 292| 313| 334| 358| 382| 407| 434| 461
Cooling Mode| 16 SEER R410A AC Charge Chart 5 TON
---|---
Outdoor Ambient Temperature( oF )
65| 70| 75| 80| 85| 90| 95| 100| 105
Liquid Pressrue at Small Service Value (psig)
Suction Pressure at Large Service Valve (psig)| 165| 273| 294| 317| 339| 361| 383| 404| 431| 458
161| 271| 292| 314| 336| 358| 381| 403| 430| 457
157| 269| 289| 311| 334| 356| 379| 401| 428| 455
153| 267| 287| 308| 331| 353| 377| 400| 426| 453
149| 266| 285| 306| 328| 350| 374| 398| 424| 451
145| 264| 283| 304| 326| 348| 373| 397| 423| 450
141| 262| 281| 302| 324| 346| 371| 395| 421| 448
137| 260| 279| 300| 322| 344| 369| 393| 419| 446
133| 259| 278| 298| 320| 342| 367| 392| 418| 443
129| 257| 276| 296| 318| 340| 365| 390| 415| 440
125| 255| 274| 294| 316| 338| 363| 388| 413| 438
121| 253| 272| 292| 314| 336| 361| 386| 411| 435
117| 252| 271| 291| 313| 335| 360| 384| 409| 433
113| 250| 269| 290| 312| 334| 358| 382| 407| 431
109| 248| 268| 289| 311| 333| 357| 380| 404| 428
105| 246| 266| 288| 310| 331| 355| 378| 402| 426

REFRIGERANT CHARGING CHART FOR HP SYSTEM

Cooling Mode 16SEER R410A HP Charge Chart 1.5TON(Cooling mode)

O u t doo r A m b i ent T emperature( oF )
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
Liquid Pressure at Small Service Valve (psig)
Suction Pressure at Large| 165| | | 246| 265| 284| 303| 323| 343| 364| 390| 416| 441| 467
161| | | 244| 263| 282| 301| 321| 341| 362| 388| 414| 439| 465
157| | | 242| 261| 280| 299| 319| 339| 360| 386| 412| 437| 463
153| | 221| 240| 259| 278| 297| 317| 337| 358| 384| 410| 435| 461
149| | 219| 238| 257| 276| 295| 315| 335| 356| 382| 408| 433| 459
145| | 217| 236| 255| 274| 293| 313| 333| 354| 380| 406| 431| 457
141| 196| 215| 234| 253| 272| 291| 311| 331| 352| 378| 404| 429| 455
137| 195| 213| 232| 251| 269| 288| 309| 328| 350| 376| 402| 427| 453
133| 193| 211| 230| 249| 267| 286| 306| 326| 347| 373| 399| 425| 451
129| 191| 209| 228| 247| 265| 284| 304| 323| 344| 370| 397| 423| 449
125| 190| 209| 227| 245| 264| 282| 302| 320| 341| 368| 394| 421| 447
121| 190| 208| 226| 244| 262| 280| 300| 320| 341| 367| 393| 419| 445
117| 188| 206| 224| 242| 260| 278| 298| 318| 339| 365| 391| 417| 443
113| 186| 204| 222| 240| 258| 276| 296| 316| 337| 363| 389| 415| 441
109| 184| 202| 220| 238| 256| 274| 294| 314| 335| 361| 387| 413| 439
105| 182| 200| 218| 236| 254| 272| 292| 312| 333| 359| 385| 411| 437
Cooling Mode| 16SEER R410A HP Charge Chart 2TON(Cooling mode)
---|---
Outdoor Ambient Temperature( oF̧ )
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
Liquid Pressure at Small Service Valve (psig)
Suction Pressure at Large Service Valve(psig)| 165| | | 255| 274| 294| 313| 335| 358| 381| 407| 434| 461| 486
161| | | 253| 272| 292| 311| 333| 356| 379| 405| 432| 459| 484
157| | | 251| 270| 290| 309| 331| 354| 377| 403| 430| 457| 482
153| | 230| 249| 268| 288| 307| 329| 352| 375| 401| 428| 455| 480
149| | 228| 247| 266| 286| 305| 327| 350| 373| 399| 426| 453| 478
145| | 226| 245| 264| 284| 303| 325| 348| 371| 397| 424| 451| 476
141| 204| 224| 243| 262| 282| 301| 323| 346| 369| 395| 422| 449| 474
137| 203| 222| 241| 260| 279| 298| 320| 344| 367| 393| 420| 447| 472
133| 201| 220| 239| 258| 277| 296| 318| 342| 365| 391| 418| 445| 470
129| 199| 218| 237| 256| 275| 294| 316| 340| 363| 389| 416| 443| 468
125| 197| 216| 235| 254| 273| 292| 314| 338| 361| 387| 414| 441| 466
121| 195| 214| 233| 252| 271| 290| 312| 336| 359| 385| 412| 439| 464
117| 193| 212| 231| 250| 269| 288| 310| 334| 357| 383| 410| 437| 462
113| 191| 210| 229| 248| 267| 286| 308| 332| 355| 381| 408| 435| 460
109| 189| 208| 227| 246| 265| 284| 306| 330| 353| 379| 406| 433| 458
105| 187| 206| 225| 244| 263| 282| 304| 328| 351| 377| 404| 431| 456
Cooling Mode| 16SEER R410A HP Charge Chart 2.5TON(Cooling mode)
---|---
O u t doo r A m b i ent T emperature ( o F)
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
Liquid Pressure at Small Service Valve (psig)
Suction Pressure at Large Service Valve(psig)| 165| | | 253| 269| 288| 305| 327| 348| 370| 390| 414| 435| 461
161| | | 251| 267| 286| 303| 325| 346| 368| 388| 412| 433| 459
157| | | 249| 265| 284| 301| 323| 344| 366| 386| 410| 431| 457
153| | 231| 247| 263| 282| 299| 321| 342| 364| 384| 408| 429| 455
149| | 229| 245| 261| 280| 297| 319| 340| 362| 382| 406| 427| 453
145| | 227| 243| 259| 278| 295| 317| 338| 360| 380| 404| 425| 451
141| 208| 225| 241| 257| 276| 293| 315| 336| 358| 378| 402| 423| 449
137| 206| 223| 239| 255| 274| 291| 313| 334| 356| 376| 400| 421| 447
133| 204| 221| 237| 253| 272| 289| 311| 332| 354| 374| 398| 419| 445
129| 202| 219| 235| 251| 270| 287| 309| 330| 352| 372| 396| 417| 443
125| 199| 215| 232| 249| 267| 285| 307| 328| 350| 370| 394| 415| 441
121| 195| 213| 230| 247| 267| 285| 306| 327| 348| 368| 392| 413| 439
117| 193| 211| 228| 245| 265| 283| 304| 325| 346| 366| 390| 411| 437
113| 191| 209| 226| 243| 263| 281| 302| 323| 344| 364| 388| 409| 435
109| 189| 207| 224| 241| 261| 279| 300| 321| 342| 362| 386| 407| 433
105| 187| 205| 222| 239| 259| 277| 298| 319| 340| 360| 384| 405| 431
Cooling Mode| 16SEER R410A HP Charge Chart 3TON(Cooling mode)
---|---
Outdoor Ambient Temperature( oF  )
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
Liquid Pressure at Small Service Valve (psig)
Suction Pressure at Large Service Valve(psig)| 165| | | 260| 278| 296| 314| 336| 359| 381| 402| 427| 454| 482
161| | | 258| 276| 294| 312| 334| 357| 379| 400| 425| 452| 480
157| | | 256| 274| 292| 310| 332| 355| 377| 398| 423| 450| 478
153| | 236| 254| 272| 290| 308| 330| 352| 374| 395| 420| 448| 476
149| | 234| 252| 270| 288| 306| 328| 350| 372| 393| 418| 446| 474
145| | 232| 250| 268| 286| 304| 326| 347| 369| 390| 416| 444| 472
141| 212| 230| 248| 266| 284| 302| 323| 345| 366| 388| 413| 442| 470
137| 210| 228| 246| 264| 282| 300| 321| 342| 363| 385| 411| 439| 468
133| 208| 226| 244| 262| 280| 298| 319| 339| 360| 382| 408| 437| 466
129| 206| 224| 242| 260| 278| 296| 316| 337| 357| 379| 406| 435| 464
125| 204| 222| 240| 258| 276| 294| 314| 335| 355| 377| 404| 433| 462
121| 202| 220| 238| 256| 274| 292| 312| 333| 353| 375| 402| 431| 460
117| 200| 218| 236| 254| 272| 290| 310| 331| 351| 373| 400| 429| 458
113| 198| 216| 234| 252| 270| 288| 308| 329| 349| 371| 398| 427| 456
109| 196| 214| 232| 250| 268| 286| 306| 327| 347| 369| 396| 425| 454
105| 194| 212| 230| 248| 266| 284| 304| 325| 345| 367| 394| 423| 452
Cooling Mode| 16SEER R410A HP Charge Chart 3.5TON(Cooling mode)
---|---
Outdoor Ambient Temperature( oF  )
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
Liquid Pressure at Small Service Valve (psig)
Suction Pressure at Large Service Valve(psig)| 165| | | 254| 271| 288| 305| 327| 348| 370| 394| 417| 441| 464
161| | | 252| 269| 286| 303| 325| 346| 368| 392| 415| 439| 462
157| | | 250| 267| 284| 301| 323| 344| 366| 390| 413| 437| 460
153| | 231| 248| 265| 282| 299| 321| 342| 364| 388| 411| 435| 458
149| | 229| 246| 263| 280| 297| 319| 340| 362| 386| 409| 433| 456
145| | 227| 244| 261| 278| 295| 317| 338| 360| 384| 407| 431| 454
141| 208| 225| 242| 259| 276| 293| 315| 336| 358| 382| 405| 429| 452
137| 206| 223| 240| 257| 274| 291| 313| 334| 356| 380| 403| 427| 450
133| 204| 221| 238| 255| 272| 289| 311| 332| 354| 378| 401| 425| 448
129| 202| 219| 236| 253| 270| 287| 309| 330| 352| 376| 399| 423| 446
125| 200| 217| 234| 251| 268| 285| 307| 328| 350| 374| 397| 421| 444
121| 198| 215| 232| 249| 266| 283| 305| 326| 348| 372| 395| 419| 442
117| 196| 213| 230| 247| 264| 281| 303| 324| 346| 370| 393| 417| 440
113| 194| 211| 228| 245| 262| 279| 301| 322| 344| 368| 391| 415| 438
109| 192| 209| 226| 243| 260| 277| 299| 320| 342| 366| 389| 413| 436
105| 190| 207| 224| 241| 258| 275| 297| 318| 340| 364| 387| 411| 434
Cooling Mode| 16 SEER R410A HP Charge Chart 4 TON(Cooling mode)
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value (psig)
Suction Pressure at Large Service Valve (psig)| 165| | | 249| 265| 281| 302| 324| 345| 365| 385| 412| 438| 465
161| | | 247| 263| 279| 300| 322| 343| 363| 383| 410| 437| 463
157| | | 245| 261| 277| 298| 320| 341| 361| 381| 408| 435| 461
153| | 228| 243| 259| 275| 296| 318| 339| 359| 379| 406| 433| 459
149| | 226| 241| 257| 273| 294| 316| 337| 357| 377| 404| 431| 457
145| | 234| 239| 255| 271| 292| 314| 335| 355| 375| 402| 429| 455
141| 209| 223| 237| 253| 269| 290| 312| 333| 353| 373| 400| 427| 453
137| 207| 221| 235| 251| 267| 288| 310| 331| 351| 371| 398| 425| 451
133| 205| 219| 233| 249| 265| 286| 308| 329| 349| 369| 396| 423| 449
129| 203| 217| 231| 247| 263| 284| 306| 327| 347| 367| 394| 421| 447
125| 201| 215| 229| 245| 261| 282| 304| 325| 345| 365| 392| 419| 445
121| 197| 212| 227| 243| 259| 280| 302| 323| 343| 363| 390| 417| 443
117| 194| 210| 225| 241| 257| 278| 300| 321| 341| 361| 388| 415| 441
113| 190| 207| 223| 239| 255| 277| 298| 320| 340| 360| 387| 414| 439
109| 188| 205| 221| 237| 253| 275| 296| 318| 338| 358| 385| 412| 437
105| 186| 203| 219| 235| 251| 273| 294| 316| 336| 356| 383| 410| 435
Cooling Mode| 16 SEER R410A HP Charge Chart 5 TON(Cooling mode)
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value (psig)
Suction Pressure at Large Service Valve (psig)| 165| | | 254| 274| 291| 309| 329| 350| 370| 398| 421| 447| 472
161| | | 252| 271| 289| 306| 327| 348| 368| 396| 419| 445| 470
157| | | 250| 268| 287| 304| 325| 346| 366| 394| 417| 443| 468
153| | 229| 248| 266| 285| 302| 323| 344| 364| 392| 415| 441| 466
149| | 227| 246| 264| 283| 300| 321| 342| 362| 390| 413| 439| 464
145| | 225| 244| 262| 281| 298| 319| 340| 360| 388| 411| 437| 462
141| 205| 224| 242| 260| 279| 296| 317| 338| 358| 386| 409| 435| 460
137| 202| 222| 240| 258| 277| 294| 315| 336| 356| 384| 407| 433| 458
133| 199| 220| 238| 256| 275| 292| 313| 334| 354| 382| 405| 431| 456
129| 197| 218| 236| 254| 273| 290| 311| 332| 352| 380| 403| 429| 454
125| 195| 216| 234| 252| 271| 288| 310| 330| 350| 378| 401| 427| 452
121| 193| 214| 232| 250| 269| 286| 308| 328| 348| 376| 399| 425| 450
117| 191| 212| 230| 248| 267| 284| 306| 326| 346| 374| 397| 423| 448
113| 189| 210| 228| 246| 265| 282| 304| 324| 344| 372| 395| 421| 446
109| 187| 208| 226| 244| 263| 280| 302| 322| 342| 370| 393| 419| 444
105| 185| 206| 224| 242| 261| 278| 300| 320| 340| 368| 391| 417| 442

Add refrigerant if the design liquid line pressure is lower than the chart value.

  • Connect gages to refrigerant bottle and unit as illustrated (Figure 40).
  • Purge all hoses.
  • Open bottle.
  • Stop adding refrigerant when liquid line pressure matches the
  • Refrigerant Charging Chart.

Recover refrigerant if the design liquid line pressure is lower than the chart value.

Stabilize the system.

  • Wait 20 minutes for the system condition to stabilize between adjustments.
  • When the liquid line pressure match the chart, the system is properly charged.
  • Remove gages.
  • Replace service port caps to prevent leaks. Tighten finger tight plus an additional 1/6 turn.

Record system Information for reference (Table 8).
Record system pressures and temperatures after charging is complete.

Description Value
Outdoor model number °F
Measured Outdoor Ambient °F
Measured Indoor Ambient PSIG
Liquid Gage Pressure PSIG
Suction Gage Pressure

System operation and troubleshooting

15.1 Compressor crankcase heater (CCH) (Heat pump only)
The crankcase heating start must meet two conditions:
A. Outdoor temperature<41°F
B. At power up or if the compressor has been off for more than 3 hours
The crankcase heating stop must meet the following condition: Outdoor temperature>44.6°F or compressor starts.
15.2 Reversing valve (Heat pump only)
Reversing valve energizes at the heating conditions, and cuts off at the cooling condition.
15.3 Protection function (Heat pump only)
T3 = Outdoor Coil Temperature
T3>143.6°F, compressor stops working
T3<125.6°F, compressor restarts working
T4 = Out Ambient Temperature
T4 < 5°F, compressor stops working
T4 > 10.4°F, compressor restarts working
When T4< 5°F, the outdoor unit would provide a signal to drive up the heater installed in the indoor unit.

  • Discharge temperature protection
    Discharge temperature > 275°F, compressor stops working.
    Discharge temperature < 194°F, compressor restarts working.

  • High pressure protection
    High pressure > 638 PSIG, compressor and outdoor fan motor stop working.
    High pressure < 464 PSIG, compressor and outdoor fan motor restart working (3 minutes delay necessary).

  • Low pressure protection
    Low pressure < 21 PSIG, compressor and outdoor fan motor stop working.
    Low pressure > 44 PSIG, compressor and outdoor fan motor restart working (3 minutes delay necessary).

In stand-by status, the compressor will not start in low pressure protection. Within 30 minutes, if 4 protection cycles occur. The system will be locked. It will be restore after power cycle.
15.4 Protection function (Air conditioner only)
High pressure protection
High pressure > 638 PSIG, compressor and outdoor fan motor stop working.
High pressure < 464 PSIG, compressor and outdoor fan motor restart working (3 minutes delay necessary).

15.5 Defrost mode (Heat pump only)
Manual defrost mode
When the switch SW3-1 is set to “ON”, the system turns to the defrost mode. The defrost mode exits by the logic of shut-down conditions of defrost mode.TRANE R410A Split System Air Conditioner and Heat Pump - Figure
41

15.6 Temperature sensor resistance table

Temperature °F| Resistance kΩ| Temperature °F| Resistance kΩ| Temperature °F| Resistance kΩ| Temperature °F| Resistance kΩ
---|---|---|---|---|---|---|---
-4| 106.73| 37| 29.87| 78| 10.00| 119| 3.69
-3| 103.25| 38| 29.22| 79| 9.50| 120| 3.61
-2| 99.89| 39| 28.19| 80| 9.26| 121| 3.53
-1| 96.65| 40| 27.39| 81| 9.03| 122| 3.45
0| 93.53| 41| 26.61| 82| 8.81| 123| 3.38
1| 90.53| 42| 25.85| 83| 8.59| 124| 3.30
2| 87.62| 43| 25.12| 84| 8.38| 125| 3.23
3| 84.83| 44| 24.42| 85| 8.17| 126| 3.16
4| 82.13| 45| 23.73| 86| 7.97| 127| 3.10
5| 79.52| 46| 23.07| 87| 7.78| 128| 3.03
6| 77.01| 47| 22.42| 88| 7.59| 129| 2.96
7| 74.58| 48| 21.80| 89| 7.40| 130| 2.90
8| 72.24| 49| 21.20| 90| 7.22| 131| 2.84
9| 69.98| 50| 20.61| 91| 7.05| 132| 2.78
10| 67.80| 51| 20.04| 92| 6.88| 133| 2.72
11| 65.69| 52| 19.49| 93| 6.72| 134| 2.67
12| 63.65| 53| 18.96| 94| 6.56| 135| 2.61
13| 61.68| 54| 18.44| 95| 6.40| 136| 2.56
14| 59.78| 55| 17.94| 96| 6.25| 137| 2.50
15| 57.95| 56| 17.45| 97| 6.10| 138| 2.45
16| 56.17| 57| 16.98| 98| 5.96| 139| 2.40
17| 54.46| 58| 16.52| 99| 5.82| 140| 2.35
18| 52.80| 59| 16.08| 100| 5.68| 141| 2.30
19| 51.20| 60| 15.65| 101| 5.55| 142| 2.25
20| 49.65| 61| 15.23| 102| 5.42| 143| 2.21
21| 48.16| 62| 14.83| 103| 5.30| 144| 2.16
22| 46.71| 63| 14.43| 104| 5.18| 145| 2.12
23| 45.31| 64| 14.05| 105| 5.06| 146| 2.08
24| 43.95| 65| 13.68| 106| 4.94| 147| 2.03
25| 42.64| 66| 13.32| 107| 4.83| 148| 1.99
26| 41.38| 67| 12.97| 108| 4.72| 149| 1.95
27| 40.15| 68| 12.64| 109| 4.61| 150| 1.91
28| 38.97| 69| 12.31| 110| 4.51| 151| 1.88
29| 37.82| 70| 11.99| 111| 4.41| 152| 1.84
30| 36.71| 71| 11.68| 112| 4.31| 153| 1.80
31| 35.64| 72| 11.38| 113| 4.21| 154| 1.77
32| 34.60| 73| 11.09| 114| 4.12| 155| 1.73
33| 33.59| 74| 10.80| 115| 4.03| 156| 1.70
34| 32.61| 75| 10.53| 116| 3.94| 157| 1.66
35| 31.67| 76| 10.00| 117| 3.85| 158| 1.63
36| 30.76| 77| 10.00| 118| 3.77| 159| 1.60

15.5  Electrical data table

TRANE R410A Split System Air Conditioner and Heat Pump -
tarboshooting

C- Cooling H – Heating P – Primary Causes S – Secondary Causes

Warranty

Assist owner with processing Warranty cards and/or online registration.
16.1 Maintenance
Dirt should not be allowed to accumulate on the indoor or outdoor coils or other parts in the air circuit. Clean as often as necessary to keep the unit clean. Use a brush, vacuum cleaner attachment or other suitable means.
The outdoor fan motor is permanently lubricated and does not require periodic oiling.
Refer to the furnace or air handler instructions for filter and blower motor maintenance.
The indoor coil and drain pan should be inspected and cleaned regularly to assure proper drainage.
It is unlawful to knowingly vent, release or discharge refrigerant into the open air during repair, service, maintenance or the final disposal of this unit. When the system is functioning properly and the owner has been fully instructed, secure the owner’s approval.
16.2 Changing motor
When motor requires changing, follow the steps below:
STEP 1 – Go into electrical panel, disconnect motor power lines.
Note: Disconnect main power to unit. Severe burns and electrical shock will occur if you do not disconnect main power.
STEP 2 – Remove cover (be careful of motor wires).
STEP 3 – Be sure to place fan cover unit on the ground (Figure 43).
Note: Do not place or lean fan blades on ground or against surface.
STEP 4 – Remove fan motor by removing 5/16″ nuts from cover.
STEP 5 – Remove fan blade from motor by removing 1/2″ nut and place fan on the ground.
STEP 6 – Reverse removal process to reinstall the fan and motor.
Note: When connecting motor wires be sure to check motor direction.
Damage will occur to condenser unit if you remove 5/16’’ nuts prior to cover removal.

TRANE R410A Split System Air Conditioner and Heat Pump - Figure
42

Wiring diagrams

17.1 For 18K-48K HP System 17.2 For 60K HP System

TRANE R410A Split System Air Conditioner and Heat Pump - Figure
43| TRANE R410A Split System Air
Conditioner and Heat Pump - Figure 44
17.3 For 18K-36K AC System| 17.4 For 42K-60K AC System
TRANE R410A Split System Air Conditioner and Heat Pump - Figure
45| TRANE R410A Split System Air
Conditioner and Heat Pump - Figure 46

Matching table and Checkout Procedures

18.1 Matching table

Condensing Unit| Air Handle/A-Coil| Piston Size/TXV Valve Model| SEER| If P reinstalled Piston Replace Required
---|---|---|---|---
J4AC6018A1000M| J4AH4E36A1 BOOM| 52| 16| YES
J4AC6024A1000M| J4AH4E36A1 BOOM| 58| 16| YES
J4AC6030A1000M| J4AH4E36A1 BOOM| 65| 16| YES
J4AC6036A1000M| J4AH4E60A1COOAA| 73| 16| YES
J4AC6042A1000M| J4AH4E60A1COOAA| 75| 16| YES
J4AC6048A1000M| J4AH4E60A1COOAA| 80| 16| YES
J4AC6060A1000M| J4AH4E60A1COOAA| 4AYTXVH3G6000A| 15| YES
J4HP6018A1000M| J4AH4E36A1BOOM| 52| 16| YES
J4HP6024A1000M| J4AH4E36A1BOOM| 58| 16| YES
J4HP6030A1000M| J4AH4E36A1BOOM| 4AYTXVH3G2436A| 16| YES
J4HP6036A1000M| J4AH4E60A1COOAA| 70| 16| YES
J4HP6042A1000M| J4AH4E60A1COOAA| 4AYTXVH3G4248A| 16| YES
J4HP6048A1000M| J4AH4E60A1COOAA| 4AYTXVH3G6000A| 16| YES
J4HP6060A1000M| J4AH6E60A1COOAA| 4AYTXVH3G6000A| 15| YES

Note: Since the manufacturer has a policy of continuous product and product data improvement, if the system combination you are looking for is not listed, check for the latest version of this document at www.oxboxhvac.com.
18.2 Operational and Checkout Procedures
Final phases of this installation are the unit Operational and Checkout Procedures. To obtain proper performance, all units must be operated and charge adjustments made in accordance with procedures found in the Service Facts of the Outdoor Unit.
After installation has been completed, it is recommended that the entire system be checked against the following list:

  1. Be sure unit suspension(if used) is secure and that there are no tools or loose debris in or around or on top of the unit…………………………….. [ ]
  2. Properly insulate suction lines and fittings………… [ ]
  3. Properly secure and isolate all refrigerant lines… [ ]
  4. Verify that all electrical connections are tight. ….. [ ]
  5. Check all duct outlets; they must be open and unrestricted. ….. [ ]
  6. Check drain lines and be sure all joints are tight…………… [ ]
  7. Be sure that a return air filter is installed……………………… [ ]
  8. Operate complete system in each mode to verify proper performance. Verify operation of supplementary electric heater. …………………………..[]

BX-SVN-J4ACHP6-1A-EN

Documents / Resources

| TRANE R410A Split System Air Conditioner and Heat Pump [pdf] Installation Guide
R410A, R410A Split System Air Conditioner and Heat Pump, Split System Air Conditioner and Heat Pump, System Air Conditioner and Heat Pump, Air Conditioner and Heat Pump, Heat Pump, Pump
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Trane User Manuals

Related Manuals