TRANE R410A Split System Air Conditioner and Heat Pump Installation Guide
- June 12, 2024
- Trane
Table of Contents
- R410A Split System Air Conditioner and Heat Pump
- Key to symbols and safety instructions
- Unit location considerations
- Unit preparation
- Setting up the unit
- Refrigerant line considerations
- Refrigerant line routing
- Refrigerant line brazing
- Refrigerant line leak check
- Evacuation
- Service valves
- Electrical – low voltage
- Electrical – high voltage
- Start up
- System charge adjustment
- System operation and troubleshooting
- Warranty
- Wiring diagrams
- Matching table and Checkout Procedures
- Documents / Resources
INSTALLATION INSTRUCTIONS
16 SEER
Split System Air Conditioner & Heat Pump
1.5-5 Tons
R410A
NOTE : Appearance of unit may vary.
R410A Split System Air Conditioner and Heat Pump
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION
WARNING
These instructions are intended as an aid to qualified licensed service
personnel for proper installation, adjustment and operation of this unit. Read
these instructions thoroughly before attempting installation or operation.
Failure to follow these instructions may result in improper installation,
adjustment, service or maintenance possibly resulting in fire, electrical
shock, property damage, personal injury or death.
DO NOT DESTROY THIS MANUAL
Please read carefully and keep in a safe place for future reference by a
serviceman.
All phases of this installation must comply with NATIONAL, STATE, AND LOCAL
CODES.
Key to symbols and safety instructions
1.1 Key to symbols
Warnings in this document are identified by a warning triangle. Keywords
at the start of a warning indicate the type and seriousness of the ensuing
risk if measures to prevent the risk are not taken.
This symbol indicates important information where there is no risk to people
or property.
The following keywords are defined and can be used in this document:
DANGER indicates a hazardous situation which, if not avoided, will result
in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, could
result in minor to moderate injury.
NOTICE is used to address practices not related to personal injury.
1.2 Safety
CAUTION:
This document is customer property and is to remain with this unit. Please
return to service information pack upon completion of work.
These instructions do not cover all variations in systems or provide for every
possible contingency to be met in connection with the installation.
Should further information be desired or should particular problems arise
which are not covered sufficiently for the purchaser’s purposes, the matter
should be referred to your installing dealer or local distributor.
This document contains a wiring diagram and service information.
CAUTION:
This information is intended for use by individuals possessing adequate
backgrounds of electrical and mechanical experience. Any attempt to repair a
central air conditioning product may result in personal injury and/or property
damage.
WARNING: HAZARDOUS VOLTAGE
Failure to follow this warning could result in property damage, severe
personal injury or death.
Disconnect all electric power, including remote disconnects before servicing.
Follow proper lockout/tagout procedures to ensure the power cannot be
inadvertently energized.
WARNING: REFRIGERANT OIL
These units use R-410A refrigerant which operates at 50% to 70% higher
pressures than R-22. Use only R-410A approved service equipments. Refrigerant
cylinders are painted a “Rose” color to indicate the type of refrigerant and
may contain a “dip” tube to allow for charging of liquid refrigerant into the
system. All R-410A systems use a POE oil that readily absorbs moisture from
the atmosphere. To limit this “hygroscopic” action, the system should remain
sealed whenever possible. If a system has been opening to the atmosphere for
more than 4 hours, the compressor oil must be replaced. Never break a vacuum
with air and always change the driers when opening the system for component
replacement.
CAUTION: HOT SURFACE
May cause minor to severe burning. Failure to follow this Caution could result
in property damage or personal injury. Do not touch the top of compressor.
CAUTION: CONTAINS REFRIGERANT
Failure to follow proper procedures can result in personal illness or injury
or severe equipment damage. System contains oil and refrigerant under high
pressure. Recover refrigerant to relieve pressure before opening system.
CAUTION: GROUNDING REQUIRED
Failure to inspect or use proper service tools may result in equipment damage
or personal injury. Reconnect all grounding devices. All parts of this product
that are capable of conducting electrical current are grounded. If grounding
wires, screws, straps, clips, nuts or washers used to complete a path to
ground are removed for service, they must be returned to their original
position and properly fastened.
WARNING: SERVICE VALVES
Failure to follow this warning will result in abrupt release of system charge
and may result in personal injury and/or property damage. Extreme caution
should be exercised when opening the Liquid Line Service Valve. Turn valve
stem counterclockwise only until the stem contacts the rolled edge. No torque
is required.
WARNING: BRAZING REQUIRED
Failure to inspect lines or use proper service tools may result in equipment
damage or personal injury. All outdoor unit and evaporator coil connections
are copper-to-copper and should be brazed with a phosphorous’s-copper alloy
material such as Silfos-5 or equivalent. Do not use soft solder.
WARNING: HIGH CURRENT LEAKAGE
Failure to follow this warning could result in property damage, severe
personal injury or death. Grounding is essential before connecting electrical
supply.
Unit location considerations
2.1 Unit dimensions
Unit Dimensions|
---|---
Model| H(Inchs)| W(Inchs)| L(Inchs)
AC| HP
18| 18/24| 24-15/16| 23-5/8| 23-5/8
24| 30| 24-15/16| 28| 28
30| 36| 24-15/16| 29-1/8| 29-1/8
/| 42| 33-3/16| 28| 28
36/42/48/60| 48/60| 33-3/16| 29-1/8| 29-1/8
Table 1
The unit’s weight value is on the cardboard box.
When mounting the outdoor unit on a roof, be sure the roof will support the
unit’s weight. Properly selected isolation is recommended to prevent sound or
vibration transmission to the building structure.
2.2 Location restrictions
Ensure the top discharge area is unrestricted for at least 60 inches above the
unit.
Do not locate outdoor unit near bedrooms since normal operational sounds may
be objectionable.
Position unit to allow adequate space for unobstructed airflow, wiring,
refrigerant lines, and serviceability.
Maintain a distance of 24 inches between units.
24 inches clearance must be provided in front of the control box (access
panels) and any other side requiring service.
Position unit where water, snow or ice from roof or overhang cannot fall
directly on unit.
Position the outdoor unit a minimum of 12’’ from any wall or surrounding
shrubbery to ensure adequate airflow.
See Figure 2 and Figure 3.
Cold climate considerations (heat pump only)
Precautions must be taken for units being installed in areas where snow
accumulation and prolonged below-freezing temperatures occur.
Units should be elevated 3-12 inches above the pad or rooftop, depending on
local weather. This additional height will allow drainage of snow and ice
melted during defrost cycle prior to its refreezing. Ensure that drain holes
in unit base pan are not obstructed, preventing drainage of defrost water
(Figure 4).
If possible, avoid locations that are likely to accumulate snow drifts.
If not possible, a snow drift barrier should be installed around the unit to
prevent a build-up of snow on the sides of the unit.
Unit preparation
3.1 Pre-installation
STEP 1 – Check for damage and report promptly to the carrier any damage found
to the unit (Figure 5).
STEP 2 – Instruments must be designed to install/serve R410A equipmens.
- Gauge sets, hoses, refrigerant containers and recovery system must be designed to handle the POE type oils.
- Manifold sets should be 800 PSIG high side and 250 PSIG low side.
- All hoses must have a 700 PSIG service pressure rating.
- Leak detectors should be disigned to detect R410A.
- Recovery equipments (including refrigerant recovery containers) must be specifically designed to handle R410A.
- Do not use an R22 TXV.
Setting up the unit
4.1 Pad installation
When installing the unit on a support pad, such as a concrete slab, consider
the following:
- The pad must be at least 1-2” larger than the unit on all sides.
- The pad must be separate from any structure.
- The pad must be level.
- The pad must be high enough above grade to allow for drainage.
- The pad location must comply with National, State and Local codes.
These instructions are intended to provide a method to tie-down system to concrete slab as a securing procedure for high wind areas. Check Local Codes for tie-down methods and protocols.
Refrigerant line considerations
5.1 Service valve connection sizes
Model | Suction line connection | Liquid line connection |
---|---|---|
AC | HP | |
18 | 18 | 3/4 |
24 | 24 | 3/4 |
30 | 30 | 3/4 |
36 | 36 | 3/4 |
/ | 42 | 3/4 |
42 | / | 7/8 |
48 | 48 | 7/8 |
60 | 60 | 7/8 |
5.2 Refrigerant line sizes
Model | Suction | line | Liquid | line |
---|---|---|---|---|
optional | standard | optional | standard | |
18 | 5/8 | 3/4 | 5/16 | 3/8 |
24 | 5/8 | 3/4 | 5/16 | 3/8 |
30 | 5/8 | 3/4 | 5/16 | 3/8 |
36 | 5/8 | 3/4 | 5/16 | 3/8 |
42 | 3/4 | 7/8 | 5/16 | 3/8 |
48 | 7/8 | 1-1/8 | 1/2 | 3/8 |
60 | 7/8 | 1-1/8 | 1/2 | 3/8 |
5.3 Refrigerant piping limits and required refrigerant line length
Model | Liquid line (Inches) | Total equivalent length(Feet) |
---|---|---|
25 | 50 | 75 |
Maximum vertical length(Feet)
18| 5/16| 25| 50| 60| 58| 40| 30
3/8| 25| 50| 60| 60| 40| 30
24| 5/16| 25| 36| 29| 23| 16| 9
3/8| 25| 50| 60| 60| 40| 30
30| 5/16| 25| 49| 38| 27| 17| 6
3/8| 25| 50| 60| 60| 40| 30
36| 5/16| 25| 50| 37| 22| 7| N/A
3/8| 25| 50| 60| 60| 40| 30
42| 5/16| 25| 23| 4| N/A| N/A| N/A
3/8| 25| 50| 43| 36| 30| 24
48| 1/2| 25| 50| 56| 55| 40| 30
3/8| 25| 46| 38| 30| 22| 15
60| 1/2| 25| 50| 60| 60| 40| 30
3/8| 25| 50| 56| 44| 32| 20
Model| Suction line (Inches)| Total suction line length(Feet)
---|---|---
25| 50| 100| 150
Coefficient
18| 5/8| 1.00| 0.97| 0.94| 0.90
3/4| 1.00| 0.98| 0.95| 0.92
24| 5/8| 1.00| 0.97| 0.94| 0.90
3/4| 1.00| 0.98| 0.95| 0.92
30| 5/8| 1.00| 0.97| 0.94| 0.90
3/4| 1.00| 0.98| 0.96| 0.93
36| 5/8| 1.00| 0.97| 0.94| 0.90
3/4| 1.00| 0.99| 0.97| 0.96
42| 3/4| 1.00| 0.98| 0.97| 0.95
7/8| 1.00| 0.99| 0.98| 0.97
48| 7/8| 1.00| 0.98| 0.97| 0.96
1-1/8| 1.00| 0.99| 0.98| 0.97
60| 7/8| 0.99| 0.98| 0.94| 0.90
1-1/8| 1.00| 0.99| 0.98| 0.97
Table 5 Suction line length/size VS capacity multiplier
Using suction line larger than shown in chart will result in poor oil return
and is not recommended.
For example: the system capacity published in AHRI is 17800 Btu/h. This data
is based on the AHRI test condition and 25 feet line set with standard suction
tube size (3/4″ tube). If you need to add the line set more than 25 feet or
use the optional suction tube size, you need to recalculate the capacity with
the coefficient in the table. For 50 feet line and 5/8″ suction tube, the
capacity will be 17800*0.97=17266 Btu/h.
Determine required line length and lift. You will need this later in Section
14.
Total Line Length = __ Feet.
Total Vertical Change(Lift) = __ Feet.
5.4 Refrigerant line insulation
The suction line must always be insulated. DO NOT allow the Liquid Line and
Suction Line to come in direct (metal to metal) contact.
5.5 Reuse existing refrigerant lines
CAUTION:
If using existing refrigerant lines make certain that all joints are brazed,
not soldered.
For retrofit applications, where the existing refrigerant lines will be used,
the following precautions should be taken:
Ensure that the refrigerant lines are the correct size. Refer to Section
5.1 listed and Table 3.
Ensure that the refrigerant lines are free of leaks, acid, and oil.
The manufacturer recommends installing only approved matched indoor and
outdoor systems. All of the manufacturer’s split systems are AHRI certified.
Some of the benefits of installing approved matched indoor and outdoor split
systems are maximum efficiency, optimum performance and the best overall
system reliability.
Refrigerant line routing
6.1 Precautions
Take precautions to prevent noise within the building structure due to
vibration transmission from the refrigerant lines. For example:
- When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type hangers.
- Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
- Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
- Isolate the lines from all ductwork.
- Minimize the number of 90º turns.
- Use PVC piping as a conduit for all underground installations as shown in Figure 15. Buried lines should be keep as short as possible.
- The lines should not obstruct service access to the coil, air handling system or filter.
- Care must also be taken to isolate the refrigerant lines to minimize noise transmission from the equipment to the structure.
Comply with National, State, and Local Codes when isolating line sets from joists, rafters, walls or other structural elements.
Refrigerant line brazing
7.1 Braze the refrigerant lines
-
Remove caps or plugs. Use a deburring tool to deburr the pipe ends.
Clean both internal and external surfaces of the tubing using an emery cloth. -
Remove the pressure tap cap from both service valves.
-
Purge the refrigerant lines and indoor coil with dry nitrogen.
-
Wrap a wet rag around the valve body to avoid heat damage and continue the dry nitrogen purge (Figure 19).
Braze the refrigerant lines to the service valves.
Check liquid line filter drier’s directional flow arrow to confirm correct direction of refrigeration flow (away from outdoor unit and toward evaporator coil) as illustrated. Brazing the filter drier to the Liquid Line.
Continue the dry nitrogen purge. Do not remove the wet rag until all brazing is completed.
Remove the wet rag before stopping the dry nitrogen purge. -
Replace the pressure tap caps after the service valves have cooled.
Note: Do not over tighten (between 40 and 60 inch-lbs. maximum).
Refrigerant line leak check
8.1 Check for leaks
- Pressurize the refrigerant lines and evaporator coil to 150 PSIG using dry nitrogen.
- Check for leaks by using a soapy solution or bubbles at each brazed location.
Remove nitrogen pressure and repair any leaks before continuing.
Evacuation
9.1 Evacuate the refrigerant lines and indoor coil
Do not open the service valves until the refrigerant lines and indoor coil
leak check and evacuation are complete.
-
Evacuate until the micron gauge reads no higher than 350 microns, then close off the valve to the vacuum pump.
-
Observe the micron gauge. Evacuation is complete if the micron gauge does not rise above 500 microns in one (1) minute.
Once evacuation is complete blank off the vacuum pump and micron gauge, and close the valves on the manifold gauge set.
Service valves
10.1 Open the service valves
WARNING:
Extreme caution should be exercised when opening the Liquid Line Service
Valve. Turn counterclock wise until the valve stem just touches the rolled
edge. No torque is required. Failure to follow this warning will result in
abrupt release of system charge and may result in personal injury and /or
property damage. Leak check and evacuation must be completed before opening
the service valves.
- Remove service valve cap (Figure 25).
- Fully insert hex wrench into the stem and back out counterclockwise until valve stem just touches the rolled edge.
- Replace the valve stem cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
Electrical – low voltage
11.1 Low Voltage Maximum Wire Length
Table 6 defines the maximum total length of low voltage wiring from the
outdoor unit to the indoor unit and to the thermostat.
24 Volts – Wire size | Max. wire length |
---|---|
18 AWG | 150 Ft. |
16 AWG | 225 Ft. |
14 AWG | 300 Ft. |
11.2 Low voltage hook-up diagrams
Notes:
“ ” The electric auxiliary heat connection(optional).
W : Electric auxiliary heat signal.
W1 : The first Electric auxiliary heat signal.
W2 : The second Electric auxiliary heat signal.
Notes:
“___ ” The electric auxiliary heat connection(option).
W : Electric auxiliary heat signal.
W1 : The first Electric auxiliary heat signal.
W2 : The second Electric auxiliary heat signal.
D signal is connect to the Electric auxiliary heat or the first Electric
auxiliary heat.
“”: Outdoor unit signal. Only for single-stage compressor systems.
Notes:
“ ” The electric auxiliary heat connection(option).
W : Electric auxiliary heat signal,connect to the Electric auxiliary heat or
the first Electric auxiliary heat.
W1 : The first Electric auxiliary heat signal.
W2 : The second Electric auxiliary heat signal.
Electrical – high voltage
12.1 High voltage power supply
WARNING: LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and trouble shooting of this product,
it may be necessary to work with live electrical components.
Failure to follow all electrical safety precautions when exposed to live
electrical components could result in death or serious injury.
The high voltage power supply must agree with the equipment nameplate.
Power wiring must comply with National, State and Local Codes.
Follow instructions on unit wiring diagram located on the inside of the access
panel.
12.2 High voltage disconnect switch
Install a separate disconnect switch at the outdoor unit.
Field provided flexible electrical conduit must be used for high voltage
wiring.
12.3 High voltage ground
Ground the outdoor unit per National, State and Local Code requirements.
Start up
13.1 System start up
- Ensure Sections 7, 8, 9, 10, 11 and 12 have been completed.
- Set System Thermostat to OFF.
- Turn on disconnect to apply power to the indoor and outdoor units.
- Wait one (1) hour before starting the unit if compressor crankcase heater is used and the outdoor ambient temperature is below 70 ºF.
- Set system thermostat to ON.
System charge adjustment
14.1 Charging: Weigh-In Method
Weigh-In Method can be used for the initial installation, or anytime a system
charge is being replaced. Weigh-In Method can also be used when power is not
available to the equipment site or operating conditions (indoor/outdoor
temperatures) are not in range to verify with the liquid line pressure
charging method.
Model | Factory Charge | Charge multiplier for liquid line length |
---|---|---|
All models | The data on nameplate | 5/16″ |
0.4 oz/ft | 0.6 oz/ft | 1.2 oz/ft |
The factory charge in the outdoor unit is sufficient for 15 feet of standard
size interconnecting liquid line.
New Installations — Calculating additional charge for lineset greater than 15
feet.
- Total Line Length (ft)= (a)
- Standard Line set (ft)= 15 (b)(a) minus (b)
- Refrigerant Multiplier = (c)
- Refrigerant Adder (cd) = (d)= (e)
- *If lineset is less than 15 feet, (e) = 0
Sealed-System Repairs — Calculating total system charge.
- Total Line Length (ft)=__ (a)
- Standard Line set (ft)= __15 (b)
- (a) minus (b)= (c)=__ (d)
- Refrigerant Multiplier= __(e*)
- Refrigerant Adder (c*d)= __(f)
- Factory Charge (nameplate)
- Total System Charge (e+f)
*If line set is less than 15 feet, (e) = 0
The only mode approved for validating system charge is while in Cooling Mode.
Outdoor Temperature must be between 55°F and 115°F with Indoor Temperature
kept between 70°F and 80°F.
14.2 Liquid line pressure charging and refrigerant adjustment in cooling
(above 55°F outdoor temp.)
• For 5 TON AC unit,the Outdoor Temperature must be between 65°F and 105°F
-
Check the outdoor ambient temperatures.
Liquid line pressure (in cooling mode) is the only recommended method of charging above 55ºF outdoor ambient temperatures.
For outdoor ambient temperatures below 55ºF , use weigh-in charge method.
Note: It is important to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient temperature is above 55ºF. For best results the indoor temperature should be kept between 70ºF to 80ºF. Note: The temperature tolerance for actual approach is ± 3ºF. -
Ensure Sections 7, 8, 9, 10,11,12 and 13 have been completed.
-
Stabilize the system by operating for a minimum of 20 minutes.
At startup, or whenever charge is removed or added, the system must be operated for a minimum of 20 minutes to stabilize before accurate measurements can be made. Note:The pressure tolerance for actual approach is ± 5psig -
Calculate liquid line pressure (According to Refrigerant Charging Chart)
• Measured Suction Line Pressure = ____PSIG
• Outdoor Ambient Temperature = ___ ºF
• Calculate Liquid Line Pressure = ____PSIG
REFRIGERANT CHARGING CHART FOR AC SYSTEM
Cooling Mode | 16 SEER R410A AC Charge Chart 1.5 TON |
---|
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90|
95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value (psig)
Suction Pressure at Large Service Valve(psig)| 165| | | 252|
269| 286| 306| 326| 350| 373| 395| 419| 442| 467
161| | | 250| 267| 284| 304| 324| 348| 371| 393| 417| 440| 464
157| | | 248| 265| 282| 302| 322| 345| 368| 390| 414| 437| 461
153| | 228| 244| 262| 280| 300| 320| 342| 365| 387| 411| 435| 459
149| | 226| 242| 260| 277| 298| 318| 339| 362| 385| 409| 432| 457
145| | 224| 240| 258| 275| 296| 316| 337| 360| 382| 406| 430| 455
141| 205| 222| 238| 255| 272| 293| 314| 334| 357| 380| 404| 428| 453
137| 203| 220| 236| 253| 269| 291| 312| 332| 355| 377| 402| 426| 451
133| 201| 218| 234| 250| 266| 288| 310| 330| 353| 375| 400| 424| 449
129| 199| 216| 232| 248| 264| 286| 308| 328| 351| 374| 398| 422| 447
125| 198| 214| 230| 246| 262| 284| 306| 326| 349| 372| 396| 420| 445
121| 196| 212| 228| 244| 260| 282| 304| 324| 347| 370| 394| 418| 443
117| 194| 210| 226| 242| 258| 280| 302| 322| 345| 367| 392| 416| 441
113| 192| 208| 224| 240| 256| 278| 300| 320| 343| 365| 390| 414| 439
109| 190| 206| 222| 238| 254| 276| 298| 318| 340| 362| 387| 412| 437
105| 188| 204| 220| 236| 252| 273| 295| 316| 338| 360| 385| 410| 435
Cooling Mode| 16 SEER R410A AC Charge Chart 2 TON
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90|
95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value(psig)
Suction Pressure
at Large Service Valve(psig)
| 165| | | 258| 277| 295| 316| 337| 358| 382| 405| 430| 454| 479
161| | | 256| 275| 293| 314| 335| 356| 380| 403| 428| 452| 477
157| | | 254| 273| 291| 312| 333| 354| 378| 401| 426| 450| 475
153| | 236| 252| 271| 289| 310| 331| 352| 376| 399| 424| 448| 473
149| | 234| 250| 269| 287| 308| 329| 350| 374| 397| 422| 446| 471
145| | 232| 248| 267| 285| 306| 327| 348| 372| 395| 419| 443| 469
141| 214| 230| 246| 265| 283| 304| 325| 346| 370| 393| 417| 441| 467
137| 212| 228| 244| 262| 280| 301| 322| 343| 367| 391| 415| 439| 465
133| 210| 226| 242| 260| 278| 299| 320| 341| 365| 389| 413| 437| 463
129| 208| 224| 240| 258| 276| 297| 318| 339| 363| 387| 411| 435| 461
125| 206| 222| 238| 256| 274| 295| 316| 337| 361| 385| 409| 433| 459
121| 204| 220| 236| 254| 272| 293| 314| 335| 359| 383| 407| 431| 457
117| 202| 218| 234| 252| 270| 291| 312| 333| 357| 381| 405| 429| 455
113| 199| 216| 232| 250| 268| 289| 310| 331| 355| 379| 403| 427| 453
109| 197| 214| 230| 248| 266| 287| 308| 329| 353| 377| 401| 425| 451
105| 195| 212| 228| 246| 264| 285| 306| 327| 351| 375| 399| 423| 449
Cooling Mode| 16 SEER R410A AC Charge Chart 2.5 TON
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90|
95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value (psig)
165| | | 261| 280| 299| 319| 340| 360| 382| 404| 431| 457| 483|
161| | | 259| 278| 297| 317| 338| 358| 380| 401| 428| 455| 481|
157| | | 257| 276| 295| 315| 336| 356| 377| 398| 426| 453| 479|
153| | 240| 255| 274| 293| 313| 333| 353| 375| 396| 424| 451| 477|
149| | 238| 253| 272| 291| 311| 331| 351| 373| 394| 422| 449| 475|
145| | 236| 251| 270| 289| 309| 329| 349| 371| 392| 420| 447| 473|
141| 218| 234| 249| 268| 287| 307| 327| 347| 369| 390| 418| 445| 471|
137| 216| 232| 247| 266| 285| 305| 325| 345| 367| 388| 416| 443| 469|
133| 214| 230| 245| 264| 283| 303| 323| 343| 364| 385| 413| 441| 467|
129| 212| 228| 243| 262| 281| 301| 321| 341| 362| 383| 411| 439| 465|
125| 210| 226| 241| 260| 279| 299| 319| 339| 360| 381| 409| 437| 463|
121| 207| 223| 239| 258| 277| 297| 317| 337| 358| 379| 407| 435| 461|
117| 204| 221| 237| 256| 275| 295| 315| 335| 356| 377| 405| 433| 459|
113| 202| 219| 235| 254| 273| 293| 313| 333| 354| 375| 403| 431| 457|
109| 200| 217| 233| 252| 271| 291| 311| 331| 352| 373| 401| 429| 455|
105| 198| 215| 231| 250| 269| 289| 309| 329| 350| 371| 399| 427| 453|
Cooling Mode| 16 SEER R410A AC Charge Chart 3 TON
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90|
95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value (psig)
165| | | 259| 277| 295| 316| 337| 358| 384| 410| 435| 460| 486|
161| | | 257| 275| 293| 314| 335| 356| 382| 408| 433| 458| 484|
157| | | 255| 273| 291| 312| 333| 354| 380| 406| 431| 456| 482|
153| | 235| 253| 271| 289| 310| 331| 352| 378| 404| 429| 454| 480|
149| | 233| 251| 269| 287| 308| 329| 350| 376| 402| 427| 452| 478|
145| | 231| 249| 267| 285| 306| 327| 348| 374| 400| 425| 450| 476|
141| 214| 229| 247| 265| 283| 304| 325| 346| 372| 398| 423| 448| 474|
137| 212| 227| 245| 263| 281| 302| 323| 344| 263| 396| 263| 446| 472|
133| 210| 225| 243| 261| 279| 300| 321| 342| 368| 394| 419| 444| 470|
129| 208| 223| 241| 259| 277| 298| 319| 340| 366| 392| 417| 442| 468|
125| 206| 221| 239| 257| 275| 296| 317| 338| 364| 390| 415| 440| 466|
121| 204| 219| 237| 255| 273| 294| 315| 336| 362| 388| 413| 438| 464|
117| 202| 217| 235| 253| 271| 292| 313| 334| 360| 386| 411| 436| 462|
113| 200| 215| 233| 251| 269| 290| 311| 332| 358| 384| 409| 434| 460|
109| 198| 213| 231| 249| 267| 288| 309| 330| 356| 382| 407| 432| 458|
105| 196| 211| 229| 247| 265| 286| 307| 328| 354| 380| 405| 430| 456|
Cooling Mode| 16 SEER R410A AC Charge Chart 3.5 TON
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90|
95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value (psig)
Suction Pressure at Large Service Valve (psig)| 165| | | 258|
277| 296| 314| 332| 350| 376| 401| 427| 452| 478
161| | | 256| 275| 294| 312| 330| 348| 374| 399| 425| 450| 476
157| | | 254| 273| 292| 310| 328| 346| 372| 397| 423| 448| 474
153| | 237| 252| 271| 290| 308| 326| 344| 370| 395| 421| 446| 472
149| | 235| 250| 269| 288| 306| 324| 342| 368| 393| 419| 444| 470
145| | 233| 248| 267| 286| 304| 322| 340| 366| 391| 417| 442| 468
141| 215| 231| 246| 265| 284| 302| 320| 338| 364| 389| 415| 440| 466
137| 213| 229| 244| 263| 281| 299| 318| 336| 362| 387| 413| 438| 464
133| 211| 227| 242| 260| 278| 297| 315| 334| 360| 385| 411| 436| 462
129| 209| 225| 240| 258| 275| 294| 313| 332| 358| 383| 409| 434| 460
125| 207| 223| 238| 256| 273| 292| 311| 330| 356| 381| 407| 432| 458
121| 205| 221| 236| 254| 271| 290| 309| 328| 354| 379| 405| 430| 456
117| 202| 218| 234| 252| 269| 288| 307| 326| 352| 377| 403| 428| 454
113| 199| 216| 232| 250| 267| 286| 305| 324| 350| 375| 401| 426| 452
109| 197| 214| 230| 248| 265| 284| 303| 322| 348| 373| 399| 424| 450
105| 195| 212| 228| 246| 263| 282| 301| 320| 346| 371| 397| 422| 448
Cooling Mode| 16 SEER R410A AC Charge Chart 4 TON
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90|
95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value (psig)
Suction Pressure at Large Service Valve (psig)| 165| | | 264|
282| 300| 322| 343| 364| 388| 412| 437| 464| 491
161| | | 262| 280| 298| 320| 341| 362| 386| 410| 435| 462| 489
157| | | 260| 278| 296| 318| 339| 360| 384| 408| 433| 460| 487
153| | 239| 258| 276| 294| 316| 337| 358| 382| 406| 431| 458| 485
149| | 237| 256| 274| 292| 314| 335| 356| 380| 404| 429| 456| 483
145| | 235| 254| 272| 290| 312| 333| 354| 378| 402| 427| 454| 481
141| 215| 233| 252| 270| 288| 310| 331| 352| 376| 400| 425| 452| 479
137| 213| 231| 250| 268| 286| 308| 329| 350| 374| 398| 423| 450| 477
133| 211| 229| 248| 266| 284| 306| 327| 348| 372| 396| 421| 448| 475
129| 209| 227| 246| 264| 282| 304| 325| 346| 370| 394| 419| 446| 473
125| 207| 225| 244| 262| 280| 302| 323| 344| 368| 392| 417| 444| 471
121| 205| 223| 242| 260| 278| 300| 321| 342| 366| 390| 415| 442| 469
117| 203| 221| 240| 258| 276| 298| 319| 340| 364| 388| 413| 440| 467
113| 201| 219| 238| 256| 274| 296| 317| 338| 362| 386| 411| 438| 465
109| 199| 217| 236| 254| 272| 294| 315| 336| 360| 384| 409| 436| 463
105| 197| 215| 234| 252| 270| 292| 313| 334| 358| 382| 407| 434| 461
Cooling Mode| 16 SEER R410A AC Charge Chart 5 TON
---|---
Outdoor Ambient Temperature( oF )
65| 70| 75| 80| 85| 90| 95| 100|
105
Liquid Pressrue at Small Service Value (psig)
Suction Pressure at Large Service Valve (psig)| 165| 273| 294|
317| 339| 361| 383| 404| 431| 458
161| 271| 292| 314| 336| 358| 381| 403| 430| 457
157| 269| 289| 311| 334| 356| 379| 401| 428| 455
153| 267| 287| 308| 331| 353| 377| 400| 426| 453
149| 266| 285| 306| 328| 350| 374| 398| 424| 451
145| 264| 283| 304| 326| 348| 373| 397| 423| 450
141| 262| 281| 302| 324| 346| 371| 395| 421| 448
137| 260| 279| 300| 322| 344| 369| 393| 419| 446
133| 259| 278| 298| 320| 342| 367| 392| 418| 443
129| 257| 276| 296| 318| 340| 365| 390| 415| 440
125| 255| 274| 294| 316| 338| 363| 388| 413| 438
121| 253| 272| 292| 314| 336| 361| 386| 411| 435
117| 252| 271| 291| 313| 335| 360| 384| 409| 433
113| 250| 269| 290| 312| 334| 358| 382| 407| 431
109| 248| 268| 289| 311| 333| 357| 380| 404| 428
105| 246| 266| 288| 310| 331| 355| 378| 402| 426
REFRIGERANT CHARGING CHART FOR HP SYSTEM
Cooling Mode | 16SEER R410A HP Charge Chart 1.5TON(Cooling mode) |
---|
O u t doo r A m b i ent T
emperature( oF )
55| 60| 65| 70| 75| 80| 85| 90|
95| 100| 105| 110| 115
Liquid Pressure at Small Service Valve (psig)
Suction Pressure at Large| 165| | | 246| 265| 284| 303| 323| 343|
364| 390| 416| 441| 467
161| | | 244| 263| 282| 301| 321| 341| 362| 388| 414| 439| 465
157| | | 242| 261| 280| 299| 319| 339| 360| 386| 412| 437| 463
153| | 221| 240| 259| 278| 297| 317| 337| 358| 384| 410| 435| 461
149| | 219| 238| 257| 276| 295| 315| 335| 356| 382| 408| 433| 459
145| | 217| 236| 255| 274| 293| 313| 333| 354| 380| 406| 431| 457
141| 196| 215| 234| 253| 272| 291| 311| 331| 352| 378| 404| 429| 455
137| 195| 213| 232| 251| 269| 288| 309| 328| 350| 376| 402| 427| 453
133| 193| 211| 230| 249| 267| 286| 306| 326| 347| 373| 399| 425| 451
129| 191| 209| 228| 247| 265| 284| 304| 323| 344| 370| 397| 423| 449
125| 190| 209| 227| 245| 264| 282| 302| 320| 341| 368| 394| 421| 447
121| 190| 208| 226| 244| 262| 280| 300| 320| 341| 367| 393| 419| 445
117| 188| 206| 224| 242| 260| 278| 298| 318| 339| 365| 391| 417| 443
113| 186| 204| 222| 240| 258| 276| 296| 316| 337| 363| 389| 415| 441
109| 184| 202| 220| 238| 256| 274| 294| 314| 335| 361| 387| 413| 439
105| 182| 200| 218| 236| 254| 272| 292| 312| 333| 359| 385| 411| 437
Cooling Mode| 16SEER R410A HP Charge Chart 2TON(Cooling mode)
---|---
Outdoor Ambient Temperature( oF̧ )
55| 60| 65| 70| 75| 80| 85| 90|
95| 100| 105| 110| 115
Liquid Pressure at Small Service Valve (psig)
Suction Pressure at Large Service Valve(psig)| 165| | | 255| 274|
294| 313| 335| 358| 381| 407| 434| 461| 486
161| | | 253| 272| 292| 311| 333| 356| 379| 405| 432| 459| 484
157| | | 251| 270| 290| 309| 331| 354| 377| 403| 430| 457| 482
153| | 230| 249| 268| 288| 307| 329| 352| 375| 401| 428| 455| 480
149| | 228| 247| 266| 286| 305| 327| 350| 373| 399| 426| 453| 478
145| | 226| 245| 264| 284| 303| 325| 348| 371| 397| 424| 451| 476
141| 204| 224| 243| 262| 282| 301| 323| 346| 369| 395| 422| 449| 474
137| 203| 222| 241| 260| 279| 298| 320| 344| 367| 393| 420| 447| 472
133| 201| 220| 239| 258| 277| 296| 318| 342| 365| 391| 418| 445| 470
129| 199| 218| 237| 256| 275| 294| 316| 340| 363| 389| 416| 443| 468
125| 197| 216| 235| 254| 273| 292| 314| 338| 361| 387| 414| 441| 466
121| 195| 214| 233| 252| 271| 290| 312| 336| 359| 385| 412| 439| 464
117| 193| 212| 231| 250| 269| 288| 310| 334| 357| 383| 410| 437| 462
113| 191| 210| 229| 248| 267| 286| 308| 332| 355| 381| 408| 435| 460
109| 189| 208| 227| 246| 265| 284| 306| 330| 353| 379| 406| 433| 458
105| 187| 206| 225| 244| 263| 282| 304| 328| 351| 377| 404| 431| 456
Cooling Mode| 16SEER R410A HP Charge Chart 2.5TON(Cooling mode)
---|---
O u t doo r A m b i ent T
emperature ( o F)
55| 60| 65| 70| 75| 80| 85| 90|
95| 100| 105| 110| 115
Liquid Pressure at Small Service Valve (psig)
Suction Pressure at Large Service Valve(psig)| 165| | | 253| 269|
288| 305| 327| 348| 370| 390| 414| 435| 461
161| | | 251| 267| 286| 303| 325| 346| 368| 388| 412| 433| 459
157| | | 249| 265| 284| 301| 323| 344| 366| 386| 410| 431| 457
153| | 231| 247| 263| 282| 299| 321| 342| 364| 384| 408| 429| 455
149| | 229| 245| 261| 280| 297| 319| 340| 362| 382| 406| 427| 453
145| | 227| 243| 259| 278| 295| 317| 338| 360| 380| 404| 425| 451
141| 208| 225| 241| 257| 276| 293| 315| 336| 358| 378| 402| 423| 449
137| 206| 223| 239| 255| 274| 291| 313| 334| 356| 376| 400| 421| 447
133| 204| 221| 237| 253| 272| 289| 311| 332| 354| 374| 398| 419| 445
129| 202| 219| 235| 251| 270| 287| 309| 330| 352| 372| 396| 417| 443
125| 199| 215| 232| 249| 267| 285| 307| 328| 350| 370| 394| 415| 441
121| 195| 213| 230| 247| 267| 285| 306| 327| 348| 368| 392| 413| 439
117| 193| 211| 228| 245| 265| 283| 304| 325| 346| 366| 390| 411| 437
113| 191| 209| 226| 243| 263| 281| 302| 323| 344| 364| 388| 409| 435
109| 189| 207| 224| 241| 261| 279| 300| 321| 342| 362| 386| 407| 433
105| 187| 205| 222| 239| 259| 277| 298| 319| 340| 360| 384| 405| 431
Cooling Mode| 16SEER R410A HP Charge Chart 3TON(Cooling mode)
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90|
95| 100| 105| 110| 115
Liquid Pressure at Small Service Valve (psig)
Suction Pressure at Large Service Valve(psig)| 165| | | 260| 278|
296| 314| 336| 359| 381| 402| 427| 454| 482
161| | | 258| 276| 294| 312| 334| 357| 379| 400| 425| 452| 480
157| | | 256| 274| 292| 310| 332| 355| 377| 398| 423| 450| 478
153| | 236| 254| 272| 290| 308| 330| 352| 374| 395| 420| 448| 476
149| | 234| 252| 270| 288| 306| 328| 350| 372| 393| 418| 446| 474
145| | 232| 250| 268| 286| 304| 326| 347| 369| 390| 416| 444| 472
141| 212| 230| 248| 266| 284| 302| 323| 345| 366| 388| 413| 442| 470
137| 210| 228| 246| 264| 282| 300| 321| 342| 363| 385| 411| 439| 468
133| 208| 226| 244| 262| 280| 298| 319| 339| 360| 382| 408| 437| 466
129| 206| 224| 242| 260| 278| 296| 316| 337| 357| 379| 406| 435| 464
125| 204| 222| 240| 258| 276| 294| 314| 335| 355| 377| 404| 433| 462
121| 202| 220| 238| 256| 274| 292| 312| 333| 353| 375| 402| 431| 460
117| 200| 218| 236| 254| 272| 290| 310| 331| 351| 373| 400| 429| 458
113| 198| 216| 234| 252| 270| 288| 308| 329| 349| 371| 398| 427| 456
109| 196| 214| 232| 250| 268| 286| 306| 327| 347| 369| 396| 425| 454
105| 194| 212| 230| 248| 266| 284| 304| 325| 345| 367| 394| 423| 452
Cooling Mode| 16SEER R410A HP Charge Chart 3.5TON(Cooling mode)
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90|
95| 100| 105| 110| 115
Liquid Pressure at Small Service Valve (psig)
Suction Pressure at Large Service Valve(psig)| 165| | | 254| 271|
288| 305| 327| 348| 370| 394| 417| 441| 464
161| | | 252| 269| 286| 303| 325| 346| 368| 392| 415| 439| 462
157| | | 250| 267| 284| 301| 323| 344| 366| 390| 413| 437| 460
153| | 231| 248| 265| 282| 299| 321| 342| 364| 388| 411| 435| 458
149| | 229| 246| 263| 280| 297| 319| 340| 362| 386| 409| 433| 456
145| | 227| 244| 261| 278| 295| 317| 338| 360| 384| 407| 431| 454
141| 208| 225| 242| 259| 276| 293| 315| 336| 358| 382| 405| 429| 452
137| 206| 223| 240| 257| 274| 291| 313| 334| 356| 380| 403| 427| 450
133| 204| 221| 238| 255| 272| 289| 311| 332| 354| 378| 401| 425| 448
129| 202| 219| 236| 253| 270| 287| 309| 330| 352| 376| 399| 423| 446
125| 200| 217| 234| 251| 268| 285| 307| 328| 350| 374| 397| 421| 444
121| 198| 215| 232| 249| 266| 283| 305| 326| 348| 372| 395| 419| 442
117| 196| 213| 230| 247| 264| 281| 303| 324| 346| 370| 393| 417| 440
113| 194| 211| 228| 245| 262| 279| 301| 322| 344| 368| 391| 415| 438
109| 192| 209| 226| 243| 260| 277| 299| 320| 342| 366| 389| 413| 436
105| 190| 207| 224| 241| 258| 275| 297| 318| 340| 364| 387| 411| 434
Cooling Mode| 16 SEER R410A HP Charge Chart 4 TON(Cooling mode)
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90|
95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value (psig)
Suction Pressure at Large Service Valve (psig)| 165| | | 249|
265| 281| 302| 324| 345| 365| 385| 412| 438| 465
161| | | 247| 263| 279| 300| 322| 343| 363| 383| 410| 437| 463
157| | | 245| 261| 277| 298| 320| 341| 361| 381| 408| 435| 461
153| | 228| 243| 259| 275| 296| 318| 339| 359| 379| 406| 433| 459
149| | 226| 241| 257| 273| 294| 316| 337| 357| 377| 404| 431| 457
145| | 234| 239| 255| 271| 292| 314| 335| 355| 375| 402| 429| 455
141| 209| 223| 237| 253| 269| 290| 312| 333| 353| 373| 400| 427| 453
137| 207| 221| 235| 251| 267| 288| 310| 331| 351| 371| 398| 425| 451
133| 205| 219| 233| 249| 265| 286| 308| 329| 349| 369| 396| 423| 449
129| 203| 217| 231| 247| 263| 284| 306| 327| 347| 367| 394| 421| 447
125| 201| 215| 229| 245| 261| 282| 304| 325| 345| 365| 392| 419| 445
121| 197| 212| 227| 243| 259| 280| 302| 323| 343| 363| 390| 417| 443
117| 194| 210| 225| 241| 257| 278| 300| 321| 341| 361| 388| 415| 441
113| 190| 207| 223| 239| 255| 277| 298| 320| 340| 360| 387| 414| 439
109| 188| 205| 221| 237| 253| 275| 296| 318| 338| 358| 385| 412| 437
105| 186| 203| 219| 235| 251| 273| 294| 316| 336| 356| 383| 410| 435
Cooling Mode| 16 SEER R410A HP Charge Chart 5 TON(Cooling mode)
---|---
Outdoor Ambient Temperature( oF )
55| 60| 65| 70| 75| 80| 85| 90|
95| 100| 105| 110| 115
Liquid Pressrue at Small Service Value (psig)
Suction Pressure at Large Service Valve (psig)| 165| | | 254|
274| 291| 309| 329| 350| 370| 398| 421| 447| 472
161| | | 252| 271| 289| 306| 327| 348| 368| 396| 419| 445| 470
157| | | 250| 268| 287| 304| 325| 346| 366| 394| 417| 443| 468
153| | 229| 248| 266| 285| 302| 323| 344| 364| 392| 415| 441| 466
149| | 227| 246| 264| 283| 300| 321| 342| 362| 390| 413| 439| 464
145| | 225| 244| 262| 281| 298| 319| 340| 360| 388| 411| 437| 462
141| 205| 224| 242| 260| 279| 296| 317| 338| 358| 386| 409| 435| 460
137| 202| 222| 240| 258| 277| 294| 315| 336| 356| 384| 407| 433| 458
133| 199| 220| 238| 256| 275| 292| 313| 334| 354| 382| 405| 431| 456
129| 197| 218| 236| 254| 273| 290| 311| 332| 352| 380| 403| 429| 454
125| 195| 216| 234| 252| 271| 288| 310| 330| 350| 378| 401| 427| 452
121| 193| 214| 232| 250| 269| 286| 308| 328| 348| 376| 399| 425| 450
117| 191| 212| 230| 248| 267| 284| 306| 326| 346| 374| 397| 423| 448
113| 189| 210| 228| 246| 265| 282| 304| 324| 344| 372| 395| 421| 446
109| 187| 208| 226| 244| 263| 280| 302| 322| 342| 370| 393| 419| 444
105| 185| 206| 224| 242| 261| 278| 300| 320| 340| 368| 391| 417| 442
Add refrigerant if the design liquid line pressure is lower than the chart value.
- Connect gages to refrigerant bottle and unit as illustrated (Figure 40).
- Purge all hoses.
- Open bottle.
- Stop adding refrigerant when liquid line pressure matches the
- Refrigerant Charging Chart.
Recover refrigerant if the design liquid line pressure is lower than the chart value.
Stabilize the system.
- Wait 20 minutes for the system condition to stabilize between adjustments.
- When the liquid line pressure match the chart, the system is properly charged.
- Remove gages.
- Replace service port caps to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
Record system Information for reference (Table 8).
Record system pressures and temperatures after charging is complete.
Description | Value |
---|---|
Outdoor model number | °F |
Measured Outdoor Ambient | °F |
Measured Indoor Ambient | PSIG |
Liquid Gage Pressure | PSIG |
Suction Gage Pressure |
System operation and troubleshooting
15.1 Compressor crankcase heater (CCH) (Heat pump only)
The crankcase heating start must meet two conditions:
A. Outdoor temperature<41°F
B. At power up or if the compressor has been off for more than 3 hours
The crankcase heating stop must meet the following condition: Outdoor
temperature>44.6°F or compressor starts.
15.2 Reversing valve (Heat pump only)
Reversing valve energizes at the heating conditions, and cuts off at the
cooling condition.
15.3 Protection function (Heat pump only)
T3 = Outdoor Coil Temperature
T3>143.6°F, compressor stops working
T3<125.6°F, compressor restarts working
T4 = Out Ambient Temperature
T4 < 5°F, compressor stops working
T4 > 10.4°F, compressor restarts working
When T4< 5°F, the outdoor unit would provide a signal to drive up the heater
installed in the indoor unit.
-
Discharge temperature protection
Discharge temperature > 275°F, compressor stops working.
Discharge temperature < 194°F, compressor restarts working. -
High pressure protection
High pressure > 638 PSIG, compressor and outdoor fan motor stop working.
High pressure < 464 PSIG, compressor and outdoor fan motor restart working (3 minutes delay necessary). -
Low pressure protection
Low pressure < 21 PSIG, compressor and outdoor fan motor stop working.
Low pressure > 44 PSIG, compressor and outdoor fan motor restart working (3 minutes delay necessary).
In stand-by status, the compressor will not start in low pressure protection.
Within 30 minutes, if 4 protection cycles occur. The system will be locked. It
will be restore after power cycle.
15.4 Protection function (Air conditioner only)
High pressure protection
High pressure > 638 PSIG, compressor and outdoor fan motor stop working.
High pressure < 464 PSIG, compressor and outdoor fan motor restart working (3
minutes delay necessary).
15.5 Defrost mode (Heat pump only)
Manual defrost mode
When the switch SW3-1 is set to “ON”, the system turns to the defrost mode.
The defrost mode exits by the logic of shut-down conditions of defrost
mode.
15.6 Temperature sensor resistance table
Temperature °F| Resistance kΩ| Temperature °F| Resistance
kΩ| Temperature °F| Resistance kΩ| Temperature °F|
Resistance kΩ
---|---|---|---|---|---|---|---
-4| 106.73| 37| 29.87| 78| 10.00| 119| 3.69
-3| 103.25| 38| 29.22| 79| 9.50| 120| 3.61
-2| 99.89| 39| 28.19| 80| 9.26| 121| 3.53
-1| 96.65| 40| 27.39| 81| 9.03| 122| 3.45
0| 93.53| 41| 26.61| 82| 8.81| 123| 3.38
1| 90.53| 42| 25.85| 83| 8.59| 124| 3.30
2| 87.62| 43| 25.12| 84| 8.38| 125| 3.23
3| 84.83| 44| 24.42| 85| 8.17| 126| 3.16
4| 82.13| 45| 23.73| 86| 7.97| 127| 3.10
5| 79.52| 46| 23.07| 87| 7.78| 128| 3.03
6| 77.01| 47| 22.42| 88| 7.59| 129| 2.96
7| 74.58| 48| 21.80| 89| 7.40| 130| 2.90
8| 72.24| 49| 21.20| 90| 7.22| 131| 2.84
9| 69.98| 50| 20.61| 91| 7.05| 132| 2.78
10| 67.80| 51| 20.04| 92| 6.88| 133| 2.72
11| 65.69| 52| 19.49| 93| 6.72| 134| 2.67
12| 63.65| 53| 18.96| 94| 6.56| 135| 2.61
13| 61.68| 54| 18.44| 95| 6.40| 136| 2.56
14| 59.78| 55| 17.94| 96| 6.25| 137| 2.50
15| 57.95| 56| 17.45| 97| 6.10| 138| 2.45
16| 56.17| 57| 16.98| 98| 5.96| 139| 2.40
17| 54.46| 58| 16.52| 99| 5.82| 140| 2.35
18| 52.80| 59| 16.08| 100| 5.68| 141| 2.30
19| 51.20| 60| 15.65| 101| 5.55| 142| 2.25
20| 49.65| 61| 15.23| 102| 5.42| 143| 2.21
21| 48.16| 62| 14.83| 103| 5.30| 144| 2.16
22| 46.71| 63| 14.43| 104| 5.18| 145| 2.12
23| 45.31| 64| 14.05| 105| 5.06| 146| 2.08
24| 43.95| 65| 13.68| 106| 4.94| 147| 2.03
25| 42.64| 66| 13.32| 107| 4.83| 148| 1.99
26| 41.38| 67| 12.97| 108| 4.72| 149| 1.95
27| 40.15| 68| 12.64| 109| 4.61| 150| 1.91
28| 38.97| 69| 12.31| 110| 4.51| 151| 1.88
29| 37.82| 70| 11.99| 111| 4.41| 152| 1.84
30| 36.71| 71| 11.68| 112| 4.31| 153| 1.80
31| 35.64| 72| 11.38| 113| 4.21| 154| 1.77
32| 34.60| 73| 11.09| 114| 4.12| 155| 1.73
33| 33.59| 74| 10.80| 115| 4.03| 156| 1.70
34| 32.61| 75| 10.53| 116| 3.94| 157| 1.66
35| 31.67| 76| 10.00| 117| 3.85| 158| 1.63
36| 30.76| 77| 10.00| 118| 3.77| 159| 1.60
15.5 Electrical data table
C- Cooling H – Heating P – Primary Causes S – Secondary Causes
Warranty
Assist owner with processing Warranty cards and/or online registration.
16.1 Maintenance
Dirt should not be allowed to accumulate on the indoor or outdoor coils or
other parts in the air circuit. Clean as often as necessary to keep the unit
clean. Use a brush, vacuum cleaner attachment or other suitable means.
The outdoor fan motor is permanently lubricated and does not require periodic
oiling.
Refer to the furnace or air handler instructions for filter and blower motor
maintenance.
The indoor coil and drain pan should be inspected and cleaned regularly to
assure proper drainage.
It is unlawful to knowingly vent, release or discharge refrigerant into the
open air during repair, service, maintenance or the final disposal of this
unit. When the system is functioning properly and the owner has been fully
instructed, secure the owner’s approval.
16.2 Changing motor
When motor requires changing, follow the steps below:
STEP 1 – Go into electrical panel, disconnect motor power lines.
Note: Disconnect main power to unit. Severe burns and electrical shock
will occur if you do not disconnect main power.
STEP 2 – Remove cover (be careful of motor wires).
STEP 3 – Be sure to place fan cover unit on the ground (Figure 43).
Note: Do not place or lean fan blades on ground or against surface.
STEP 4 – Remove fan motor by removing 5/16″ nuts from cover.
STEP 5 – Remove fan blade from motor by removing 1/2″ nut and place fan on the
ground.
STEP 6 – Reverse removal process to reinstall the fan and motor.
Note: When connecting motor wires be sure to check motor direction.
Damage will occur to condenser unit if you remove 5/16’’ nuts prior to cover
removal.
Wiring diagrams
17.1 For 18K-48K HP System | 17.2 For 60K HP System |
---|
|
17.3 For 18K-36K AC System| 17.4 For 42K-60K AC System
|
Matching table and Checkout Procedures
18.1 Matching table
Condensing Unit| Air Handle/A-Coil| Piston Size/TXV Valve
Model| SEER| If P reinstalled Piston Replace Required
---|---|---|---|---
J4AC6018A1000M| J4AH4E36A1 BOOM| 52| 16| YES
J4AC6024A1000M| J4AH4E36A1 BOOM| 58| 16| YES
J4AC6030A1000M| J4AH4E36A1 BOOM| 65| 16| YES
J4AC6036A1000M| J4AH4E60A1COOAA| 73| 16| YES
J4AC6042A1000M| J4AH4E60A1COOAA| 75| 16| YES
J4AC6048A1000M| J4AH4E60A1COOAA| 80| 16| YES
J4AC6060A1000M| J4AH4E60A1COOAA| 4AYTXVH3G6000A| 15| YES
J4HP6018A1000M| J4AH4E36A1BOOM| 52| 16| YES
J4HP6024A1000M| J4AH4E36A1BOOM| 58| 16| YES
J4HP6030A1000M| J4AH4E36A1BOOM| 4AYTXVH3G2436A| 16| YES
J4HP6036A1000M| J4AH4E60A1COOAA| 70| 16| YES
J4HP6042A1000M| J4AH4E60A1COOAA| 4AYTXVH3G4248A| 16| YES
J4HP6048A1000M| J4AH4E60A1COOAA| 4AYTXVH3G6000A| 16| YES
J4HP6060A1000M| J4AH6E60A1COOAA| 4AYTXVH3G6000A| 15| YES
Note: Since the manufacturer has a policy of continuous product and
product data improvement, if the system combination you are looking for is not
listed, check for the latest version of this document at
www.oxboxhvac.com.
18.2 Operational and Checkout Procedures
Final phases of this installation are the unit Operational and Checkout
Procedures. To obtain proper performance, all units must be operated and
charge adjustments made in accordance with procedures found in the Service
Facts of the Outdoor Unit.
After installation has been completed, it is recommended that the entire
system be checked against the following list:
- Be sure unit suspension(if used) is secure and that there are no tools or loose debris in or around or on top of the unit…………………………….. [ ]
- Properly insulate suction lines and fittings………… [ ]
- Properly secure and isolate all refrigerant lines… [ ]
- Verify that all electrical connections are tight. ….. [ ]
- Check all duct outlets; they must be open and unrestricted. ….. [ ]
- Check drain lines and be sure all joints are tight…………… [ ]
- Be sure that a return air filter is installed……………………… [ ]
- Operate complete system in each mode to verify proper performance. Verify operation of supplementary electric heater. …………………………..[]
BX-SVN-J4ACHP6-1A-EN
Documents / Resources
|
TRANE R410A Split System Air Conditioner and Heat
Pump
[pdf] Installation Guide
R410A, R410A Split System Air Conditioner and Heat Pump, Split System Air
Conditioner and Heat Pump, System Air Conditioner and Heat Pump, Air
Conditioner and Heat Pump, Heat Pump, Pump
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>