RS 233-3534 Pro Multi-Function Panel Meter Instructions
- June 4, 2024
- RS
Table of Contents
RS229-T4 Comfort Spot Wit GU10 Set Instruction Manual © Innr Lighting
B.V. 2018
www.innr.com
To connect the lamp to the bridge, follow the instructions in the mobile app.
Factory-reset: switch the lamp OFF and ON six times (6x) with intervals of 0,5
seconds.
The lamp will blink to indicate it is the factory reset. It can then be
connected to a bridge again.
Important safety instructions
- For indoor use only.
- Do not disassemble the product; if any part is damaged, the product should not be used.
- Do not immerse in water.
- For cleaning, use a damp cloth, never a strong cleaning agent.
- Keep these instructions for future use.
Declaration of Conformity
Hereby, Inner Lighting BV declares that the radio equipment types RB 26x, BY
26x, RB 27x T, BY 27x T, RB 28x C,
BY 28x C, RB 24x, RB 24x T, RS 22x, RS 22x T, and RS 23x C are in compliance
with Directive 2014/53/EU.
The full text of the EU declaration of conformity is available at the
following internet address:
www.innrlighting.com/en/downloads
Frequency: 2.4 GHz (2400 ~ 2483.5MHz) – RF power: max. 10 dBm
Instruction
RS PRO Multi-Function Panel Meter Process Indicator
Stock No: see below
ENGLISH
RoHS
PROCESS INDICATOR : (48*96)
Ordering Information:
Sr.No CAT No.
Description
1
180 to 270 VAC, Process Indicator, Analog Input 233-3534 (0-10VDC / 4-20mA)
2
233-3538
180 to 270 VAC, Process Indicator, Thermocouple & RTD input
CAT No: 233-3534W & 233-3538W (Where W stands for White display)
NOTE:
Ø The technical information provided in this document was correct at the time
of publish.
Ø Product innovation being a continuous process, we reserve the right to alter
specications without any prior notice.
TECHNICAL SPECIFICATION:
233-3538/ 233-3534 Supply Characteristics: Supply Voltage (Un) 180 to 270VAC
Supply Frequency 47 / 63 Hz Power Consumption 5 VA max @ 230 VAC
Functional Characteristics:
PRODUCT DESCRIPTION:
Process Indicator 233-3534 and 233-3538 helps to indicate temperature, Flow,
Level, RPM. Monitors the process by accepting inputs from sensor or from
analog signals in process industries, with inbuilt hour meter functionality.
FEATURES:
Ø Flush Mounting Version 48X96 mm with 7 segment display Ø Thermocouple (J, k,
T, R & S)/ RTD 3-wire (PT-100) sensor input Ø Analog Input (0-10VDC/ 0-20mA/
4-20mA) Ø °C & °F temperature unit selectable Ø Short depth of 65mm Ø IP 20
(For terminal), IP 30 (For enclosure) & IP 65 (For Front Panel) Ø Hour meter
counter functionality Ø Automatic Decimal Point Adjust
Menu Password
Sensor Measurement Range
60 Default (User Selectable)
Applicable for Cat_id: PIT200
J-type
K-type
T-type
R-type & S-type RTD (Pt-100)
°C
-200 to 950
°F
-328 to 1742
°C
-200 to 1350
°F
-328 to 2462
°C
-200 to 400
°F
-328 to 752
°C
-200 to 850
°F
-328 to 1562
°C
0 to 1750
°F
32 to 3182
Analog Input: Applicable for Cat_id: PIA200
CAUTION:
Voltage
0 to 10VDC
Ø When extending the thermocouple lead wires always use thermocouple
compensation
Ø wires for wiring. Ø For RTD sensor, use a wiring material with a small lead
resistance
(10O max per lead) Ø & no resistance differentials among 3 wires. Ø For 2 wire
RTD sensor Short terminal RTD2 & RTD3 then connect to
the Devices. Ø Clean the product with a soft and clean cloth. Do not use
isopropyl alcohol or any Ø other cleaning agent. Ø 20 min warm-up time after
connecting thermocouple input. Ø When replacing the sensor, please turn OFF
the power. Ø Product innovation being a continuous process, we reserve the
right to alter Ø specications without any prior notice. Ø Ensure the congure
and connected input Sensor are same.
Current
0 to 20mA, 4 to 20mA
J, K, T & Pt-100
0.1°/1°
Resolution
R & S
1°
Analog inputs
1/0.1/0.01/0.001
RTD
±0.1% of F.S
± 1°C
233-3538 J, K & T
±0.25% of F.S
± 1°C
R & S
±0.5% of F.S
± 2°C
Measurement Accuracy
233-3534 Signal input
0.5% of F.S
Temperature Unit °C/°F selectable (Appliable for PIT200)
Signal Sampling Time 168 ms
SUITABILITY FOR USE:
Display
Seven Segment Display (Red Color)
These are products with Auto reset, hence never use the products for an application involving signicant risk to life without ensuring that the system as a whole has been designed to address the risks and that
Front Keypad
4 Keys as ESC ( ), DOWN ( ), UP ( ), ENTER ( )
our products are properly rated and installed for the intended use within the entire system or equipment.
Key de-bounce time 40 ms
1
52LL001_00
TECHNICAL SPECIFICATION:
Functional Characteristics:
233-3538 / 233-3534
J, K, T & Pt-100
0.1°/1°
Resolution
R & S Analog inputs
1° 1/0.1/0.01/0.001
RTD
±0.1% of F.S
± 1°C
Measurement Accuracy
PIT200 J, K & T R & S
±0.25% of F.S ±0.5% of F.S
± 1°C ± 2°C
PIA200 Signal input
0.5% of F.S
Temperature Unit °C/°F selectable (Appliable for PIT200)
Signal Sampling Time 168 ms
Display
Seven Segment Display (Red Color)
Front Keypad
4 Keys as ESC ( ), DOWN ( ), UP ( ), ENTER ( )
Key de-bounce time 40 ms
Error Indications
Sens Sensor open/Break error ovrg Over range error
unrg Under range error
Environmental Characteristics:
Operating Temperature
Storage Temperature
0 to 50 °c -20 to 75 °c
Operating Humidity 85 % RH (Non-Condensing)
Operating Altitude 2000 m (max) Pollution Degree II
IP 20: Terminal
Degree of Protection
IP 65: Front Facial IP 30: Enclosure
Enclosure
Flame Retardant (UL 94 V-0)
Other Characteristics:
Mounting (WXHXD) mm
48X96X65
Weight
(Un-Packed)
PIA200 : 144 gm PIT200 : 145 gm
Operating Position Horizontal (Readable)
rspro.com
FUNCTIONAL PARAMETERS:
Parameter Inp Menu: Input
Description
senS
Sensor input setting
j
J-type
K-type
S y
S-type
r
r-type
t
T-type
Default j
Pt1
Pt-100
rAte ofst
RATE Range: 0.000 to 2.000
OFFSet Range: -1999 to 9999
DP
Decimal Point Range: 0 to 1 for J, K, Pt1 & T 0 for R, S
unIt Filt
Temperature Unit Range: °C or °F Filter Range: 0 to 10
misc Menu: Miscellaneouc
unit
hcnt
Unit Range: OFF,day,hr
hcth
Counter Threshold Range: OFF to 9999
This Parameter will displays the Current
Ver
Product Firmware Version
pwd Menu: Password
stat
Password Status Range: EN or DIS
EN: Enable DIS: Disable
set
Password Set
Range: 0 to 9999
Hide Menu: Hiding
Input
Range: OFF or ON
inp
OFF: Inp menu will not hide
ON: Inp menu will hide
Misc
Miscellaneouc Range:OFF or ON
OFF: Misc menu will not hide ON: Misc menu will hide
1.000 0 0 o C 0
oFF oFF
…
En 60
off
off
Parameter
Description
pwd Menu: Password
Password
Pwd
Range: OFF or ON
OFF: PWD menu will not hide
ON: PWD menu will hide
rset
Reset Range: OFF or ON
OFF: Rset menu will not hide ON: Rset menu will hide
rset Menu: Reset
rset
Reset To reset the devices & load default setting (Press Enter key)
Default off off
cnfm
If “Yes”: Will display Conrm reset
If “No” : Will get to menu
no
After Conrm, If “Yes”: Devices Reset and back to main
Screen If ” No”: Back to main Screen
2
The Functional parameter for cat_id: 233-3534 is same as above only input menu is different
Inp Menu: Input
senS
Sensor input setting
0_20
0 to 20mA
4_20
4 to 20mA
0_10
0 to 10VDC
0_20
Analog Input Low Scale
IScL
Range: -1999 to ISCH
0
Selectable low value for analog input
isch
Analog Input High Scale Range: ISCL to 9999 Selectable high value for analog input
100.00
airl
airH rAte ofst
DP Filt
Analog Input Range Low Range: For 0_20: 0 to AirH
For 4_20: 4 to AirH For 0_10: 0 to AirH Selectable low value for Display
scaling
Analog Input Range High Range: For 0_20: AirL to 20
For 4_20: AirL to 20 For 0_10: AirL to 10 Selectable high value for Display
scaling
RATE Range: 0.000 to 2.000
OFFSet Range: -1999 to 9999
Decimal Point Range: 0 to 3 for V & I
Filter Range: 0 to 10
00.00
20.00
1.000 0 0 2
EMI/EMC Compliance:
Harmonic Current Emission ESD Radiated Susceptibility Electrical Fast
Transients (Power Ports)
Surge
IEC 61000-3-2 (Class A) IEC 61000-4-2 (Level III) IEC 61000-4-3 (Level III) IEC 61000-4-4 (Level IV) IEC 61000-4-5 (Level IV)
Conducted Susceptibility IEC 61000-4-6 (Level III)
Power Frequency Magnetic Field
IEC 61000-4-8 (Class 4)
Voltage Dips/Interruption IEC 61000-4-11
Voltage Dips (DC)
IEC 61000-4-29
Conducted & Radiated Emission
CISPR 11 (Class A)
Product Standard Safety Compliance: Dielectric Strength (Input & Output)
IEC 61326-1 IEC 60255-5
Impulse(Input & Output) IEC 60255-5 (Level IV)
Single Fault
IEC 61010-1
Insulation Resistance Leakage Current
UL 508 (>100 M) UL 508 (< 3 mA)
Environmental Compliance:
Cold Heat Dry Heat
Vibration
IEC 60068-2-1 IEC 60068-2-2 IEC 60068-2-6 (5g)
CONNECTION DETAIL:
DC Analog Input
V mA
+ — + 1 2 3 4 5 6 7 8 9 10
21
23
22
233-3534
24
11 12 13 14 15 16 17 18 19 20
Pt-100
RTD1 RTD2 RTD3
+ TC/mV 1 2 3 4 5 6 7 8 9 10
21
22
233-3538
23 24
11 12 13 14 15 16 17 18 19 20
NL Input Supply
NL Input Supply
FRONT FACIA:
1 6
2
5
Sr.
Keys/
No. Indication
1
PV
2
3
4
5
6
°F
3
4
Description
To displays the Process Value’ &
Menu’.
To exit from menu. To abort changed value or parameter. To return to home
screen.
To view parameter downward. To decrement/ change parameter value in edit mode.
To view hour counter unit & threshold (Press for >2 sec )
To view parameter upward. To increment/change parameter value in edit mode.
To enter into main menu (Press for >2 sec ) To select and save parameter
To indicates LED `°F’ unit setting.
MECHANICAL DIMENSIONS (in mm):
FRONT VIEW
SIDE VIEW
PANEL CUTOUT
Terminal Details:
Ø4……5.0mm Combi Head Bit./Flat
AWG
0.5 N.m (4.4lb.in) to 0.7N.m (6.2lb.in)
2 x 2.5 mm2 Solid / Standard Wire
1 X 20 to 12
rspro.com
3
FUNCTION MENU:
Cat_id: 233-3538
60
pwd
Press Enter key for 2 sec
(60 is password)
1np SenS rate oFSt
DP
UnIt
J
1.000
0
0
oC
y
of
s
r
T
pt1
misc Unit off
hcnt off
pwd stat SET
Dis
60
Hide
inp misc PWD rset
off off
rset no
yes
off off
cnF
no
yes
filt 2
Cat_id: 233-3534
60
pwd
Press Enter key for 2 sec (60 is password)
1np SenS iSCL isch airl airh
0_20 4_20
0
100
00.00 20.00
filt
DP
oFSt rate
0_10 misc Unit
2 off
0
0
1.000
hcnt off
pwd stat SET
Dis
60
Hide
inp misc PWD rset
off off
rset no
yes
off off
cnF
no
yes
DESCRIPTION & DEFINATION:
Rate (rate) & Offset (ofst): This menu is used to adjust the PV value in cases
where it is necessary for PV value to agree with another recorder or
indicator, or when the sensor cannot be mounted in correct Location. E.g.
Sensor is mounted at a location, where less than actual temperature is
observed. Let us say actual temperature is 550 and sensor is located to such a
location where the temperature is 500.This device will measure 500 and show
the value accordingly. To observe the actual temperature, user should add
offset of 50 to measured temperature value. i.e. 500+50=550. Now device will
show 550 instead of 500, Rate can be applied as slope; range is from 0.001 to
2.000. Display temp. = rAtE * Measured Temp + oFst
HOUR METER: It is the number of hour/day that the instrument is turned ON.
When the DUT reached to the threshold value (Programmable) the display will
indicate an message of “INSP”(Inspection), to indicated that set threshold is
completed and can start his necessary action. After acknowledge the hour meter
will continue to record the hours till new threshold is set. If counter
threshold is edited then it will reset the current count. UNIT (UNIT): It is
used to select day or hour. HOUR METER THRESHOLD (hcNT): It is used to set the
threshold.
ANALOG INPUT & DISPLAY SETTING E.g. We have few setting in Inp menu. Sens =
0_10 (0V to 10V) AlrL = 1, Alrh = 10, (Selectable high & low value for analog
input) IScL = 0, ISch = 99 (Selectable high & low value for Display scaling
value) When analog input voltage is 1V then value on display will be 0. When
analog input voltage is 10V, then value on display will be 99.This value will
vary from 0 to 99 according to analog input.
E-Waste Regulatory notice: Kindly treat, recycle or dispose of this equipment
in an environmentally sound manner after End of Life, as per WEEE (Waste and
Electronic Equipment) regulations; or hand it over to General Industrial
Controls Pvt. Ltd, through website https://www.gicindia.com/get-intouch/
4 rspprco.cmom
PROCESS INDICATORS : (48*96)
RoHS
Ordering Information:
FRONT FACIA:
Sr.No CAT No
1
233-3535
Description
85-270V AC/DC, Process indicator, Analog Input (0-10VDC/0-20mA),Thermocouple,
RTD & mV, 24VDC Sensor Supply
85-270V AC/DC, Process indicator, Analog Input
2
233-3536 (0-10VDC/0-20mA),Thermocouple, RTD & mV,
Alarm outputs-Analog (0-10V/0-5V,0-20mA/4-20mA)
& Relay 5A for alarm indication, 24VDC Sensor Supply)
85-270V AC/DC, Process indicator, Analog Input
3
233-3537 (0-10VDC/0-20mA),Thermocouple, RTD & mV,
Alarm outputs-Analog (0-10V/0-5V,0-20mA/4-20mA)
& Relay 5A for alarm indication with Rs485 Modbus
communication, 24VDC Sensor Supply)
CAT No: PIB110W, PIB120W & PIB12CW (Where W stands for White display)
PRODUCT DESCRIPTION:
Process indicator Series with scalable analog input and output, monitors the process, indicates the temperature, level, ow and pressure, retransmits the analog output, provides alarm indication, with inbuilt hour meter functionality and RS485 Modbus communication.
FEATURES:
Ø Flush Mounting Version 48X96 mm with 7 segment display Ø Thermocouple (J, k,
T, R & S)/ RTD 3-wire (PT-100) sensor input Ø Analog Input (0-10VDC/ 0-20mA/
4-20mA), mV(Linear) -5 to 56mV Ø Alarm Outputs, Analog (0-20mA/ 4-20mA or
0-10VDC/0-5VDC) and Ø Relay 5A for alarm indication Ø Congurable Band,
Deviation Alarms Ø °C & °F temperature unit selectable Ø Short depth of 65mm Ø
RS485 Communication (applicable for Cat No: PIB12C) Ø IP 20 (For terminal), IP
30 (For enclosure) & IP 65 (For Front Panel) Ø 24 VDC (30mA) sensor supply Ø
Hour meter counter functionality Ø Automatic Decimal Point Adjust
1 2
6 7 8 5
Sr. Keys/ No. Indication
1
PV
2
3
4
5
6
AL1
7
AL2
8
°F
3
4
Description
To display the Process Value’ &
Menu’.
To exit from menu. To abort changed value or parameter. To return to home
screen. To view parameter upward. To increment/change parameter value in edit
mode.
To view parameter downward. To decrement/change parameter value in edit mode.
To view hour counter unit & threshold(Press for >2 sec )
To enter into main menu (Press for >2 sec ) To select and save parameter To
indicate LED for Alarm 1. To indicate LED for Alarm 2. To indicate LED `°F’
unit setting.
FRONT VIEW
SIDE VIEW
AL1 AL2
CAUTION:
Ø When extending the thermocouple lead wires, Always use Ø thermocouple
compensation wires for wiring. Ø For 2 wire RTD short terminal RTD2 & RTD3 and
then connect to the
devices. Ø Clean the product with a soft and clean cloth. Do not use
isopropyl alcohol or any other cleaning agent. Ø 20 min warm-up time after
connecting thermocouple input Ø When replacing the sensor, please turn OFF the
power. Ø Product innovation being a continuous process, we reserve the
right to alter specications without any prior notice. Ø Ensure the congure and
connected input Sensor are same. Ø For RTD sensor, Use a wiring material with
small Lead resistance Ø (100O max per lead) & no resistance differentials
among 3 wires
MECHANICAL DIMENSIONS (in mm): PANEL CUTOUT
Terminal Details:
Ø4……5.0mm Combi Head Bit./Flat
AWG
0.5 N.m (4.4lb.in) to 0.7N.m (6.2lb.in)
2 x 2.5 mm2 Solid / Standard Wire
1 X 20 to 12
52LL002_00
1 rspprco.cmom
TECHNICAL SPECIFICATION:
Supply Characteristics:
233-3535 / 233-3536
Supply Voltage (Un) Supply Frequency Power Consumption
85 to 270 VAC/DC 47 to 63 Hz 8 VA @ 230 VAC
/ PIB12C
Functional Characteristics:
Menu Password Sensor Inputs (IEC)
Sensor Measurement Range
60 Default (User Selectable)
Thermocouple (J, K, T, R & S) RTD (Pt-100, 3-wire, 2-wire) For 2 wire RTD short terminal no 6 & 7
J-type
°C -200 to 950 °F -328 to 1742
K-type
T-type R-type & S-type
°C -200 to 1350 °F -328 to 2462 °C -200 to 400 °F -328 to 752
°C 0 to 1750 °F 32 to 3182
RTD (Pt-100)
°C -200 to 850 °F -328 to 1562
Analog Input
Voltage Current
0 to 10VDC 0 to 20mA, 4 to 20mA
Resolution
mV
-5 to 56mV
J, K, T & Pt-100
0.1°/1°
R & S
1°
Analog inputs
1/0.1/0.01/0.001
RTD
±0.1% of F.S
± 1°C
Measurement Accuracy
J, K & T R & S Signal input
±0.25% of F.S ±0.5% of F.S 0.5% of F.S
± 1°C ± 2°C
20 min warm up
Temperature Unit °C/°F selectable
Signal Sampling Time 168 ms
Display
Seven Segment Display (Red Color)
Front Keypad
4 Keys as ENTER ( ), UP ( ), DOWN ( ), ESC ( ),
Key de-bounce time 40 ms
Error Indications
Sens Sensor open/Break error Ovrg Over range error Unrg Under range error
Sensor Supply Characteristics:
Output Voltage
24 VDC (26.4 V Max.)
Load Current
30 mA (Max)
Relay(Alarm Indication) Characteristics:
Applicable for cat No: PIB120 and PIB12C
Contact Arrangement 1 C/O (SPDT)
Contact Rating
5A(NO), 3A(NC), RES. @ 250VAC/ 24VDC
Contact Material
Ag alloy (Cd free)
Utilization Category (AC-15)
Switching Frequency
Ue Rated Voltage (V): 120 / 240 Ie Rated Current (A): 3.0 / 1.5 1800 Operations/Hour
Electrical Life
50,000 Operations
Mechanical Life
5,000,000 Operations
Linear DC Output Characteristics: Applicable for cat No: PIB120 and PIB12C
Programmable output
Voltage: 0 to 10V/ 0 to 5V Current: 0 to 20 mA / 4 to 20mA
Output update rate 100mS
Accuracy of DC Output 0.25% of F.S.
Min. load resistance (Voltage)
Min 30K
Max. load resistance (Current)
Max 600
LED Indications(For Alarm Indication): AL1 and AL2 LED’s are applicable for cat No: PIB120 and PIB12C
AL1 (Red LED) ON AL2 (Red LED) ON
Relay output ON Relay output ON
°F’ (Red LED) ON Display
°F’ value OFF Display `°C’ value
Communication Characteristics: Applicable for cat No: PIB12C
Interface Standard
RS-485 (Modbus RTU)
Communication Address
1 to 247
Transmission Distance Upto 1000 m
Transmission Speed 2400,4800, 9600, 19200 BPS
Parity
Even, Odd, None
Communication
Half Duplex
Environmental Characteristics:
Operating Temperature 0 to 50 °c
Storage Temperature -20 to 75 °c Operating Humidity 85 % RH (Non-Condensing)
Operating Altitude Pollution Degree
2000 m (max) II
Degree of Protection
Enclosure Other Characteristics:
IP 20: Terminal
IP 65: Front Facial IP 30: Enclosure Flame Retardant (UL 94 V-0)
Mounting (HXWXD) Weight (Un-Packed)
48X96X65 (mm) 233-3535:160 gm 233-3536 :200 gm 233-3537 :200 gm
Operating Position
Horizontal (Readable)
EMI/EMC Compliance:
Harmonic Current Emission
ESD
IEC 61000-3-2 (Class A) IEC 61000-4-2 (Level II)
Radiated Susceptibility IEC 61000-4-3 (Level III)
Electrical Fast Transients (Power Ports)
IEC
61000-4-4 (Level
IV)
Surge
IEC 61000-4-5 (Level IV)
Conducted Susceptibility IEC 61000-4-6 (Level III)
Power Frequency Magnetic Field
IEC 61000-4-8 (Class 4)
Voltage Dips/Interruption IEC 61000-4-11
Voltage Dips (DC)
IEC 61000-4-29
Conducted & Radiated CISPR 11 (Class A)
Emission
Product Standard
IEC 61326-1
Safety Compliance:
Dielectric Strength (Input & Output)
IEC 60255-5
Impulse (Input & Output)
IEC 60255-5 (Level IV)
Single Fault
IEC 61010-1
Insulation Resistance UL 508 (>100 M)
Leakage Current
UL 508 (< 3 mA)
Environmental Compliance:
Cold Heat
IEC 60068-2-1
Dry Heat
IEC 60068-2-2
Vibration
IEC 60068-2-6 (5g)
2
ALARM MENU:
Alarm Types: 1. Absolute low (“AbLO” on display): Alarm is activated if PV goes below A1th and is deactivated if PV goes above (A1th+A1hY).
Menu AL1
Sub menu A1tY
Option AbLo
PV A1hY
A1th+A1hY A1th
ON
OFF
ON
OFF
ON
Time
2. Absolute high (“AbhI” on display): Alarm is activated if PV goes above A1th and is deactivated if PV goes below (A1th-A1hy).
Menu AL1
Sub menu A1tY
Option Abhi
PV A1hY
A1th A1th-A1hY
OFF
ON
OFF
ON
OFF
Time
3. Absolute band (“AbbA” on display): Alarm is activated if PV goes above A1hi or below A1Lo. It is deactivated if it goes below (A1hi-A1hy) or above (A1Lo+A1hy).
Menu AL1
Sub menu A1tY
Options AbbA
PV A1hY A1hy
Menu AL1
ON O F F
ON O F F
ON O ON O ON
F
F
F
F
A1hi A1hi-A1hy A1L0+A1hy A1Lo
Time
Sub menu A1tY
Options
AbLo AbhI AbbA
AL Menu: This Menu is applicable for Cat No: PIB120 & PIB12C
A1tY
Alarm 1 type: Range: 1. AbLo: Absolute low 2. AbhI: Absolute high 3. AbbA: Absolute band
AbLo
Alarm 1 function:
0 : Alarm on Error
+1: Acknowledge alarm
A1Fn
+2: Delayed alarm
0
+4: Latch alarm
+8: No alarm at power on
Range: 0-15
A1Lo A1th
Alarm 1 low level Range: -1999 to A1th
Alarm 1 Threshold Range: A1Lo to A1Hi
-1999 0
A1hI A1hY
Alarm 1 high level Range: A1th to 9999
Alarm 1 hysteresis Range: OFF to 9999
9999 1
Alarm 1 Annunciator
Range: LED, DISP, OFF
LED: LED blinks at 0.2 Sec
A1AN
after alarm occurrence DISP: Message gets displayed
Off
On Screen and LED gets
ON after alarm occurrence
OFF: LED is continuous ON
A1dL
Alarm 1 delay Range: OFF to 9999 s
Off
Alarm Functions:
Sr.No Value
Details
Applications
10 21 32 44 58
Normal Activation: When alarm condition occurs. Deactivation: When the alarm
condition Disappear.
Acknowledge Activation: When alarm condition occurs. Deactivation: 1)When the
alarm condition disappear. 2)When configurable key is programmed for
acknowledgment and it is pressed in alarm condition.
Normal
To ignore the alarm Condition
Delayed
To delay the
Activation: Delayed by time set in A1dL alarm
parameter after occurrence of the alarm generated,
condition.
some times
Deactivation: When the alarm condition alarm can be
disappear.
generated for
Note: During the delay if the alarm
shorter time
condition disappears, alarm will not
due to some
generated.
disturbance in
system
Latched
To record or
Activation: When alarm condition occurs. draw attention
Deactivation: When configurable key is of alarm
programmed for acknowledgment and generation
it is pressed in alarm condition.
condition every
Note: Alarm will not automatically
time. since no
deactivated once generated.
automatic of
alarm
No alarm at Power ON Activation: IF alarm condition exist at power on, alarm will not be activated. Once devices comes out of alarm condition after power on, there after alarm will be activated at every occurrence of the alarm condition. Deactivation: Alarm will be deactivated in no alarm condition.
To avoid alarm after power on. Since possibility of alarm condition after every power on.
Note: Alarm types and functions are explained for alarm 1. The explanation for
AL1 is same as AL2. 2. Binary addition of alarm function allows Combination of
different function.
Eg. If it is required to have no alarm at power On [8] and Delayed [2], set
function as 10.
FUNCTIONAL PARAMETERS:
Parameter
Description
Inp Menu: Input
senS
Sensor input setting
j
J-type
S y
K-type
S-type
r
r-type
t
T-type
Pt1
Pt-100
0_20
0 to 20mA
4_20
4 to 20mA
0_10
0 to 10VDC
56mV
56mV Analog input
IScL
Analog Input Low Scale Range: -1999 to ISCH
Isch
Analog Input High Scale Range: ISCL to 9999
airl
Analog Input Range Low Range: For 0_20: 0 to AirH
For 4_20: 4 to AirH For 0_10: 0 to AirH For 56mV: -5 to AirH
airH
Analog Input Range High Range: For 0_20: AirL to 20
For 4_20: AirL to 20 For 0_10: AirL to 10 For 56mV: AirL to 56
Default
j
0 100 0.00 20.00
3
rAte
RATE Range: 0.000 to 2.000
ofst
OFFSet Range: -1999 to 9999
DP unIt
Decimal Point Range: 0 to 3 for V, I & mV
0 to 1 for J, K, Pt1 & T 0 for R, S
Temperature Unit Range: °C or °F
PvLO PvhI Filt
Process Value Low Range: -1999 to 9999 Corresponds to 0 or 4mA / 0VDC
Process Value High Range: -1999 to 9999 Corresponds to 20mA / 10VDC
Filter Range: 0 to 10
0p Menu: Output
Output 1
Range: OFF
A1NO(Alarm 1 Normally open)
op1
A1NC(Alarm 1 Normally Close) A2NO(Alarm 2 Normally open)
A2NC(Alarm 2 Normally Close)
SMER(Sensor Measurement Error)
Output 2
Range: OFF
A1NO(Alarm 1 Normally open)
op2
A1NC(Alarm 1 Normally Close)
A2NO(Alarm 2 Normally open)
A2NC(Alarm 2 Normally Close)
SMER(Sensor Measurement Error)
op3 manl Serr
Output 3 Range: V005(0 to 5 VDC)
V010(0 to 10 VDC) I020(0 to 20 mA) I420(4 to 20 mA)
Manual mode Range: ON, OFF
Sensor Error Range: Low, High (Note: the parameter will only be visible if
manual mode is OFF) When ever sensor error conditions occurs in that case
analog o/p will be High (for e.g 5 VDC)
Ptag
Percentage Error Range: 0.0 to 100.0 (Note: The parameter will only be visible if manual mode is ON) if PtAg: 50 & OP3: V005 then, When ever sensor error conditions occurs in that case analog o/p will be 2.5VDC (Percentage value of Analog o/P )
misc Menu: Miscellaneouc
hcnt
unit Unit Range: OFF,day,hr
hcth Counter Threshold Range: OFF to 9999
This Parameter will displays the
ver
Current Product Firmware Version
modb Menu: Modbus
addr
Address (Devices ID) Range: 1 to 247
1.000 0 0 oC 0 100 0
oFF
oFF
V005 off high
0
oFF oFF … 1
baud
Baud rate Range: 24, 48, 96, 192
24: 2400 baud rate 48: 4800 baud rate 96: 9600 baud rate 192: 19200 baud rate
part
Parity Range: None, Odd, Even
None: None Parity odd : Odd Parity Even : Even parity
Stpb
Number of stop bits Range: 1 to 2
pwd Menu: Password
stat
Password Status Range: EN or DIS
EN: Enable DIS: Disable
set
Password Set Range: 0 to 9999
Hide Menu: Hiding
Input
inp
Range: OFF or ON OFF: Inp menu will not hide
ON : Inp menu will hide
Alarm1
Al1
Range: OFF or ON
OFF: AL1 menu will not hide
ON : AL1 menu will hide
Al2 op Misc
Alarm2 Range: OFF or ON
OFF: AL2 menu will not hide ON : AL2 menu will hide
Output Range: OFF or ON
OFF: OP menu will not hide ON : OP menu will hide
Miscellaneouc Range: OFF or ON
OFF: Misc menu will not hide ON : Misc menu will hide
Modb
Modbus Range: OFF or ON
OFF: Modb menu will not hide ON : Modb menu will hide
Password
Pwd
Range: OFF or ON OFF: PWD menu will not hide
ON : PWD menu will hide
rset
Reset Range: OFF or ON
OFF: Rset menu will not hide ON : Rset menu will hide
rset Menu: Reset
rset cnfm
Reset To reset the devices & load default setting (Press Enter key) If “Yes” :
Will display Confirm reset If “No” : Will get to menu After Confirm, If “Yes”
: Devices Reset and back to
main Screen If ” No” : Back to main Screen
96
none 1 En 60 off off off off off off off off
no
4 rspro.com
The Functional parameter for cat_id: PIA200 is same as above only input menu is different
Inp Menu: Input
senS
Sensor input setting
0_20 4_20
0 to 20mA 4 to 20mA
0_10
0 to 10VDC
IScL
Analog Input Low Scale
Range: -1999 to ISCH Selectable low value for analog input
isch
Analog Input High Scale Range: ISCL to 9999 Selectable high value for analog input
4_20 0
100.00
airl
Analog Input Range Low Range: For 0_20: 0 to AirH
For 4_20: 4 to AirH For 0_10: 0 to AirH Selectable low value for Display
scaling
00.00
airH
Analog Input Range High Range: For 0_20: AirL to 20
For 4_20: AirL to 20 For 0_10: AirL to 10 Selectable high value for Display
scaling
20.00
MECHANICAL DIMENSIONS (in mm):
FRONT VIEW
SIDE VIEW
PANEL CUTOUT
Terminal Details:
Ø4……5.0mm Combi Head Bit./Flat
AWG
0.5 N.m (4.4lb.in) to 0.7N.m (6.2lb.in)
2 x 2.5 mm2 Solid / Standard Wire
1 X 20 to 12
rAte
RATE Range: 0.000 to 2.000
ofst DP Filt
OFFSet Range: -1999 to 9999
Decimal Point Range: 0 to 3 for V & I
Filter Range: 0 to 10
CONNECTION DIAGRAM:
Pt-100 DC Analog
RTD1 RTD2 RTD3
Input
+ TC/mV –
V mA
+ — +
1 2 3 4 5 6 7 8 9 10
21 22
233-3535
23 24
11 12 13 14 15 16 17 18 19 20
+ 24V –
Sensor Supply
N/- L/+
Input Supply
OP3
RTD1 RTD2 RTD3
0-5V 0-20mA 0-10V 4-20mA
Pt-100
DC Analog Input
+ – + + TC/mV –
V-
mA
–
1 2 3 4 5 6 7 8 9 10
21 22
233-3536
23 24
11 12 13 14 15 16 17 18 19 20
NO
NC
P
OP1
NO
NC
P
OP2
+ 24V –
Sensor Supply
N/- L/+
Input Supply
OP3
0-5V 0-20mA 0-10V 4-20mA
Pt-100
DC Analog Input
+ – + + TC/mV –
V mA
+ — +
1 2 3 4 5 6 7 8 9 10
D 21 D- 22
233-3537
23 24
11 12 13 14 15 16 17 18 19 20
NO
NC
P
OP1
NO
NC
P
OP2
+ 24V –
Sensor Supply
N/- L/+
Input Supply
RS485 RTD1
RTD2 RTD3
1.000
0 0 2
FUNCTION MENU:
60
pwd
Press Enter key for 2 sec
(60 is password)
1np SenS rate oFSt
DP
UnIt
J
1.000
0
0
oC
y
of
s
r
T
pt1
misc Unit off
hcnt off
pwd stat SET
Dis
60
Hide
inp misc PWD rset
off off
rset no
yes
off off
cnF
no
yes
filt 2
5
rspro.com
Cat_id: 233-3534
60
pwd
Press Enter key for 2 sec (60 is password)
1np SenS iSCL isch airl airh
0_20 4_20
0
100
00.00 20.00
filt
DP
oFSt rate
0_10 misc Unit
2 off
0
0
1.000
hcnt off
pwd stat SET
Dis
60
Hide
inp misc PWD rset
off off
rset no
yes
off
off
cnF
no
yes
DESCRIPTION & DEFINATION:
Rate (rate) & Offset (ofst): This menu is used to adjust the PV value in cases
where it is necessary for PV value to agree with another recorder or
indicator, or when the sensor cannot be mounted incorrect Location. E.g.
Sensor is mounted at a location, where less than actual temperature is
observed. Let us say actual temperature is 550 and sensor is located to such a
location where the temperature is 500.This device will measure 500 and show
the value accordingly. To observe the actual temperature, user should add
offset of 50 to measured temperature value.i.e. 500+50=550. Now device will
show 550 instead of 500, Rate can be applied as slope; range is from 0.001 to
2.000. Display temp. = rAtE * Measured Temp + oFst
HOUR METER: It is the number of hour/day that the instrument is turned ON.
When the DUT reached to the threshold value (Programmable) the display will
indicate an message of “INSP”(Inspection), to indicated that set threshold is
completed and can start his necessary action. After acknowledge the hour meter
will continue to record the hours till new threshold is set. If counter
threshold is edited then it will reset the current count. UNIT (UNIT): It is
used to select day or hour. HOUR METER THRESHOLD (hcNT): It is used to set the
threshold.
ANALOG INPUT & DISPLAY SETTING E.g. We have few setting in Inp menu. Sens =
0_10 (0V to 10V)AlrL = 1, Alrh = 10, (Selectable high & low value for analog
input)IScL = 0, ISch = 99 (Selectable high & low value for Display scaling
value) When analog input voltage is 1V then value on display will be 0. When
analog input voltage is 10V, then value on display will be 99.This value will
vary from 0 to 99 according to analog input.
6 rspro.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>