RS PRO 264-1025 BACnet Module for Power Quality Analyser Owner’s Manual
- May 15, 2024
- RS PRO
Table of Contents
- Features
- Product Description
- Installation and Operation
- Configuration
- BACnet Protocol Implementation
- Supporting private propertiesWntabIe properties
- Attribute Idenblter : 9600 Type of Data : Integer Meaning : Baud Rate0:
- Writable properties
- Analogue input object
- Analogue output object
- Analogue value object
- Binary input object
- Binary output object
- Binary value object
- Data link layer options
- Object identifier
- Maximum number of primary nodes 9600
- 9601
- Supporting private properties : No Writable properties : No
- Supporting private properties : No Writable properties : No
- Supporting private properties : No Writable properties : The current
- Supporting private properties : No Writable properties : No
- Supporting private properties : No Writable properties : The current
- Supporting private properties : No Writable properties : No
- MS/TP Master (Chapter 9)
- Baud rate: 1200, 2400. 4800, 9600. 19200 bps.
- Note : The baud rates of 1200, 2400 and 4800 bps are not recommended
- Technical Parameters
- Dimensions
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
**RS PRO 264-1025 BACnet Module for Power Quality Analyser Owner’s Manual
**
Features
- Extends the capability of the 264-1020 Multifunction Network Analysers
- Automatically recognised by 264-1020
- Baud rate: 1200/2400/4800/9600/ 19200 bps
- Real-time data measurement from RIF550
RS Professionally Approved Products bring to you professional quality parts across all product categories. Our product range has been tested by engineers and provides a comparable quality to the leading brands without paying a premium price.
Product Description
The 264-1025 is a BACnet/MSTP communication module used to extend the bus communication function of the 264-1020 Network Analyser.
Baud rate: 1200/2400/4800/9600/19200 bps
Based on MSTP communication method
Relevant parameters can be configured through the host computer or 264-1020 Network Analyser.
Installation and Operation
Disconnect the power supply of Network Analyser and then connect the 264-1025
module to slot X2 (take X2 slot as an example)
Connect the Network Analyser to the power supply, and then enter the module interface of the Analyser to check the information of slot X2.
If the connection between the meter and the module is correct, the parameters
of 264-1025 module will be shown.
In the BACnet/MSTP network, users can read the real-time measurement data of 264-1020 Network analyser (with 264-1025 module) through standard protocol, or realize remote parameter configuration through fixed instructions.
Configuration
In the BACnet/MSTP network, users can read the real-time measurement data of Network Analyser (with 264-1025 module) through standard protocol, or realize remote parameter configuration through fixed instructions.
Configuring the 264-1025 module through the 264-1020 Analyser
Configuring the 264-1025 module via computer with RI-FXX Viewer software.
After opening the 264-1020 Network Analyser host computer:
- Change the slave address (this address is the Modbus address of the 264-1020 Network Analyser)
- Open serial port settings from setup options
- Modify port number, baud rate, data format, etc.
- Click ‘Accept’ to save the communication settings.
BACnet Protocol Implementation
Supporting private propertiesWntabIe properties
|
Attribute Idenblter : 9600 Type of Data : Integer Meaning : Baud Rate0:
1200 bps1 : 2400 bps2: 4800 bps3: 9600 bps (default)4: 19200 bpsAttribute Identifier : 9601Type of Data : IntegerMeaning : MAC address (0…127)Object identifier MAXIMUM number of primary nodes 96009601
---|---
Writable properties
Analogue input object
Analogue output object
Analogue value object
Binary input object
Binary output object
Binary value object
Data link layer options
|
Object identifier
Maximum number of primary nodes 9600
9601
Supporting private properties : No Writable properties : No
Supporting private properties : No Writable properties : No
Supporting private properties : No Writable properties : The current
value.
Supporting private properties : No Writable properties : No
Supporting private properties : No Writable properties : The current
value.
Supporting private properties : No Writable properties : No
MS/TP Master (Chapter 9)
Baud rate: 1200, 2400. 4800, 9600. 19200 bps.
Note : The baud rates of 1200, 2400 and 4800 bps are not recommended
because they are not standard baud rates in the protocol.
---|---
Technical Parameters
Communication Interface | RS485 |
---|---|
Baud rate | 1200/2400/4800/9600/19200 bps |
Operating type | MACnet/MSTP Master |
Communication protocol | MACnet/MSTP |
Environmental
Operating Temperature | -25˚C…+75˚C |
---|---|
Storage Temperature | -40˚C…+85˚C |
Relative humidity | 0…95%, non-condensing |
Dimensions
All dimensions in millimeters
Safety Instruction
It is recommended to use this module as a reference to the following content:
264-1020 Network Analyser User Manual, BACnet Standard 135-2008. Please read
this user manual carefully before using this module. This module must be
installed and serviced only by professional personnel. Manufacturer shall not
be held responsible for failure to comply with the instructions in this
manual.