niko 41752 Swiss Garde 360 Presence Detector
Secondary presence detector 24m, 360°
Picture Illustration
Product description (1)
The device detects the movements and the presence of persons using a passive
infrared sensor (PIR).
It reacts most sensitively to movements which are tangential to the monitored
area.
Movements directly towards the detector have a reduced sensitivity of approx.
-50%.
Application (2)
The detector is used to increase the detection range of a Master detector
(Swiss Garde 360 DALI Master A-Comfort).
The detector is designed for ceiling installation.
Adhere to the following during installation:
– Install only on stable ceilings.
– Mask moving objects in the monitored area by deactivation of the sector
(setting over remote control analogous to Master).
– Do not place any lamps underneath or next to the detector at a distance of
less than 1m away.
– Do not install in direct cold or hot air flows.
Range (1)
The recommended installation height for this detector is 2–3,5m, 2,5 is the
optimal installation height.
To reduce the detection area the enclosed half-shells can be clamped between
lens and cover.
It is possible to connect up to 10 secondary detectors to one Master which controls the load according to its settings. To achieve complete converage by using several detectors, it is recommended to have an overlap of approximately 30%.
Safety notes
Ensure that the electrical lines are de-energised before installation.
Installation is only permitted by electricians in compliance with local
legislation.
Installation (3)
The detector is intended for ceilling installation at a height of 2 to 3,5m.
The diameter Ø of the monitored area depends on the installed height.
Install the detector as follows:
– Remove the front cover by turning it anti-clockwise, then unscrew the upper
section of the detector.
– Mark and drill the drilled holes in the desired installation location.
– Pull the cable through the cable ducts.
– Fasten the detector with a set of screws / dowels.
– Wire the detector according to item 5.
– Fit and screw back on the upper section of the detector.
– Fasten the front cover by turning it clockwise.
– The detector is after about 40s operational and is automatically detected by
master.
Technical Data
Supply voltage | Via DALI Bus |
---|---|
Power consumption | 5.5mA |
Detection angle | 360° |
Detection range | max. Ø6m presence, approx. Ø24m at a height of 3m |
Installation height | 2–3.5m |
Protection class | IP54 |
Temperature range | -5 to +50 °C |
Dimensions | Edition UP: Ø100×46.4mm (visible dimensions) |
Edition AP: Ø117.3×45.9mm (visible dimensions)
Drill-hole (Edition UP)| Ø90mm
Colour| RAL9010
Sensitivity setup, factory reset and test mode
Programming and configuration are done via the P-IR remote control DALI
addressable Art.-Nr. 41934 (6).
The programming mode will indicated by the yellow LED. Each receiving of a
proper signal is confirmed with a short lapse of the yellow LED.
Note: At the secondary detectors allways, the yellow led flash as a response to a pressing of the «Lock/Unlock» or «Status» button ( the master always response with the green LED).
Setting of sensitivity (1)
The 360° detection range is split into 3 sectors A – B – C of 120° each. Sensitivity may be adjusted either for all three sectors or for each individual sector. Sectors may be completely deactivated.
Sensitivity setup for all 3 sectors:
- Briefly press «Lock/Unlock» button: Programming mode
- Briefly press «Sens.» button: sensitivity for all 3 sectors
- Set sensitivity by pressing «1» for Max, «2» for High, «3» for Low, «4» for Min
- Briefly press «Lock/Unlock» button: Operating mode
Warnings regarding installation
The installation of products that will permanently be part of the electrical
installation and which include dangerous voltages, should be carried out by a
qualified installer and in accordance with the applicable regulations. This
user manual must be presented to the user. It should be included in the
electrical installation file and it should be passed on to any new owners.
Additional copies are available on the Niko website or via Niko customer
services.
CE marking
This product complies with all of the relevant European guidelines and regulations. For radio equipment Niko llc declares that the radio equipment in this manual conforms with the 2014/53/EU directive. The full text of the EU declaration of conformity is available at www.niko.eu under the product reference, if applicable.
Support & contact
nv Niko sa
Industriepark West 40
9100 Sint-Niklaas, Belgium
www.niko.eu
+32 3 778 90 80
support@niko.eu
Niko prepares its manuals with the greatest care and strives to make them as complete, correct and up-to-date as possible. Nevertheless, some deficiencies may subsist. Niko cannot be held responsible for this, other than within the legal limits. Please inform us of any deficiencies in the manuals by contacting Niko customer services at support@niko.eu.