EXOR eSMART107 Essential Resistive Touch Controller 7 Inch Display Installation Guide
- June 12, 2024
- EXOR
Table of Contents
**EXOR eSMART107 Essential Resistive Touch Controller 7 Inch Display
**
DIMENSION-CUT OUT
A | B |
---|---|
176mm/06.90” | 136mm/05.35” |
MODEL | H |
--- | --- |
eSMART107 | 147mm/05.79” |
MODEL | CSD |
--- | --- |
eSMART107 | 600mm/23.62” |
CSD = Minimum Compass Safe Distance of standard compass
CSD2 = Minimum Compass Safe Distance of steering compass, standby
steering compass, emergency compass
FIXING BRACKET
- A. eSMART107
- B. Installation cut-out
Tightening torque: 75 Ncm
REAR VIEW
1 | Power supply (11-30Vdc) | 6 | USB |
---|---|---|---|
2 | RS422/485 + CAN (COM2 / CAN0) | 7 | ETH0 – 10/100Mbit/s |
3 | RS422/485 + CAN (COM3 / CAN1) | 8 | ETH1 – 10/100Mbit/s |
4 | RS232 + RS232 (COM1 / COM4) | 9 | RS485 + CAN port configuration |
5 | USB | 10 | RS485 + CAN port configuration |
All ports are SELV (Safety Extra – Low Voltage) according European Standards and Class 2 according UL Standards
POWER SUPPLY
Extra low voltage power supply / Limited power source.
DC Power Connector – AWG24 wire size – R/C Terminal Blocks (XCFR2), Female pitch 5.08mm, torque 4.5 lb-in (50Ncm)
Don’t open the panel rear cover when the power supply is applied.
The unit must always be grounded to earth. Earth connection will have to be
done using either the screw or the fast on terminal located near the power
supply terminal block. Also connect to ground the terminal 3 on the power
supply terminal block.
Ensure that the power supply has enough power capacity for the operation of the equipment.
Ensure that the power supply has enough power capacity for the operation of the equipment.
CONNECTIONS
The kit supplied with the panel contains the terminals and the contacts for wiring.
Reference | Pin | Description |
---|---|---|
X4 RS232 (COM1) | 1 | GND |
2 | TxD | |
3 | RxD | |
4 | RTS | |
5 | CTS | |
X4 RS232 (COM4) | 6 | GND |
7 | TxD | |
8 | RxD | |
9 | RTS | |
10 | CTS |
Terminal and contact 43025-1000 and 43030-0001 MOLEX
Reference | Pin | Description |
---|---|---|
X2 RS485 (COM2) | 1 | Used by CAN |
2
3
4
5
6| Reserved
7| GND
8| Reserved
9| Y (TX+)
10| Z (TX-)
11| A (RX+)
12| B (RX-)
Terminal and contact 43025-1200 and 43030-0001 MOLEX
Reference | Pin | Description |
---|---|---|
X3 RS485 (COM3) | 1 | Used by CAN |
2
3
4
5
6| Reserved
7| GND
8| Reserved
9| Y (TX+)
10| Z (TX-)
11| A (RX+)
12| B (RX-)
Terminal and contact 43025-1200 and 43030-0001 MOLEX
Reference | Pin | Description |
---|---|---|
X2 CAN0 | 1 | GND |
2 | Reserved | |
3 | CAN-H | |
4 | CAN-L | |
5 | Reserved | |
6 | Used by RS485 |
7
8
9
10
11
12
Terminal and contact 43025-1200 and 43030-0001 MOLEX
Reference | Pin | Description |
---|---|---|
X3 CAN1 | 1 | GND |
2 | Reserved | |
3 | CAN-H | |
4 | CAN-L | |
5 | Reserved | |
6 | Used by RS485 |
7
8
9
10
11
12
Terminal and contact 43025-1200 and 43030-0001 MOLEX
RS485 – CAN port configuration (ref. S1 – S2)
Reference | Pos | Description |
---|---|---|
S1 | 1 | CAN0 termination |
2 | CAN0 termination | |
3 | RS485 half duplex | |
4 | RS485 half duplex | |
5 | RS485 termination (COM2) | |
6 | RS485 termination (COM2) | |
S2 | 1 | CAN1 termination |
2 | CAN1 termination | |
3 | RS485 half duplex | |
4 | RS485 half duplex | |
5 | RS485 termination (COM3) | |
6 | RS485 termination (COM3) |
For use in Pollution Degree 2 Environment, Maximum Surrounding Air Temperature 50°C
CAUTION: FOR USE IN A CONTROLLED ENVIRONMENT, REFER TO MANUAL FOR ENVIRONMENTAL CONDITIONS.
DISPOSE OF BATTERIES
Dispose of batteries according to local regulations.
This device cannot be disposed of as a domestic waste but according to WEEE European Directive 2012/19/EU
The products have been designed for use in an industrial environment in compliance with the 2014/30/EU directive
The products have been designed in compliance with:
EN 61000-6-4 EN 55011 Class A EN 61000-6-3 EN 55022 Class B
EN 61000-6-2 EN 61000-4-2 EN 61000-6-1 EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-8
EN 60945
Software available in this product is based on OpenSource. Visit oss.exorint.net for more details.
Reproduction of the contents of this copyrighted document, in whole or part, without written permission of Exor International S.p.A., is prohibited.
User Manual available on: www.exorint.com
Customer Service
MANESMA107U001 V.1.10 09.08.2022
©2014-2022 Exor International S.p.A
Exor International S.p.A. – San Giovanni Lupatoto VR, Italy
www.exorint.com