EXOR eSMART04xx Industrielle Touch Panel HMI / PLC Installation Guide
- June 10, 2024
- EXOR
Table of Contents
EXOR eSMART04xx Industrielle Touch Panel HMI / PLC
DIMENSION-CUT OUT
MODEL | A | B |
---|---|---|
eSMART04xx | 136mm/05.35” | 96mm/3.78” |
eSMART07xx | 176mm/06.93” | 136mm/5.35” |
eSMART10xx | 271mm/10.66” | 186mm/7.32” |
MODEL | C | H |
--- | --- | --- |
eSMART04xx | 29mm/01.14” | 107mm/04.21” |
eSMART07xx | 29mm/01.14” | 147mm/05.79” |
eSMART10xx | 29mm/01.14” | 197mm/07.75” |
Model | CSD | CSD2 |
--- | --- | --- |
eSMART04xx | 350mm/13.77” | 200mm/07.87” |
eSMART07xx | 500mm/19.68” | 400mm/15.74” |
eSMART07Mx | 550mm/21.65” | 350mm/13.77” |
eSMART10xx | 350mm/13.77” | 250mm/09.84” |
- CSD = Minimum Compass Safe Distance of standard compass
- CSD2 = Minimum Compass Safe Distance of steering compass, standby steering compass, emergency compass
FIXING BRACKET
- A. eSMARTxxxx
- B. Installation cut-out
Tightening torque: 75 Ncm
REAR VIEW
- Serial port (5V 100mA max.)
- Ethernet port
- USB port (version 2.0, 5V 500mA max)
- Power supply (18-32Vdc)
WARNING – (USB Connectors) NOT FOR USE IN HAZARDOUS LOCATIONS
All ports are SELV (Safety Extra – Low Voltage) according European Standards and Class 2 according UL Standards For use in Pollution Degree 2 Environment, Maximum Surrounding Air Temperature 50°C
CAUTION : FOR USE IN A CONTROLLED ENVIRONMENT, REFER TO MANUAL FOR ENVIRONMENTAL CONDITIONS
The graphic panel must not be exposed to direct sunlight. The vents in the panel casing must not be obstructed. The products have been designed for use in Hazardous Location according ANSI/ISA-12.12.01
POWER SUPPLY
Extra low voltage power supply Limited power source
DC Power Connector – AWG24 wire size – R/C Terminal Blocks (XCFR2), Female pitch 5.08mm, torque 4.5 lb-in (50Ncm)
Do not open the cabinet while the system is powered up. Don’t open the panel rear cover when the power supply is applied. The unit must always be grounded to earth. Earth connection will have to be done using either the screw or the faston terminal located near the power supply terminal block. Also connect to ground the terminal 3 on the power supply terminal block
Ensure that the power supply has enough power capacity for the operation of the equipment.
WARNING : Do not separate when energized
CONNECTIONS
Pin | Description |
---|---|
1 | GND |
2 | |
3 | TX/CHA- |
4 | RX/CHB- |
5 | |
6 | +5V output |
7 | CTS/CHB+ |
8 | RTS/CHA+ |
9 |
To operate in RS485 pins 4-3 and 8-7 must be connected externally
USAGE IN EXPLOSION-HAZARDOUS AREAS ZONE 2 AND ZONE 22
The connection and installation have to be done in conformity with ATEX Directive, EN 60079-14, and have to be performed by authorized, qualified personnel and in possession of necessary skillsConfirm that the location is free from explosively hazardous gases or dust before connecting or disconnecting equipment, replacing or wiring modules. Confirm that the power supply has been turned OFF before disconnecting, replacing or wiring modules Check that graphic panels are mounted in an industrial control panel/enclosure satisfying minimum IP54 degree of protection for application in zone 2.
WARNING – Power, input and output (I/O) wiring must be in accordance with Class I, Division 2 wiring methods, Article 501.10 (B) of the National Electrical Code, NFPA 70 for installation in the U.S., or as specified in Section 18-1J2 of Canadian Electrical Code for installations within Canada and in accordance with the authority having jurisdictions.
- A. WARNING – EXPLOSION HAZARD – SUBSTITUTION OF ANY COMPONENT MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2
- B. WARNING – EXPLOSION HAZARD – DO NOT CONNECTO OR DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN REMOVED OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.
- C. SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C AND D HAZARDOUS LOCATIONS, OR NONHAZARDOUS LOCATIONS ONLY.
- D. INSTALL IN AN ENCLOSURE SUITABLE FOR THE ENVIRONMENT SUCH THAT THE EQUIPMENT IS ONLY ACCESSIBLE WITH THE USE OF A TOOL.
This device cannot be disposed of as a domestic waste but according to WEEE European Directive 2012/19/EU
PRODUCT IDENTIFICATION
The product may be identified through a plate attached to the rear cover. You will have to know the type of unit you are using for correct usage of the information contained in the guide. An example of this plate is shown in the figure below
- product model name eSMART04
- product part number ESMA04U301
- year/week of production 2244
- serial number AA0001002000000001AA
- version id of the product 100201A07006000
- manufacturer address and read instruction warning Exor International S.p.A.
Specific conditions of use
- The equipment shall only be used in an area of at least pollution degree 2, as defined in EN 60664-1.
- The equipment shall be installed in an enclosure that provides a minimum ingress protection of IP 54 in accordance with EN 60079-0.
- Transient protection shall be provided that is set at a level not exceeding 140 % of the peak rated voltage value at the supply terminals to the equipment.
Ensure that the labelling specifications are compatible with the conditions permitted for the hazardous area at the site where it is being used (Zones 2) Type examination certificate number: DEMKO 16 ATEX 1761X / UL22UKEX2725X
Software available in these products is based on OpenSource. Visit oss.exorint.net for more details. Reproduction of the contents of this copyrighted document, in whole or part, without written permission of Exor International S.p.A., is prohibited User Manual available on www.exorint.com
©2014-2022 Exor International S.p.A Exor International S.p.A. – San Giovanni Lupatoto VR, Italy www.exorint.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>