SmartGen HAT162 ATS Controller User Manual
- June 4, 2024
- SmartGen
Table of Contents
- Introduction
- OVERVIEW
- PERFORMANCE AND CHARACTERISTICS
- SPECIFICATION
- OPERATION
- CLOSE FAULT ALARM
- WIRE CONNECTION
- DEFINITION AND RANGE OF PARAMETERS
- PARAMETERS SETTING
- TYPICAL APPLICATION
- OVERALL DIMENSION AND PANEL CUTOUT
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SmartGen HAT162 ATS Controller User Manual
Introduction
All rights reserved. No part of this publication may be reproduced in any
material form (including photocopying or storing in any medium by electronic
means or other) without the written permission of the copyright holder.
Applications for the copyright holder’s written permission to reproduce any
part of this publication should be addressed to SmartGen Technology at the
address above.
Any reference to trademarked product names used within this publication is
owned by their respective companies.
SmartGen Technology reserves the right to change the contents of this document
without prior notice.
Date | Version | Content |
---|---|---|
2018-05-10 | 1.0 | Original release. |
2022-08-09 | 1.1 | Update company logo and manual format. |
OVERVIEW
HAT162 ATS Controller is suitable for no breaking two stage ATS. It can
accurately detect 2-way-3-phase voltage and judge voltage abnormal (such as
over voltage, under voltage, over frequency, under frequency, lack of phase
and phase rotation), and then control ATS to switch. When ATS switches
abnormally, the controller can detect close/open failure and alarm on the
front panel to ensure the correct action of ATS. In auto mode, if source 1
failure, controller will send signal to start the genset.
Moreover, it can also realize remote communication, remote control and
parameter configuration functions via LINK port communication.
PERFORMANCE AND CHARACTERISTICS
HAT162 controller can detect 2-way voltage (2-way mains, 1-way mains and 1-way gen ) and control ATS.
Mains characters are as below,
-
It is suitable for AC system with 3-phase 4-wire, 2-phase 3-wire, single phase, 3-phase 3-wire (special order required);
-
“1# Main (auto transfer and restore)”, “2# Main (auto transfer and restore)”, and “No Main Use (auto transfer and non-auto restore)” power supply methods;
-
Measuring and displaying 2-way voltage and frequency: 1# 2#
Phase voltage (Ua, Ub, Uc) Phase voltage (Ua, Ub, Uc)
Line voltage (Uab, Ubc, Uca) Line voltage (Uab, Ubc, Uca)
Frequency Hz Frequency Hz -
With over/under voltage, over/under frequency, loss of phase, and reverse phase sequence detection functions;
-
Breaker close fail alarm indication;
-
LEDs on the panel can clearly display ATS working status;
-
Auto/Manual mode can be switched. In manual mode, ATS can be switched by pressing front panel button;
-
With manual commissioning function;
-
Applicable for 2 isolated neutral line.
-
Close output can be configured as pulse and continuous output;
-
Parameter setting: parts of parameters can be adjust from front panel; all can be adjust via LINK port (with SG72 adaptor) by using computer software;
-
Digitization adjustment of parameters (abandon simulation adjustment of regular potentiometer, and enhanced reliability and stability);
-
Modular design, self-extinguishing ABS+PC plastic shell, pluggable terminal, and compact structure;
-
Three installation ways: panel built-in, internal 35mm guide rail installation and screw mounting.
SPECIFICATION
Table 2 Specification Parameters
Items | Contents |
---|---|
Operating Voltage | AC power A1N1/A2N2 supply. |
Rated AC240V (range: AC170V~277V)
Power Consumption| Under rated voltage, power consumption is not more than 3VA
AC Voltage Input: 3-phase 4-wire
2-phase 3-wire
Single phase 2-wire 3-phase 3-wire| AC170V – AC277V (ph-N) AC170V – AC277V
(ph-N) AC170V – AC277V (ph-N) AC170V – AC277V (ph-ph) (special order required)
AC Frequency| 50/60Hz
1# Close Relay| 16A AC250V Volt free output (Normally open)
2# Close Relay| 16A AC250V Volt free output (Normally open)
Oil Engine Start Relay| 7A AC250V Volt free output (Normally close)
Programmable Output Relay| 7A AC250V Volt free output (Normally open)
Communication| LINK interface, MODBUS-RTU Protocol
Case Dimensions| 86.9mmx158mmx119.5mm
Panel Cutout| 73.5mmx144mm
Working Temperature| (-25~+70)°C
Working Humidity| (20~93)%RH
Storage Temperature| (-25~+70)°C
Protection Level| IP65: when water-proof gasket installed between control
panel andenclosure.
Insulation Strength| Apply AC2.2kV voltage between high voltage terminal and
low voltage terminal;
The leakage current is not more than 3mA within 1min.
Weight| 0.6kg
OPERATION
FRONT PANEL DESCRIPTION
Fig.1 Front Panel Description
KEY FUNCTION DESCRIPTION
Table 3 Keys Description
Icon | Function | Description |
---|
| Auto (Set)| Auto/Manual mode switch;
Enter into lamp test status by pressing for 3s;
Enter into parameter configuration mode by pressing for 8s.
| 1# Close (Increase)| 1# close in manual mode;
Adjust parameters in parameter configuration mode.
| 2# Close (Decrease)| 2# close in manual mode;
Adjust parameters in parameter configuration mode.
****| Test (Confirm)| It is active in manual mode;
While genset start signal is active, press it can deactivate the genset start
signal;
While genset start signal is inactive, press it can active the genset start
signal;
Confirm user-defined parameters in parameter setting screen.
INDICATOR DESCRIPTION
Table 4 Indicator Description
Indicators | Description |
---|---|
1# Power | Lamp illuminates: 1# power normal; |
Lamp flashes: 1# power abnormal (over/under voltage, over/under frequency,
loss of phase, and reverse phase sequence);
Lamp off: 1# loss of power.
2# Power | Lamp illuminates: 2# power normal;
Lamp flashes: 2# power abnormal (over/under voltage, over/under frequency,
loss of phase, and reverse phase sequence);
Lamp off: 2# loss of power.
1# Main| Lamp illuminates: 1# Priority (auto transfer and restore).| Both
illuminate: “mutual backup (auto transfer and non-restore)”.
2# Main | Lamp illuminates: 2# Priority (auto transfer and restore).
1# Close | Lamp illuminates: 1# Supply.
2# Close | Lamp illuminates: 2# Supply.
Alarm | Lamp illuminates: 1# or 2# Close fault.
Auto/Manual Mode | Lamp illuminates: controller in Auto mode;
Lamp off: controller in Manual mode.
Genset Status| Lamp illuminates: genset start signal outputs;
Lamp flashes: genset start signal not output.
OPERATION
AUTO/MANUAL MODE SWITCH
When the controller is normally working, if auto/manual mode indicator is off, it means controller is in manual mode; it can switch into auto mode by pressing , the indicator will be normally light; then press again to switch back to manual mode.
NOTE: After re power-on, controller mode depends on the mode in which the controller was last powered down. When the controller is powered off in manual mode, the controller is still in manual mode after re power-on.
MANUAL OPERATION
When controller is in manual mode, if press , 1# close relay outputs, and 1# close status indicator illuminated when 1# close status input detecting is active, and then 1# supply ramps on load; if press , 2# close relay outputs, and 2# close status indicator illuminated when 2# close status input detecting is active, and then 2# supply ramps on load.
AUTO OPERATION
In auto mode, controller can switch between 1# supply and 2# supply automatically.
MANUAL TEST
In manual mode, when genset start signal is active, press can deactivate the genset start signal. When genset start signal is inactive, press can active the genset start signal.
CLOSE FAULT ALARM
Breaker close fault is divided into 1# supply breaker close fault and 2#
supply breaker close fault.
After the controller send a breaker close fault alarm, alarm indicator
flashes.
Process of trigger 1# supply close fault alarm is as below:
When 1# supply voltage is normal, controller will initiate a command of close
1# supply; if 1# close input signal cannot be detected, 1# supply will be open
and close again. If controller still cannot detect the 1# close signal, it
will be regarded as 1# close failure and the alarm indicator illuminates at
the same time. Meanwhile, if 2# supply voltage is normal and doesn’t occur
close fault, then 2# power will be closed.
Process of trigger 2# supply close fault alarm is as below:
When 2# supply voltage is normal, controller will initiate a command of close
2# supply; if 2# close input signal cannot be detected, 1# supply will be open
and close again. If controller still cannot detect the 2# close signal, it
will be regarded as 2# close failure and the alarm indicator illuminates at
the same time. Meanwhile, if 1# supply voltage is normal and doesn’t occur
close fault, then 1# power will be closed.
Reset close fault alarm: after alarm occurs, switch controller to manual mode to reset alarm. This moment, troubleshooting and ATS transfer test can be carried out.
NOTE: After reset alarms, the fault must be checked and cleared.
WIRE CONNECTION
Fig.2 Controller Rear Panel Drawing
Table 5 Terminals Description
No. | Items | Function Description | Remark |
---|---|---|---|
1 | N2 | 2# AC 3-phase 4-wire input | Single phase 2-wire: connect with A2 and |
N2, B2 and C2 are not connected;
2- phase 3-wire: connect with A2, B2, and N2, C2 is not connected;
3- phase 3-wire: connect with A2, B2, and C2,
N2 is not connected (special order required).
2| C2
3| B2
4| A2
5| N1| 1# AC 3-phase 4-wire input| Single phase 2-wire: connect with A1 and
N1, B1 and C1 are not connected;
2- phase 3-wire: connect with A1, B1, and N1, C1 is not connected;
3- phase 3-wire: connect with A1, B1, and C1,
N1 is not connected (special order required).
6| C1
7| B1
8
| ****
A1
9| 1# Close Relay| Volt free normally open contact output| Rated capacity:
16A/250VAC
10
11| 2# Close Relay| Volt free normally open contact output| Rated capacity:
16A/250VAC
12
13| Gen Start Signal output| Volt free normally close contact output| Rated
capacity: 7A/250VAC
14
15| Aux. output| Volt free normally open contact output| Rated capacity:
7A/250VAC
16
17| NC| | Not connect
18| 1# Close Input| Detect 1# breaker close status, auxiliary contact
input.|
Ground is active.
19| 2# Close Input| Detect 2# breaker close status, auxiliary contact input.|
Ground is active.
20| Common Port| GND|
LINK| Communication Port| Communicate with PC and used for program update|
Used with SG72 adaptor.
F1| Fuse| | Rated 10A 250V.
F2| Fuse| | Rated 10A 250V.
DEFINITION AND RANGE OF PARAMETERS
No. | Items | Range | Default | Description |
---|---|---|---|---|
1 | AC System | (1-4) | 1 | 1: 3 Phase, 4 Wire (3P4W) |
2: Single Phase, 2 Wire (1P2W)
3: 3 Phase, 3 Wire (3P3W) (special order required)
4: 2 Phase, 3 Wire (2P3W)
2| S1 Nomal Delay| (1-7)| 2| 1: 1s
2: 5s
3: 10s
4: 20s
5: 30s
6: 45s
7: User defined (Default: 5s)
3| S2 Normal Delay| (1-7)| 2| 1: 1s
2: 5s
3: 10s
4: 20s
5: 30s
6: 45s
7: User defined (Default: 5s)
4| S1 Abnormal Delay| (1-7)| 2| 1: 1s
2: 5s
3: 10s
4: 20s
5: 30s
6: 45s
7: User defined (Default: 5s)
5| S2 Abnormal Delay| (1-7)| 2| 1: 1s
2: 5s
| | | | 3: 10s
4: 20s
5: 30s
6: 45s
7: User defined (Default: 5s)
6| Close Delay| (1-7)| 4| 1: Continuous Close Enabled 2: 1s
3: 3s
4: 5s
5: 8s
6: 10s
7: User defined (Default: 5s)
7| Again Open Delay| (1-7)| 2| 1: 1s
2: 3s
3: 5s
4: 8s
5: 10s
6: 15s
7: User defined (Default: 3s)
8| Transfer Delay Expired| (1-7)| 1| 1: 0.5s
2: 1s
3: 2s
4: 3s
5: 4s
6: 5s
7: User defined (Default: 0.5s)
9| Gen Start Delay| (1-7)| 4| 1: 3s
2: 8s
3: 15s
4: 30s
5: 50s
6: 70s
7: User defined (Default: 30s)
10| Gen Stop Delay| (1-7)| 6| 1: 3s
2: 8s
3: 15s
4: 30s
5: 50s
6: 70s
7: User defined (Default: 90s)
11| Set Priority| (1-3)| 1| 1: S1 Priority
2: S2 Priority
3: No priority
NOTE:
- The parameters in this form can be set via computers and slave;
- When delay is “7: User defined”, parameter delay must be set via computer. If parameter is not set via computer, the delay is Default; if parameter has been set via computer, then the delay is the set value.
Table 7 Parameters Definition and Range Table (2)
No. | Item | Range | Default | Description |
---|---|---|---|---|
1 | Rated Voltage | (170-270)V | 230 | Provide base for over/under volt judge. |
2 | Rated Frequency | (50.0-60.0)Hz | 50.0 | Provide base for over/under frequency |
judge.
3| Over Voltage Warn| (0-1)| 1| 0: Disabled 1: Enabled
4| Over Volt Set Value| (100-120)%| 115| Threshold value
5| Over Volt Return Value| (100-120)%| 113| Return value
6| Under Voltage Warn| (0-1)| 1| 0: Disabled 1: Enabled
7| Under Volt Set Value| (70-100)%| 75| Threshold value
8| Under Volt ReturnValue| (70-100)%| 77| Return value
9| Over Frequency Warn| (0-1)| 1| 0: Disabled 1: Enabled
10| Over Freq. Set Value| (100-120)%| 110| Threshold value
11| Over Freq. Return Value| (100-120)%| 104| Return value
12| Under Freq. Warn| (0-1)| 1| 0: Disabled 1: Enabled
13| Under Freq. Set Value| (80-100)%| 90| Threshold value
14| Under Freq. Return Value| (80-100)%| 96| Return value
15| Loss of Phase| (0-1)| 1| 0: Disabled 1: Enabled (fixed delay as 3s)
16| Reverse Phase Seq.| (0-1)| 0| 0: Disabled 1: Enabled (fixed delay as
3s)
17| Output Ports| (0-16)| 0| 0: Not Used
1: S1 Volts Normal 2: S1 Volts Abnormal 3: S2 Volts Normal 4: S2 Volts
Abnormal
: Manual Status Output 6: Auto Status Output
7: Gens Start Output(NO) 8: Gens Start Output(NC) 9: S1 Close Output
10: S2 Close Output
11: S1 Close Status Output 12: S2 Close Status Output 13: Reserved
14: Reserved
15: Reserved
16: Reserved
18| Module Address| (1-254)| 1| Address that communicates with PC software.
PARAMETERS SETTING
PARAMETERS SETTING MODE
In manual mode, enter into parameters setting mode by pressing for 8s and manual/auto indicator and gen status indicator flash; ①, ②, ③, ④ indicators illuminate. LED numbers please to see the following picture.
Fig.3 Parameter Configuration
NOTE: At this moment, press will return to normal mode after LED flash.
PARAMETERS SETTING
When it entered into parameter setting mode, users can adjusting parameters by
pressing .
And ④ and ⑦ LEDs are illuminated. ①, ②, ③, ④ indicators mean setting items
numbers (currently item number is 1); ⑤, ⑥, ⑦ indicators mean these parameter
values (currently parameter value is 1). Configurable parameter list please
check “Table 6 Parameters Definition and Range Table (1)” of item.
Specific settings are as below:
- Select setting number which needs to adjust by pressing and ;
- Enter into setting status by pressing and ⑦ indicator flashes;
- After set this parameter by pressing and , and press the key to save the value.
- Hold and press after all parameters are configured, and release when all LEDs flash, which means parameters are all saved and then it will return to normal mode.
NOTE: See “Table 8 Parameter Value Comparison” for the values corresponding of LED indicators.
NOTE: After parameters configured completely, users need to press to back to the normal mode to save the parameters. Otherwise, the setting parameters will be lost after controller power outage.
Table 8 Parameter Value Comparison
Parameter Serial No. LED Indicate| Value| Parameter Value LED
Indicate| Value
---|---|---|---
①| ②| ③|
④
| ⑤|
⑥
| ⑦
|
|
|
| 1|
|
|
| 1
|
|
|
| 2|
|
|
| 2
|
|
|
| 3|
|
|
| 3
|
|
|
| 4|
|
|
| 4
|
|
|
| 5|
|
|
| 5
|
|
|
| 6|
|
|
| 6
|
|
|
| 7|
|
|
| 7
|
|
|
| 8|
|
|
|
|
|
|
| 9|
|
|
|
|
|
|
| 10|
|
|
|
|
|
|
| 11|
|
|
|
RESET TO DEFAULT
RESET TO DEFAULT
In parameter setting mode, press , ①, ② and ③ LEDs illuminated, and ⑦ LED
flashes.
After pressing , ⑦ LED illuminates for 2s, indicating that the factory value
has been restored.
Meanwhile, all LEDs flash for 3 times and return back to the normal mode.
NOTE: If do not need to restore to factory value, press to return to the normal mode after LED flashes.
TYPICAL APPLICATION
Fig.4 SGQ-N Wire Connection
Fig.5 SGQ-T Wire Connection
Fig.6 SGQ-M Wire Connection
NOTE: Please refer to the above drawings for wiring. The actual wiring on site is subject to the ATS switch wiring instructions. And the capacity of the fuse should be selected according to the actual power consumption at the site, which cannot be based on the fuse capacity in the drawing.
Fig.7 2 Phase 3 Wire Connection
Fig.8 Single Phase 2 Wire Connection
NOTE: The above drawing shows the wiring method is the AC phase voltage of 220V. If the AC phase voltage is 110V in actual use, please contact our technical personnel to confirm the specific wiring method.
OVERALL DIMENSION AND PANEL CUTOUT
CASE DIMENSION
Fig.9 Overall Dimensions
CUTOUT DIMENSION
The controller has three installation ways: panel built-in, internal 35mm slideway and internal screw mounting. Panel built-in and internal screw mounting are as below:
Fig.10 Cutout Dimensions
INSTALLATION
Fig.11 Panel Built-in Installation
Fig.12 35mm Guide Rail Installation
Fig.13 Screw Installation
TROUBLESHOOTING
Tale 9 Troubleshooting
Symptom | Possible Solutions |
---|---|
Controller no operation | Check connections and voltages of 1# and 2# power; |
Check F1 or F2 fuse.
Controller displays normal but switch not activate| Check ATS;
Check the connections between controller and ATS.
1# or 2# power LED flashes| Check whether AC voltage is normal or not.
Alarm LED flashes| If switch close failure alarms, please check switch
auxiliary contact wiring.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>