xpr MTPX-RS-MF Elegant and Compact 13.56MHz Mifare Reader Instruction Manual
- June 12, 2024
- xpr
Table of Contents
**xpr MTPX-RS-MF Elegant and Compact 13.56MHz Mifare Reader
**
SPECIFICATIONS
Technology: Proximity (13.5 MHz, ISO14443-A)
Interface: RS-485, WS4 series compatible
Supported credentials: Mifare (Classic, Desfire, Plus, Ultralight)
Read range: Up to 6 cm
Power supply: 9 – 14 VDC, 120 mA
Sound Indicator: Internal buzzer
LED Indicators: Red, Green and Orange (Red + Green)
Environmental rating: Outdoor, IP65
Operating humidity: 5% – 95% relative humidity, non-condensing
Operating temperature: -20°C to 50°C
Mounting: Surface mount
Panel connection: Cable 0.5m
Dimensions (mm): 92 x 51 x 27
MOUNTING
Ferrite Core
Rubber gasket
Front
Back
Mounting base (optional)
Wrap the wires around the ferrite core (1 turn).
The ferrite core is provided with the kit and it is used to reduce the EMI.
WIRING
Connection reader to controller WS4
- Reader address
Connection two readers per RS-485 line
The readers for Doors 1.0 and 2.0 must be at address 0 and those for Doors 1.1
and 2.1 at address 1. For doors equipped with 2 readers, one must be at
address 0 and the other at address 1.
Recommended cabling:
Multiconductor cable 2 twisted pair with shielding. Max length: 80 m. The
cable shielding will be connected to the fixing clamp of the access unit. If
more than 80 m. are needed, then termination resistors(120 ohm) may be
required at both ends of the RS-485 line, while taking into consideration the
lengths proposed on our web site.
VISUAL AND AUDIO SIGNALIZATION
Access denied/Break-in/Too long opened/Reader off-line/Reader tamper/Door
contact tamper: Red, fast blinking
Pre-alarm: Red, fast blinking, Continuous beep
Mantrap/Forbidden period: Red ON
Emergency/Unlocked/Free period: Green, fast blinking
Access allowed/Lock ON (toggle mode): Green ON
Last person leaves the building: Multiple beeps
SOFTWARE SETTINGS
Go to Doors, select the Reader(fig.2) and then select “Mifare/Desfire” for
Card. (fig.3)
While off line, red LED blinks fast and buzzer beeps continuously. Once
communication is established, the red LED and the buzzer stop. Green LED
starts to blink continuously. If you want to stop the green LED, go to
Settings/System Options and select for the backlight ON or OFF (not default)
fig.4
CONNECTION TO PC
To update the firmware, run the XPR Toolbox and select ”WS4 readers” and
”MTPX-RS-MF V2” and click on “Open” tab. Follow the instruction in the
software to set up or update firmware.
This product herewith complies with requirements of EMC directive 2014/30/EU, Radio Equipment Directive 2014/53/EU. In addition it complies with RoHS2 directive EN50581:2012 and RoHS3 Directive 2015/863/EU.