IDEAL INV-7112 UPS Line Interactive User Manual
- June 12, 2024
- IDEAL
Table of Contents
IDEAL INV-7112 UPS Line Interactive
This manual provides safety, installation, and operation instructions that will guide you to the best performance of your equipment. Please read and keep this manual.
INTRODUCTION
System Description
The Product is line interactive UPS provides guaranteed battery backup power
during outages and unsafe fluctuations, along with full protection from
damaging surges and spikes. The UPS is integrated with a microprocessor
controller, voltage stabilizer, and LCD display in a stand-alone unit, to
provide the perfect protection to safeguard your critical devices and valued
data.
Features
- Line interactive design with microprocessor controlled.
- Auto restart upon AC recovery.
- Equipped with 2-Steps Boost & 1-Step Buck AVR to provide stable utility voltage.
- Built-in CC/CV battery charger and battery over-drain protection.
- DC start function enables UPS to start without AC power supplied.
- Off-mode charging enables UPS to charge itself even power switch is OFF.
- Provide lightning, surge, overload, and short circuit protection.
- Battery easy replacement design (Optional).
- LCD status indicator.
CAUTION
- The UPS contains electricity that is potentially hazardous. Qualified or certified technicians should proceed with all repairs and maintenance.
- The UPS has its own internal energy source (battery). The output receptacles may be active even when the UPS is not connected to an AC supply.
- The UPS is suitable for computers and electronic equipment with linear loads, but not suitable for electronic equipment with non-linear loads, such as motors & fluorescent lamps.
- Be sure to operate within the power rating of the UPS. Below 1/2 or 1/3 of the rated power is recommended for longer backup time.
- The UPS must be installed in a protected environment away from heating appliances such as a radiator or heater. DO NOT place the UPS near excessive humidity, under sunshine, or close to heating sources.
- If the UPS is out of order, disconnect the power cord and contact your dealer right away.
- The unit should be supplied by a grounded source. DO NOT operate the unit without a ground source.
- The UPS should be installed near to wall socket and equipment and be easily accessible.
- DO NOT plug the UPS’s power cord into UPS’s output socket. That will result in a safety hazard.
- A qualified technician or electrician in accordance with the local electrical code should perform the installation.
- DO NOT connect a laser printer or plotter to the UPS. A laser printer or plotter periodically draws significantly more power than its idle status and may overload the UPS.
OVERVIEW
Front Panel
- Power Switch: ON/OFF or silence button
- LCD screen
Rear Panel
- AC input line cord
- AC circuit breaker
- Backup/AVR/surge protection outlet
- Surge protection outlet
- Tel/Line/Modem surge protection RJ-45 port (Optional)
- Smart USB communication port (Optional)
OPERATION
Turn On/Off the Unit
- Turn on the UPS unit on AC mode by pressing the power switch for 1 second
- Turn off the UPS unit on AC mode by pressing the power switch for 4 seconds.
Connect to Utility and Charging
When UPS is connected to AC power and the power switch is on, UPS will charge
the battery automatically. The UPS is designed with the function of OFF-Mode
Charging, so UPS will charge the battery continuously when the power switch is
off and AC power is supplied. To power off UPS completely on OFF mode, please
remove the input of AC power.
DC Start
Turn on the UPS unit on Battery mode by pressing the power switch for 1
second. Turn off the UPS unit on Battery mode by pressing the power switch for
4 seconds, and UPS will be completely turned off in 10 seconds. Wait another
10 seconds to press the power switch for 1 second if you want to turn on the
UPS again.
Buzzer
Buzzer will beep when UPS is in Battery mode or having fault situations. Mute
the buzzer by pressing the power switch once. Restart the Buzzer by pressing
the power switch once again.
BATTERY CHARGING AND STORAGE
The UPS is shipping from Factory with an internal full-charged battery, but battery power might be lost during transportation. So please plug in the AC input line cord to wall outlet. For best result, charge the battery for at least 10 hours before initial use.
INDICATION
CHANGE BATTERY
- Remark: Only available for battery easy replacement design model UPS.
- Note: Small sparks may occur during battery connection, this is normal.
- Turn the UPS over, and slide the battery compartment cover off the battery housing.
- LIFT the battery out of the compartment, and disconnect wires from battery positive (+) and negative (-) terminals. Get a new battery and make sure to re-connect wires to positive and negative terminals correctly.
- Aligned all arrow marks and slide the battery compartment cover back onto the battery housing. Double-check if the battery compartment is well-locked.
TROUBLESHOOTING
Check UPS with the below steps when you face a UPS failure problem:
- Is the power switch of the UPS turned on?
- Is UPS plugged into a working wall outlet?
- Is line voltage within the rating specified?
- Is the circuit breaker on the UPS back panel active?
- Is UPS overloaded?
- Is the UPS battery not fully charged?
Use the table below to solve the UPS operation problems. If the problems cannot be resolved, please provide the model name, serial number, date of purchase, date of the problem occurred and full description of the problem including load status, UPS LCD status, UPS buzzer status, installation environment…etc. when calling for service.
SPECIFICATION
INPUT
- Voltage 110/115/120VAC or220/230/240VAC
- Voltage Range Label specified
- Frequency 50/60Hz auto-sensing
OUTPUT
- Capacity Label specified
- Voltage Regulation (Battery Mode) +/-10%
- Frequency 50/BOHz +/-1Hz
- Waveform Simulated sinewave
- Transfer Time «6ms (typical)
BATTERY
- Voltage 12VDC
- Recharge Time 5 hours to 90% after fully discharged
- Safety Protection Overcharge and over-discharge protection
- Advanced Battery Management Yes
INDICATORS
- LCD Programmed LCD
- Alarm Buzzer ON for battery mode, low battery, overload, fault
PROTECTION
- Short circuit
- Line Mode: AC breaker and electronic circuit
- Battery Mode: electronic circuit
- Over-temperature Thermal switch
- Over/Under Voltage Yes
- Surge Protection 175 Joules
SAFETY/REGULATORY
- Safety Approvals EN 62040-1
- EMC Compliance EN 62040-2
PHYSICAL
- Operating Temperature 0°C to 40°C (5’F to 104°F)
- Related Humidity 0 to 95% non-condensing
- Audible Noise < 40dB at 1M
- Dimension(D°W°H) 315.5°100*141mm
Read User Manual Online (PDF format)