nVent JBS-100-E Single Entry Power Connection with Junction Box Instruction Manual

June 12, 2024
nVent

nVent JBS-100-E Single Entry Power Connection with Junction Box

Product Information

  • Product Name: JBS-100-E, JBS-100-EP, JBS-100-L-E, JBS-100-L-EP – Available Languages: English (EN), German (DE), French (FR), Dutch (NL), Norwegian (NO), Swedish (SV), Danish (DA), Finnish (FI), Italian (IT), Spanish (ES), Polish (PL), Russian (RU), Czech (CZ), Hungarian (HU), Croatian (HR)
  • Product Types: BTV, QTVR, XTV(R), KTV, HTV
  • Rated Voltage: JBS-100-E(P): 480 Vac, JBS-100-L-E(P): 277 Vac
  • Maximum Pipe Temperature: Tmax intermittent, Tmax continuous, 1000 h cumulative Tmax power off
  • Heater Types: BTV, QTVR, XTV, XTVR, KTV, HTV, VPL

Product Usage Instructions

  1. Installation:
    • Before installing the product, read the installation instructions completely.
    • To prevent electrical shock, short circuit or arcing, the product must be installed correctly and water ingress must be avoided during the installation.
    • The purchaser should inform the manufacturer about any external effects or aggressive substances that the equipment may be exposed to.
  2. Safety Precautions:
    • Prolonged or repeated contact with the sealant in the core sealer may cause skin irritation. Wash hands thoroughly.
    • Overheating or burning the sealant will produce fumes that may cause polymer fume fever. Avoid contamination of cigarettes or tobacco. Refer to MSDS VEN 0033 for further information.
  3. Specific Conditions for Use:
    • For ATEX and IECEx approvals, specific conditions for use apply.
    • For voltages >254Vac and BTV, QTVR, XTV(R), KTV or HTV heating cables, use a power cable with continuous temperature resistance of minimum.
    • Use a metallic power cable gland approved for use in hazardous areas.
    • The maximum operating current shall be reduced to maximum 20 A. Please refer to the complete user manual for detailed instructions and safety information.

Single entry power connection with junction box

| BS- 100 -E BS- 100 -EP BS- 100 -L-E
BS- 100 -L-EP| |
---|---|---|---
| TB 20 ATEX 1008 U AS21UKEX0657U| Lighted version (1)
II 2 G Ex eb IIC Gb II 2 D Ex tb IIIC Db| Lighted version (2)
II 2 G Ex eb mb IIC Gb II 2 D Ex tb mb IIIC Db
| ECEx PTB 20.0014U| Ex eb IIC Gb Ex tb IIIC Db| Ex eb mb IIC Gb Ex tb mb IIIC Db
| | |
| |
| | JBS-100-E(P):
ТС RU C-BE.МЮ62.В.00054/18
Ex e IIC Gb U Ex tb IIIC Db U
Ex e mb IIC Gb U Ex tb mb IIIC Db U Ta –55°C…+56°C IP66
ООО “ТехИмпорт”
| | JBS-100-L-E(P):
ТС RU C-BE.МЮ62.В.00054/18
Ex e IIC Gb U Ex tb IIIC Db U
Ex e mb IIC Gb U Ex tb mb IIIC Db U Ta –55°C…+40°C IP66
ООО “ТехИмпорт”
| | Non lighted versions (1) :
Ex eb IIC Gb Ex tb IIIC Db| Lighted versions (2) :
Ex eb mb IIC Gb Ex tb mb IIIC Db
| |

Ex eb IIC T Gb
Ex eb mb IIC T
Gb

|
| | Non lighted versions (1) :

CL I ZN 1 AEx eb IIC T Gb ZN 21 AEx tb IIIC T°C Db
Ex eb IIC T Gb Ex tb IIIC T°C Db

| Lighted versions (2) :
CL I ZN 1 AEx eb mb IIC T Gb
ZN 21 AEx mb tb IIIC T
°C Db
Ex eb mb IIC T GbEx mb tb IIIC T°C Db

  • For system Temperature Code, see heating cable or design documentation.

    1. Non lighted versions:
    2. Lighted versions:

Warning: To prevent elec tri cal shock, short cir cuit or arc ing, this prod-uct must be in stalled cor rect ly and water ingress must be avoid ed before and during the in stal la tion.

Warning: The purchaser should make the manufacturer aware of any external effects or aggressive substances that the equipment may be exposed to.
Before installing this product, read the installation instructions completely.

Caution: Prolonged or repeated contact with the sealant in the core sealer may cause skin irritation. Wash hands thoroughly. Overheating or burning the sealant will produce fumes that may cause polymer fume fever. Avoid contamination of cigarettes or tobacco. Consult MSDS VEN 0033 for further information.

Rated voltage:| JBS-100-E(P): 480 Vac**

JBS-100-L-E(P): 277 Vac

---|---
Ambient temperature| JBS-100-E(P): –55°C to +56°C**

JBS-100-L-E(P): –40˚C to +40˚C up to 277 V for BTV, QTVR, XTV(R), KTV, HTV and VPL.

** Specific conditions for use apply for ATEX and IECEx.

Maximum pipe temperature:

Heater type| T max continuous| T max intermittent 1000 h cumulative| T max power off
---|---|---|---
BTV| 65°C| 85°C| –
QTVR| 110°C| 110°C| –
XTV| 121°C| 250°C| –
XTVR| 150°C| 250°C (2000 h)| –
KTV| 150°C| 250°C| –
HTV| 205°C| 260°C (2000 h)| –
VPL| See tables below| –| 260°C

VPL: Maximum pipe temperature in dependence of heater type, voltage and current

Heater Type| 230 Vac| 254 Vac| 277 Vac| 20 A| 25 A| 30 A
---|---|---|---|---|---|---
5VPL2-CT| 230°C| 225°C| 225°C| 180°C – 235°C| 150°C – 180°C| ≤150°C
10VPL2-CT| 210°C| 200°C| 195°C| 180°C – 235°C| 150°C – 180°C| ≤150°C
15VPL2-CT| 180°C| 145°C| 105°C| ≤180°C| 150°C – 180°C| ≤150°C
20VPL2-CT| 150°C| Not allowed| ≤150°C| ≤150°C| ≤150°C
| | | | |
Heater Type| 385 Vac| 400 Vac| 480 Vac| 20 A| 25 A| 30 A
5VPL4-CT| 230°C| 230°C| 230°C| 180°C – 235°C| 150°C – 180°C| ≤150°C
10VPL4-CT| 215°C| 215°C| 205°C| 180°C – 235°C| 150°C – 180°C| ≤150°C
15VPL4-CT| 195°C| 195°C| 160°C| ≤180°C| 150°C – 180°C| ≤150°C
20VPL4-CT| 150°C| 150°C| 150°C| ≤150°C| ≤150°C| ≤150°C

Specific conditions for use using ATEX or IECEx approvals:
For ambient temperatures >+40°C:
Use a power cable with continuous temperature resistance of minimum +90°C
Use a metallic power cable gland approved for use in hazardous areas (for example GL-38-M25-METAL).

For voltages >254Vac and BTV, QTVR, XTV(R), KTV or HTV heating cables:
Use a power cable with continuous temperature resistance of minimum +90°C
Use a metallic power cable gland approved for use in hazardous areas (for example GL-38-M25-METAL).
For pipe temperature > 150°C and XTV(R), KTV or HTV heating cables, the maximum operating current shall be reduced to maximum 20 A.

Tool Required

Assembly

Remove the tubes and dispose of them in the core sealer plastic bag.

BTV, QTVR, XTV(R), KTV, HTV, VPL

OPTION: To change direction of box opening: Loosen locknut. Lift box and rotate.

Install power cable and gland. Pull in power and ground wires, strip off 13 mm of insulation and terminate. (For -EP version only: connect earth plate to ground according to local requirements).

Install lid.
τ = 1.02 to 1.47 Nm
Apply insulation and cladding.
Weather seal the stand entry. Leave these instructions with the end user for future reference.

België / Belgique
Tel. +32 16 21 35 02
Fax +32 16 21 36 04
salesbelux@nVent.com

Česká Republika
Tel. +420 606 069 618
czechinfo@nVent.com

Danmark
Tel. +45 70 11 04 00
salesdk@nVent.com

Deutschland
Tel. 0800 1818205
salesde@nVent.com

España
Tel. +34 911 59 30 60
Fax +34 900 98 32 64
ntm-sales-es@nVent.com

France
Tél. 0800 906045
salesfr@nVent.com

Italia
Tel. +39 02 577 61 51
Fax +39 02 577 61 55 28
salesit@nVent.com

Nederland
Tel. 0800 0224978
salesnl@nVent.com

China
Tel. +86.21.2412.1688
cn.thermal.info@nVent.com

Казахстан
Tel. +7 712232 09 68
Fax +7 7122 32 55 54
saleskz@nVent.com

Lietuva
Tel. +370 5 2136633
Fax +370 5 2330084
info.baltic@nVent.com

Norge
Tel. +47 66 81 79 90
salesno@nVent.com

Österreich
Tel. 0800 29 74 10
salesat@nVent.com

Polska
Tel. +48 22 331 29 50
Fax +48 22 331 29 51
salespl@nVent.com

Россия
Тел. +7 495 926 18 85
Факс +7 495 926 1886
salesru@nVent.com

Schweiz / Suisse / Svizzera
Tel. +41 (41) 766 3080
Fax +41 (41) 766 3081
infoBaar@nVent.com

Suomi
Puh. 0800 11 67 99
salesfi@nVent.com

Sverige
Tel. +46 31 335 58 00
salesse@nVent.com

Türkiye
Tel. +90 545 284 09 05
Fax +32 16 21 36 04
salesee@nVent.com

United Kingdom
Tel. 0800 969 013
salesthermalUK@nVent.com

nVent.com/RAYCHEM

©2023 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice.

RAYCHEM-IM-EU1485-Elexant450c-ML-2304 PCN 1244-022472

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals