AKO-576410 Refrigerant Gas Detector Instructions

June 12, 2024
AKO

**AKO-576410 Refrigerant Gas Detector Instructions

**

General warnings

  • Using the unit without observing the manufacturer’s instructions may alter the appliance’s safety requirements.
  • Detectors should be installed in a place protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed the value indicated in the technical data.
  • Detectors supervise a point and not an area. If the gas leak does not reach the sensor, or the level of concentration in that point does not reach the alarm values, no alarm will be activated. If perimeter supervision is required, several sensors should be installed around that area.

Working conditions:

  • Keep the detector work environment free of chemical agents (such as solvent, paints, alcohol, acetone, silicone, etc.), andfree of engine fumes or gases from fermentations (bread, pizza) or ripening (breathing) of fruits.
  • The detector should generally be installed in an area of potential concentration/accumulation of gas, in low positions (due to the greater relative density, in relation to air, of the gases subject to detection).
  • The AKO-576410 / 576032 refrigerant gas detector may only be used in locations that have not been classified with risk of explosion.
  • Reference regulations: EN 378
  • Applicable local regulations: Compliance must be ensured

Installation

Installation
Installation
Installation
Installation

Installation
Installation
Installation
Installation

Technical specifications

Power supply 12-30 Vdc
Consumption Typical:75 mA,Maximum:150 mA
Alarm relay SPDT 30 Vdc,2A, cos j=1
Working ambient temperature 25 to 50 ºC
Storage ambient temperature 25 to 60 ºC
Range of moisture permitted 0 – 95 % RH (Without condensation)
Protection degree With cable entry using cable gland IP68
With cable entry from the back IP40
Dimensions 107 mm (W) x 85 mm (H) x 39 mm (D)

Description

Refrigerant gas detector, which can be used in independent operation or connected to alarm stations AKOCam, AKOAlarm and AKOGas. Independent detector:The detector makes a certain warning sound in the event of an Alarm ,Pre-Alarm or sensor error and the red indicator lights up (See operation section). Detector connected to the alarm station: The detector notifies the station of its status (Alarm, Pre-Alarm or sensor error) and the station notifies the alarm through sound and indicators (for further information consult the station’s manual).
Instruction

Alarm delay

Without delay

180 s

Alarm levels

A levels

B levels

 Always disconnect the power supply to do the wiring. The wiring between the detector/transmitter and the station should NEVER be installed in a conduit together with power,control or supply cables. Cables for wiring the relay contact should have an adequate section depending on the unit to be connected. Certain international standards maintain that the power supply of the alarm should originate from a different circuit to that used by the refrigeration and ventilation system. Please ensure that you comply with current local regulations.

GASES DETECTED

AKO-576410| R-410A
AKO-576032| R-32
| A LEVELS| **B LEVELS *
PRE-ALARM| ALARM| PRE-ALARM| ALARM
AKO-576410| 500 ppm| 1000 ppm| 1500 ppm| 3000 ppm
AKO-576032**| 500 ppm| 1000 ppm| 1000 ppm| 2000 ppm

Wiring

Connection to alarm station
Wiring Connection

Independent operation
Wiring Connection

Operation

Mute push-button
In the event of an Alarm or Pre-Alarm in process, any push-button press silences the Alarm/Pre-Alarm tone. Any push-button press deletes saved alarms.
Medium press (between 3 and 9 sec.): It activates or deactivates the SET- HOLD mode. Should there be a sensor error, reset the detector.
Long press ( > 9 sec.): It activates or deactivates the MAINTENANCE mode. Should there be a sensor error, reset the detector.

Indicators

| Red| Green| Blue
---|---|---|---
OFF| No alarms| Detector turned off| A levels active
ON| Alarm / Pre-Alarm activated| Standard operation| B levels active
Flashing| Alarm / Pre-Alarm saved| Standard operation, acoustic alarm disabled| MAINTENANCE modeactivated
Flash
| Detector error| Detector in initialisation process| SET HOLD mode activated

Button Instruction

Audible alarm

Pre-Alarm Alarm Sensor error
Intermittent sound Bi-tonal sound 3 tones every 2 minutes

Alarm relay

Pre-Alarm Alarm Sensor error

Configuration

In this mode the acoustic alarm can be activated / deactivated or the detector can be returned to factory settings.

To activate it:

  1. Disconnect the power supply,reconnect it and press the “CONFIGURATION” push-button 5 times within 2 minutes;the detector will emit a confirmation beep and the blue indicator will show the status of the acoustic alarm:ON:Acoustic alarm enabled / Flashing:Acoustic alarm disabled.
  2. Press the Mute push-button to enable / disable the acoustic alarm.
  3. Press the “CONFIGURATION”push-button for 5 seconds to save the changes and exit the configuration mode;the detector will make 5 short beeps.

 Optionally,you can return the detector to its factory settings.To do so,press the “CONFIGURATION”push-button 5 times before step 3.

Pre-alarm jumper
Allows for Pre-alarm detection to be enabled / disabled.Before using this option, ensure that regulations allow for two alarm levels.

SET-HOLD mode
Prevents false alarms when charging or cleaning the chambers.While this mode is activated, pre-alarms will not signal and alarms will signal as pre-alarms when faced with all effects (sound, relay activation and signalling).This mode will remain active for a maximum of 5 hours,then will deactivate automatically.

Maintenance mode
Disables gas pre-alarms and alarms for 1 hour for maintenance tasks.While this mode is activated,no gas pre-alarm or alarm will sound

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals