REZNOR VCS Radiant Heaters Installation Guide

June 12, 2024
Reznor

REZNOR VCS Radiant Heaters

REZNOR VCS Radiant Heaters product

Product Information

This product is a propane conversion kit for natural gas-fired radiant heaters. It is designed for use with models VCS, VCT, VPS, and VPT. The kit, labeled as Option DL2, includes various components necessary for converting the heater from natural gas to propane.
Danger:
There is no conversion kit available for unit size 200. Additionally, the following models should not be converted to propane if installed at elevations higher than 5,000 feet (>1,524 meters):

  • Unit size 150 of all models with S40 tube configuration
  • Unit size 170 of models VCS and VPS with S40 tube configuration

This kit is to be installed by a qualified service agency in accordance with these instructions and in compliance with all codes and requirements of authorities having jurisdiction. Improper installation, adjustment, alteration, service, and/or maintenance can cause property damage, injury, or death. In Canada, gas conversion shall be carried out in accordance with the requirements of the Provincial Authorities having jurisdiction and in accordance with the requirements of the CAN/CGA-B149.1 and CAN/CGA-B149.2 installation code. The qualified agency performing this work assumes responsibility for this conversion.
NOTE: There is no conversion kit available for unit size 200. Furthermore, the following models MUST NOT be converted to propane at installation elevations >5,000 feet (>1,524 meters): unit size 150 of all models with S40 tube configuration and unit size 170 of models VCS and VPS with S40 tube configuration.

General Information

  • This kit is intended for natural gas units installed at elevations of 0–10,000 feet (0–3,045 meters). If the unit is already manufactured for propane, the only upgrade for elevation is fan orifice plate replacement.
  • When converting fuels, it is necessary to have the complete heater model. The identifying model number can be found on the heater rating plate. The rating plate identifies only original equipment, so also compare the label on the gas valve with the description listed.
  • Refer to the installation manual provided with the heater for important safety information.
  • Ensure that all components listed in Table 1 are available before beginning installation.

Natural Gas to Propane Conversion Kit (Option DL2) Components

Component Description Unit Size Model
060 080 100 125

Kit PN
1001412| 1001413| 1001414| 1001415| 1001416| 1001417 *| 1001418 **
Component PN (Quantity) ***

Grommet| 12.5 × 9.5 mm| 270412| All
Washer| Retaining, M6| 270459
Flame plate| Propane| 269957| 269958| 269959| 269960
Conversion kit| Gas valve| 270374
Burner orifice plate| Propane| 269948| 269949| 269980| 269951| 269952| 269953
Fan orifice plate| Propane| 269924| 269925| 269929| 269931| 269933| 269937
269925| 269928| 269932| 269932| 269934
269928| 269929| 269933| 269933|

1011096

269929| 269930| 269934| 269934
1011095| 1011096
Gasket| Burner assembly| 270366 (2)
Baffle plate| For vision burners| 270328| —
Baffle plate screw| #8 × 1/2, SST| 270414 (2)
* For use with size 170 model VPS and VCS generation ZZ units—converts burner to size 150 generation BB.
** For use with size 170 model VCT and VPT generation ZZ units and all generation BB units at installation elevations of 0–2,000 feet.
***
Quantity is one (1) unless otherwise indicated.
Component| Description| Unit Size| Model
---|---|---|---
060| 080| 100| 125| 150| 170
Kit PN
1001412| 1001413| 1001414| 1001415| 1001416| 1001417 *| 1001418 **
Component PN (Quantity) ***

Self-tapping screw| #6 × 3/8, BZP| 270450 (4)| —| VPS
Plate| Fan flange| 269911
Gasket| Fan flange plate| 270365
Label| Conversion| 270653 (2)| 270655 (2)| 270657 (2)| 270659 (2)| 270661 (2)| 270661 (2)| 270663 (2)| VCS, VPS
270654 (2)| 270656 (2)| 270658 (2)| 270660 (2)| 270662 (2)| —| 270664 (2)| VCT, VPT
Jet carrier| Propane| —| 270375| All
Gas orifice| Refer to Table 2
* For use with size 170 model VPS and VCS generation ZZ units—converts burner to size 150 generation BB.
** For use with size 170 model VCT and VPT generation ZZ units and all generation BB units at installation elevations of 0–2,000 feet.
***
Quantity is one (1) unless otherwise indicated.

Propane Gas Orifices

Unit Size

060| 080, 100| 125| 150| 170
PN (Orifice Size)
270398 (1.1 mm)| 270399 (1.3 mm)| 270400 (1.5 mm)| 270401 (1.7 mm)| 270401 (1.7 mm) *
270403 (1.9 mm) **
*
For use with size 170 model VPS and VCS generation ZZ units—converts burner to size 150 generation BB.
** For use with size 170 model VCT and VPT generation ZZ units and all generation BB units at installation elevations of 0–2,000 feet.

Product Usage Instructions

Installation

  1. Remove gas and electric supply:

    • Shut OFF gas supply ahead of union at manual shutoff valve outside cabinet.
    • Disconnect electrical power/control connections.
    • Disconnect gas supply at union outside of cabinet using two wrenches.
  2. For models VCS, VCT, and VPT with ducted combustion air:

    • Loosen hose clamp that secures flexible hose to fresh air inlet on side of burner cabinet and remove hose.
  3. Loosen setscrew on burner support casting and remove burner from emitter tube.

  4. Replace burner orifice plate:

    • Remove and save four screws that secure burner assembly.

    • Remove burner support casting and gasket . Discard gasket.

    • Disconnect ignition, flame probe, and ground leads and pressure switch silicone tube .

    • Remove and save three screws that secure existing burner orifice plate to burner tube and remove plate and gasket. Discard gasket.

    • Remove retaining washer that secures impulse stud to burner orifice plate and remove stud.

    • Orient replacement burner orifice plate with impulse stud and replacement retaining washer facing in correct direction and replacement cable grommet fitted to oblong hole in bottom of plate.

    • Secure replacement burner orifice plate to burner tube using existing three screws.

  5. Replace flame plate:

    • Remove and save three screws that secure flame plate and burner head to burner tube.
    • Remove flame plate. DO NOT remove burner head.
    • Remove and discard anti-tip bracket
    • Secure flame plate on top of burner head to burner tube using existing three screws. Ensure that five holes on outer ring are aligned properly.
  6. Relace gas orifice:

    • For unit sizes 060–150:
    • Using wrench, unthread existing gas orifice from jet carrier.
    • Using approved pipe joint compound and wrench, thread replacement gas orifice into jet carrier. DO NOT overtighten.REZNOR VCS Radiant Heaters 9
    • For unit size 170 model VPS:
    • Remove and save two screws from base of jet carrier. Note ground terminal connection.
    • Remove and save four screws that secure rear burner plate to burner housing and remove plate.
    • Using wrench, unthread existing jet carrier/gas orifice from gas valve.
    • Thread replacement gas orifice into replacement jet carrier.
    • Using approved pipe joint compound and wrench, thread replacement jet carrier/gas orifice into gas valve. DO NOT overtighten.
    • Re-install rear burner plate to burner housing and secure plate using existing four screws.
    • Re-install existing two screws in base of jet carrier. Note ground terminal connection.
    • For unit size 170 models VCS, VCT, and VPT:
    • Remove and save two screws from base of jet carrier. Note ground terminal connection.
    • Remove and save four screws that secure base plate and remove plate.
    • Mark and disconnect gas valve wiring connections.
    • Remove four screws that secure gas valve inlet plate to burner housing and remove plate.
    • Remove gas valve rearwards and, using wrench, unthread existing jet carrier/gas orifice from gas valve.
    • Thread replacement gas orifice into replacement jet carrier.
    • Using approved pipe joint compound and wrench, thread replacement jet carrier/gas orifice into gas valve. DO NOT overtighten.
    • Re-install gas valve inlet plate to burner housing and secure plate using existing four screws.
    • Re-install existing two screws in base of jet carrier. Note ground terminal connection.
  7. For unit sizes 060, 080, and 100, install baffle plate:
    NOTE: For model VCS and VCT units, two existing screws in the baffle plate mounting holes need to be removed.

    • Carefully position baffle plate inside combustion chamber.
    • Align baffle plate holes with existing holes in burner cabinet and secure plate using two baffle plate screws.
  8. Replace regulator springs in combination gas valve:

    • Open access door/panel.
    • Remove brass cover screw(s), plastic adjustment screw(s), and existing regulator spring(s) from combination gas valve regulator sleeve.
    • Install replacement regulator spring(s) from gas valve conversion kit into regulator sleeve and thread adjustment screw approximately eight turns into sleeve.
    • Set correct gas pressure in accordance with Table 3 by turning adjustment screw(s) IN (clockwise) to increase pressure or OUT (counterclockwise) to decrease pressure.
    • Re-install cover screw(s) and adhere small round LP label(s) from gas valve conversion kit to top of cover screw(s).
    • Close access door/panel.
    • Adhere warning label from gas valve conversion kit where it can easily be seen on outside of burner cabinet.
      NOTE: A 5-foot (1,524-mm) burner insert (PN 270489) is used in unit sizes 060, 080, and 100. A 3-foot (914-mm) burner insert (PN 1005500) is used in unit size 125. The burner insert is installed in the first emitter tube where it is joined to the second emitter tube.REZNOR VCS Radiant Heaters
14 Gas Manifold Pressure for Propane Units****

Installation Location| Elevation (Feet (Meters))| Model| Burner Setting| Unit Size| 170
---|---|---|---|---|---
060| 080| 100| 125| 150| 170
Gas Manifold Pressure (IN WC)
US| 0–2000 (0–610)| VCS, VPS| —| 5.5| 5.2| 8.0| 7.6| 7.0| 6.1| 7.0
VCT, VPT| Low| 3.5| 2.9| 4.4| 4.6| 3.3| 3.6| —
High| 5.5| 5.2| 8.0| 7.6| 7.0| 6.1
2001–5000 (611–1525)| VCS, VPS| —| 5.5| 5.2| 8.0| 7.6| 7.0| —| 7.0
VCT, VPT| Low| 3.5| 2.9| 4.4| 4.6| 3.3| —
High| 5.5| 5.2| 8.0| 7.6| 7.0
5001–10,000 (1526–3045)| VCS, VPS| —| 5.5| 5.2| 8.0| 7.6| 6.4| —| 6.4
VCT, VPT| Low| 3.5| 2.9| 4.4| 4.6| 3.3| —
High| 5.5| 5.2| 8.0| 7.6| 6.4
Canada| 0–2000 (0–610)| VCS, VPS| —| 5.5| 5.2| 8.0| 7.6| 7.0| 6.1| 7.0
VCT, VPT| Low| 3.5| 2.9| 4.4| 4.6| 3.3| 3.6| —
High| 5.5| 5.2| 8.0| 7.6| 7.0| 6.1
2001–4500 (611–1373)| VCS, VPS| —| 5.4| 5.0| 7.8| 7.4| 6.8| —| 6.8
VCT, VPT| Low| 3.4| 2.8| 4.2| 4.4| 3.1| —
High| 5.4| 5.0| 7.8| 7.4| 6.8
Generation ZZ units.
9. If heater has burner insert(s), remove insert(s).
NOTE: The following units require additional turbulator strip(s) (PN 116019): unit size 100 with S30 tube configuration requires one (1) additional and unit size 170 with S50 tube configuration requires two (2) additional. Furthermore, all turbulator strips MUST BE REMOVED for the following models at installation elevations >5,000 feet (>1,524 meters): unit size 150 of all models with U40 tube configuration and unit size 170 of models VCS and VPS with U40 tube configuration.REZNOR VCS Radiant Heaters
15

  1. Install turbulator strip(s) as required:
  * Interlock turbulator strip sections.![REZNOR VCS Radiant Heaters 16](https://manuals.plus/wp-content/uploads/2023/07/REZNOR-VCS-Radiant-Heaters-16.png)
  * Slide connected sections into emitter tube(s) . Add further strips to form required length.![REZNOR VCS Radiant Heaters 17](https://manuals.plus/wp-content/uploads/2023/07/REZNOR-VCS-Radiant-Heaters-17.png)
  1. Reinstall burner assembly and burner support casting :
  * Run ignition, flame probe, and ground leads and pressure switch silicone tube through replacement gasket and reconnect leads and tube.
  * Position burner support casting with replacement gasket and burner assembly so that wiring leads are not pinched and secure burner support casting to burner cabinet using four screws removed in step 4a.
  * Re-install burner in emitter tube and tighten setscrew on burner support casting.
  1. Replace fan orifice plate (plates are stamped with PN):**
    Installation Location| Elevation (Feet (Meters))| Unit Size| Model
    ---|---|---|---
    VCS, VPS| VCT, VPT
    Heater Tube Configuration (Fan Orifice Plate PN)
    US| 0–2000 (0–610)| 060| S20–40, U20–40 (269924)| S20–40, U20–40 (269924)
    080| S30–40, U20–40 (269925)| S30–40, U40 (269925)
    100| S30–50, U40 (269929)| S30–40, U40 (269929)
    125| S30–60, U40–60 (269931)| S30–50, U40 (269931)
    150| S40–70, U40–60 (269933)| S40–60, U40–60 (269933)
    170 **| S50–80, U60–80 (269933)| —
    170| S50–80, U60–80 (269937)| S50–70, U60 (269937)
    2001–5000 (611–1525)| 060| S20, U20 (269925)| S30–40, U40 (269924)| S20, U20 (269925)| S30–40, U40 (269924)
    080| S30, U20 (269928)| S40, U40 (269925)| S30 (269928)| S40, U40 (269925)
    100| S30 (1011095)| S40–50, U40 (269929)| S30 (1011095)| S40, U40 (269929)
    125| S30–40 (269932)| S50–60, U40–60 (269931)| S30–40 (269932)| S50, U40 (269931)
    150| S40, U40 (269934)| S50–70, U60 (269933)| S40, U40 (269934)| S50–60, U60 (269933)
    170
    | S40, U40 (269934)| S50–70, U60 (269933)| —
    5001–8000 (1526–2440)| 060| S20, U20 (269928)| S30–40, U40 (269925)| S20, U20 (269928)| S30–40, U40 (269925)
    080| S30, U20 (269930)| S40, U40 (269928)| S30 (269930)| S40, U40 (269928)
    100| S30 (269933)| S40–50, U40 (269932)| S30 (269933)| S40, U40 (269932)
    125| S30–40 (269934)| S50–60, U40–60 (269933)| S30–40 (269934)| S50, U40 (269933)
    150| S50–70, U40, U60 (1011096)| S50–60, U40, U60 (1011096)
    170 | S50–70, U40, U60 (1011096)| —
    8001–10,000 (2441–3045)| 060| S20, U20 (269929)| S30–40, U40 (269928)| S20, U20 (269929)| S30–40, U40 (269928)
    080| S30, U20 (1011095)| S40, U40 (269929)| S30 (1011095)| S40, U40 (269929)
    100| S30 (269934)| S40–50, U40 (269933)| S30 (269934)| S40, U40 (269933)
    125| S30–40 (1011096)| S50–60, U40–60 (269934)| S30–40 (1011096)| S50, U40 (269934)
    150| S50–70, U40, U60 (1011096)| S40, U40, U60 (1011096)
    170
    | S50–70, U40, U60 (1011096)| —
    Canada| 0–2000 (0–610)| 060| S20–40, U20–40 (269924)| S20–40, U20–40 (269924)
    080| S30–40, U20–40 (269925)| S30–40, U40 (269925)
    100| S30–50, U40 (269929)| S30–40, U40 (269929)
    125| S30–60, U40–60 (269931)| S30–50, U40 (269931)
    150| S40–70, U40–60 (269933)| S40–60, U40–60 (269933)
    170 | S50–80, U60–80 (269933)| S50–70, U60 (269937)
    170| S60–80, U60–80 (269937| —
    2001–4500 (611–1373)| 060| S20, U20 (269925)| S30–40, U40 (269924)| S20, U20 (269925)| S30–40, U40 (269924)
    080| S30, U20 (269928)| S40, U40 (269925)| S30 (269928)| S40, U40 (269925)
    100| S30 (1011095)| S40–50, U40 (269929)| S30 (1011095)| S40, U40 (269929)
    125| S30–40 (269932)| S50–60, U40–60 (269931)| S30–40 (269932)| S50, U40 (269931)
    150| S40, U40 (269934)| S50–70, U60 (269933)| S40, U40 (269934)| S50–60, U60 (269933)
    170
    | S40, U40 (269934)| S50–70, U60 (269933)| —
    ***** Generation ZZ units.

NOTE: If the tube configuration includes 5-foot tubes, the required fan orifice plate is for the next size downward (e.g., S35 requires an S30 plate, S55 requires an S50 plate, etc.).

  *  **For model VCS, VCT, and VPT units:**
  * Remove and save four screws that secure top burner housing cover and remove cover to expose fan assembly.
  * Remove and save four screws that secure fan assembly and remove fan assembly to access fan.
  *  **For all models:**
  * For unit sizes 060–170, remove and save three nuts from fan studs.  

For unit size 200, remove and save four screws that secure existing fan orifice plate.

  * Remove existing fan orifice plate and install replacement plate. Secure using existing fasteners.
  *  **For model VPS generation ZZ units, replace fan flange plate:**
  * Remove four screws that secure fan outlet and unplug from burner box.
  * Remove and save two screws that secure fan flange plate with fan support bracket to burner housing and remove fan and bracket assembly.
  * Remove and save remaining two screws and remove existing fan flange plate.
  * Install self-adhesive fan flange plate gasket on underside of replacement fan flange plate.
  * Position replacement fan flange plate onto burner housing and secure using existing screws.
  * Position fan with fan support bracket on top of fan flange plate, ensuring that fan outlet is placed OUTSIDE flange, and secure using existing screws.
  * Secure fan outlet to housing using four self-tapping screws from kit.
  * For model VCS, VCT, and VPT units, re-install fan assembly and top burner housing cover using existing fasteners.
  1. Install conversion label:
  * Using permanent marker, fill in data on conversion label  for installation elevation, heat input, and gas manifold pressure.  

  * Adhere label to existing data label on **unit. NOTE:** When a generation ZZ burner is converted to propane, it becomes a generation BB burner. The burner label needs to be modified in permanent ink to indicate this.  

Installation Location| Elevation (Feet (Meters))| Model| Burner Setting| Unit Size
---|---|---|---|---
060| 080| 100| 125| 150| 170| 170
BTUh
US| 0–2000 (0–610)| VCS, VPS| —| 60,000| 80,000| 100,000| 125,000| 150,000| 169,000| 150,000
VCT, VPT| Low| 48,000| 60,000| 75,000| 95,000| 100,000| 125,000| —
High| 60,000| 80,000| 100,000| 123,500| 150,000| 169,000
2001–3000 (611–915)| VCS, VPS| —| 56,400| 75,200| 94,000| 117,500| 141,000| —| 141,000
VCT, VPT| Low| 45,120| 56,400| 70,500| 89,300| 94,000| —
High| 56,400| 75,200| 94,000| 116,090| 141,000
3001–4000 (916–1220)| VCS, VPS| —| 55,200| 73,600| 92,000| 115,000| 138,000| —| 138,000
VCT, VPT| Low| 44,160| 55,200| 69,000| 87,400| 92,000| —
High| 55,200| 73,600| 92,000| 113,620| 138,000
4001–5000 (1221–1525)| VCS, VPS| —| 54,000| 72,000| 90,000| 112,500| 135,000| —| 135,000
VCT, VPT| Low| 43,200| 54,000| 67,500| 85,500| 90,000| —
High| 54,000| 72,000| 90,000| 111,150| 135,000
5001–6000 (1526–1830)| VCS, VPS| —| 52,800| 70,400| 88,000| 110,000| 132,000| —| 132,000
VCT, VPT| Low| 42,240| 52,800| 66,000| 83,600| 88,000| —
High| 52,800| 70,400| 88,000| 108,680| 132,000
6001–7000 (1831–2135)| VCS, VPS| —| 51,600| 68,800| 86,000| 107,500| 129,000| —| 129,000
VCT, VPT| Low| 41,280| 51,600| 64,500| 81,700| 86,000| —
High| 51,600| 68,800| 86,000| 106,210| 129,000
7001–8000 (2136–2440)| VCS, VPS| —| 50,400| 67,200| 84,000| 105,000| 126,000| —| 126,000
VCT, VPT| Low| 40,320| 50,400| 63,000| 79,800| 84,000| —
High| 50,400| 67,200| 84,000| 103,740| 126,000
8001–9000 (2441–2745)| VCS, VPS| —| 49,200| 65,600| 82,000| 102,500| 123,000| —| 123,000
VCT, VPT| Low| 39,360| 49,200| 61,500| 71,250| 82,000| —
High| 49,200| 65,600| 82,000| 96,950| 123,000
9001–10,000 (2746–3045)| VCS, VPS| —| 48,000| 64,000| 80,000| 100,000| 120,000| —| 120,000
VCT, VPT| Low| 38,400| 48,000| 60,000| 69,350| 80,000| —
High| 48,000| 64,000| 80,000| 94,480| 120,000
Canada| 0–2000 (0–610)| VCS, VPS| —| 60,000| 80,000| 100,000| 125,000| 150,000| 169,000| 150,000
VCT, VPT| Low| 48,000| 60,000| 75,000| 95,000| 100,000| 125,000| —
High| 60,000| 80,000| 100,000| 123,500| 150,000| 169,000
2001–4500 (611–1373)| VCS, VPS| —| 54,000| 72,000| 90,000| 112,500| 135,000| —| 135,000
VCT, VPT| Low| 43,200| 54,000| 67,500| 85,500| 90,000| —
High| 54,000| 72,000| 90,000| 112,500| 135,000
Generation ZZ units.
14. For models VCS, VCT, and VPT with ducted combustion air, connect flexible hose to fresh air inlet on side of burner cabinet and secure using hose clamp. 15. Reconnect gas supply at union outside of cabinet and leak test connection using leak detecting solution. If leak is detected, tighten connection. If leak cannot be stopped by tightening connection, replace part(s). 16. Turn ON electric and gas. 17. Check for proper operation.

Specifications and illustrations subject to change without notice or incurring obligations. Latest version of this manual is available at www.reznorhvac.com.
©2023 Nortek Global HVAC LLC, O’Fallon, MO. All rights reserved.
VCS-VCT-VPS-VPT-DL2 (05-23) 1042554-A