Munters Ag-MIS Green CO2 Sensor Instruction Manual
- September 9, 2024
- Munters
Table of Contents
Ag-MIS Green CO2 Sensor
“`html
Specifications:
- Product Name: Green CO2 Sensor
- Model: Ag/MIS/UmGb-2820-09/21
- Revision: 1.3
- Part Number: 116857
Product Information:
The Green CO2 Sensor is a climate controller designed to measure
CO2 levels in an agricultural environment. It works in conjunction
with a controller to regulate ventilation based on user-defined
specifications.
Product Usage Instructions:
Operating Mode:
The CO2 Sensor operates in a Current Loop mode (4 – 20
milliamps). It provides a signal proportional to CO2 levels. Ensure
that J2 is not shorted to maintain proper operation.
Installation:
To install the CO2 Sensor:
-
Mount the sensor in place.
-
Remove the retaining screw from the protective cover on the
female plug. -
Pull out the connector from the protective cover.
-
Thread the cable through the protective cover.
-
Connect each wire to the corresponding port on the top of the
connector.
FAQ:
Q: Can the CO2 Sensor be used indoors?
A: The CO2 Sensor is designed for use in agricultural
environments. It is recommended to use it in such settings for
optimal performance.
Q: What is the power supply requirement for the CO2
Sensor?
A: The unit comes supplied with a 12 VDC supply. Ensure to
provide the appropriate power input for correct functioning.
“`
Manual for use and maintenance
Green CO2 Sensor
Green CO2 Sensor
Climate Controller
Ag/MIS/UmGb-2820-09/21 Rev 1.3 P/N: 116857
CO2 Sensor
Manual for use and maintenance
Rev 1.3, 05/2024 This manual for use and maintenance is an integral part of
the apparatus together with the attached technical documentation. This
document is destined for the user of the apparatus: it may not be reproduced
in whole or in part, committed to computer memory as a file or delivered to
third parties without the prior authorization of the assembler of the system.
Munters reserves the right to effect modifications to the apparatus in
accordance with technical and legal developments.
© Munters AB, 2021
2
Table of Contents
1 INTRODUCTION ……………………………………………………………………………………………………. 4 1.1
Disclaimer…………………………………………………………………………………………………. 4 1.2 Introduction
……………………………………………………………………………………………… 4 1.3 Notes
……………………………………………………………………………………………………….. 4
2 INTRODUCTION ……………………………………………………………………………………………………. 5 2.1 Features
…………………………………………………………………………………………………… 5 2.2 Operating
Mode………………………………………………………………………………………… 6
3 INSTALLATION …………………………………………………………………………………………………….. 7 3.1 Installing the
Sensor …………………………………………………………………………………..7 3.2 Controller
Connection……………………………………………………………………………….10 3.3 Calibrating the
Device………………………………………………………………………………. 12 3.4 Disconnecting the Sensor
…………………………………………………………………………. 14
4 MAINTENANCE AND CARE ………………………………………………………………………………….15 5 SPECIFICATIONS
………………………………………………………………………………………………….15 6 TROUBLESHOOTING
……………………………………………………………………………………………16 7 WARRANTY
…………………………………………………………………………………………………………. 17
© Munters AB, 2021
3
1 Introduction
1.1 Disclaimer
Munters reserves the right to make alterations to specifications, quantities,
dimensions etc. for production or other reasons, subsequent to publication.
The information contained herein has been prepared by qualified experts within
Munters. While we believe the information is accurate and complete, we make no
warranty or representation for any particular purposes. The information is
offered in good faith and with the understanding that any use of the units or
accessories in breach of the directions and warnings in this document is at
the sole discretion and risk of the user.
1.2 Introduction
Congratulations on your excellent choice of purchasing a CO2 Sensor! In order
to realize the full benefit from this product it is important that it is
installed, commissioned and operated correctly. Before installation or using
the sensor, this manual should be studied carefully. It is also recommended
that it is kept safely for future reference. The manual is intended as a
reference for installation, commissioning and dayto-day operation of the
Munters equipment.
1.3 Notes
Date of release: Jan 2018 Munters cannot guarantee to inform users about the
changes or to distribute new manuals to them. All rights reserved. No part of
this manual may be reproduced in any manner whatsoever without the expressed
written permission of Munters. The contents of this manual are subject to
change without notice.
© Munters AB, 2021
4
2 Introduction
The CO2 Sensor measures CO2 levels in an agricultural environment. Working in
conjunction with a controller, the CO2 Sensor sends a signal when the measured
CO2 levels fall outside the user-defined specifications. This signal activates
the controller’s ventilation. Refer to Figure 1.
Figure 1: CO2 Sensor Layout NOTE The unit comes supplied with a 12 VDC supply.
2.1 Features
· Self-contained environment and impact-resistant sealed box · Quick open clasps · Easy installation · Simple to connect and configure · Continuous uninterrupted CO2 sensing · Diagnostic LEDs · Door-mounted sensor
© Munters AB, 2021
5
2.2 Operating Mode
The CO2 Sensor operates in a Current Loop mode (4 – 20 milliamps). In this
mode, the CO2 Sensor provides a signal proportional to CO2 levels. Verify that
J2 is not shorted (refer to Figure 2).
Figure 2: J2 Jumper
© Munters AB, 2021
6
3 Installation
This section details: · Installing the Sensor · Controller Connection ·
Calibrating the Device · Disconnecting the Sensor
3.1 Installing the Sensor
The CO2 Sensor comes with an extension cable that is used to: · Connect the
sensor to a power source · Connect the sensor to the Green Climate Controller
· Detach the unit from the house during cleaning and maintenance procedures
(Disconnecting the Sensor, page 14)
Figure 3: CO2 Sensor Attached to Connector To install the unit: 1. Mount the
sensor in place. 2. On the female plug, remove the retaining screw from the
protective cover (Figure 4).
Figure 4: Protective Cover
© Munters AB, 2021
7
3. Pull out the connector from the protective cover (Figure 5).
Figure 5: Remove the Connector 4. Place the cable through the protective cover
(Figure 6).
Figure 6: Threading the Cable 5. On the top of the connector are numbers
(Figure 7. Each wire must be attached to the corresponding port (Table 1).
Connect the four wires to the connector Figure 8.
Figure 7: Connector Numbers
Table 1: Connecter Port Functions Port Number
Function
1
+12 V
2
-12 V (COM)
3
SIG Out
4
SIG COM
Red Black White Green
Wire Color
NOTE The cable wiring used may have different colors.
© Munters AB, 2021
8
Figure 8: Wired Connector 6. Place the wired connector back into the
protective cover and place the retaining screw in place (Figure 9).
Figure 9: Wired Unit in Protective Cover
© Munters AB, 2021
9
3.2 Controller Connection
Figure 10: RAIC11 CO2 Connector Wiring (example)
Place a jumper on the 4 20 mA on the corresponding jumper selection. In the
above drawing, the input wire is attached to IN1; the jumper would be placed
on INPUT 1 4 20 mA. The Green Climate Controller supplies the VAC current.
Refer to Figure 11.
© Munters AB, 2021
10
Figure 11: Wiring the CO2 Sensor Power Supply
© Munters AB, 2021
11
Figure 12: CO2 Sensor Wiring Schematic (colors may vary)
3.3 Calibrating the Device
Figure 13: Jumpers
The C02 sensor comes calibrated. In normal conditions fresh air should have
approximately 350 – 450 ppm CO2. Calibrate the device if the following
conditions are met:
· The CO2 sensor is exposed to fresh air or a room with open windows · The
sensor reading is above 550
To calibrate the sensor:
1. If connected, disconnect the device from the controller. 2. Place the
sensor on a steady base (in an area with fresh air or in a room with open
windows). 3. Apply 12V DC power. 4. Operate the CO2 sensor for five minutes to
stabilize the device. 5. Using the supplied jumper, short the Background
jumpers for 10 seconds as shown in Figure 14.
© Munters AB, 2021
12
Figure 14: Shorting the Background Jumpers
6. Remove the jumper. 7. Disconnect the power and (re)connect the sensor to
the controller. CAUTION Do not short the Zero jumpers; they are for factory-
calibration only. If shorted, remove the jumper and calibrate again.
NOTE If the device reading is still above 550 when exposed to fresh air,
repeat the process.
© Munters AB, 2021
13
3.4 Disconnecting the Sensor
Before cleaning the poultry/animal house, disconnect the CO2 sensor. To
disconnect the sensor: 1. Dismount the sensor from the wall. 2. Separate the
male and female plugs.
Figure 15: Plugs Separated 3. Place the plug cap on the female cap.
Figure 16: Cap in Place 4. Snap the cap into place.
Figure 17: Cap Snapped into Place
© Munters AB, 2021
14
4 Maintenance and Care
The CO2 Sensor requires little or no maintenance. The following are general
maintenance rules:
· Avoid damaging the CO2 Sensor box. · Avoid contact with water or other
fluids (when you clean the poultry house,
remove the box). · Ensure sensor grill on front box panel is clean and clear
of obstructions.
NOTE Water may damage the sensor; therefore minimize exposure while washing,
or using water for any purpose.
5 Specifications
Output signal
4 20 mAmp
CO2 range
0 5000 ppm
Accuracy
1%
Maximum cable length
300 meters
Minimum wire size
22 AWG
Power supply
12 VDC/350 mA
CAUTION Unit should be powered by Limited Energy Source per IEC 61010-1 or Limited Power Source per IEC 60950-1 or IEC 62368-1
Operating temperature
10 º – 70º C
Environmental Specifications
· Indoor use only · Altitude: -400 m to 2000 m · Relative Humidity: 0 95% · Main supply voltage fluctuation up to 5% · Overvoltage category: OVCII · Pollution degree: PD2 · Ingress Protection: IPXO
© Munters AB, 2021
15
6 Troubleshooting
The field technician diagnostic LEDs are visual diagnostic indicators for the field technician only. They are not end-user serviceable parts or indicators. Table 2 details possible system failure issues.
Table 2: CO2 Sensor System Failure Issues Problem
Solution
The Sensor Fail LED is lit when CO2 sensing element fails. The Min. Fail or
Max. Fail LED is lit: The sensor is out of acceptable range. If the diagnostic
LEDs are lit (D2, R12), indicates that the circuit may be incomplete. Readings
are off the scale, even when fresh air is present.
Readings are lower than expected.
Power LED remains unlit
Replace CO2 sensing element
Replace CO2 sensing element
Check circuitry for breaks
Verify that there is a jumper on the Green Climate RAIC11 card, placed, set
for 4 20 mA (refer to Figure 13). Remove jumper from J2 terminal (refer to
Figure 2). Check if power/COM wiring has been reversed (refer to Table 1).
© Munters AB, 2021
16
7 Warranty
Warranty and technical assistance
Munters products are designed and built to provide reliable and satisfactory
performance but cannot be guaranteed free of faults; although they are
reliable products they can develop unforeseeable defects and the user must
take this into account and arrange adequate emergency or alarm systems if
failure to operate could cause damage to the articles for which the Munters
plant was required: if this is not done, the user is fully responsible for the
damage which they could suffer.
Munters extends this limited warranty to the first purchaser and guarantees
its products to be free from defects originating in manufacture or materials
for one year from the date of delivery, provided that suitable transport,
storage, installation and maintenance terms are complied with. The warranty
does not apply if the products have been repaired without express
authorization from Munters, or repaired in such a way that, in Munters’
judgment, their performance and reliability have been impaired, or incorrectly
installed, or subjected to improper use. The user accepts total responsibility
for incorrect use of the products.
The warranty on products from outside suppliers fitted to the CO2 Sensor, (for
example analog inputs, cables, etc.) is limited to the conditions stated by
the supplier: all claims must be made in writing within eight days of the
discovery of the defect and within 12 months of the delivery of the defective
product. Munters has thirty days from the date of receipt in which to take
action, and has the right to examine the product at the customer’s premises or
at its own plant (carriage cost to be borne by the customer).
Munters at its sole discretion has the option of replacing or repairing, free
of charge, products which it considers defective, and will arrange for their
dispatch back to the customer carriage paid. In the case of faulty parts of
small commercial value which are widely available (such as bolts, etc.) for
urgent dispatch, where the cost of carriage would exceed the value of the
parts, Munters may authorize the customer exclusively to purchase the
replacement parts locally; Munters will reimburse the value of the product at
its cost price.
Munters will not be liable for costs incurred in demounting the defective
part, or the time required to travel to site and the associated travel costs.
No agent, employee or dealer is authorized to give any further guarantees or
to accept any other liability on Munters’ behalf in connection with other
Munters products, except in writing with the signature of one of the Company’s
Managers.
WARNING! In the interests of improving the quality of its products and
services, Munters reserves the right at any time and without prior notice to
alter the specifications in this manual.
The liability of the manufacturer Munters ceases in the event of:
· dismantling the safety devices;
· use of unauthorized materials;
© Munters AB, 2021
17
· inadequate maintenance; · use of non-original spare parts and accessories.
Barring specific contractual terms, the following are directly at the user’s
expense:
· preparing installation sites; · providing an electricity supply (including
the protective equipotential bonding (PE)
conductor, in accordance with CEI EN 60204-1, paragraph 8.2), for correctly
connecting the equipment to the mains electricity supply; · providing
ancillary services appropriate to the requirements of the plant on the basis
of the information supplied with regard to installation; · tools and
consumables required for fitting and installation; · lubricants necessary for
commissioning and maintenance.
It is mandatory to purchase and use only original spare parts or those
recommended by the manufacturer. Dismantling and assembly must be performed by
qualified technicians and according to the manufacturer’s instructions.
The use of non-original spare parts or incorrect assembly exonerates the
manufacturer from all liability.
Requests for technical assistance and spare parts can be made directly to the
nearest Munters office.
Ag/MIS/UmGb-2820-09/21 Rev 1.3
© Munters AB, 2021
18