fri-jado 9172310 Sensor Probe Instructions
- June 12, 2024
- fri-jado
Table of Contents
fri-jado 9172310 Sensor Probe Instructions}
Contents service kit 9172310s:
9172310 1x Pt1000 probe
9294075s 1x Bracket TDR5p
9294069 1x Bracket TDR7p
4288231 1x Screw M5x10
9110072 2x clamp
4287620 2x Selftapping screw (spare)
9293095 1x Seal, sil. @10 x @4
9293096 1x Seal, sil. @12 x @3
9124103 1x This instruction
Applied in
-
TDR5p
TDR5s ac
-
TDR7p
TDR8p
TDR7i(ac)
TDR8i(ac)
TDR7s ac
TDRS sac
TDR gas
-
TRC
No additional parts needed
- BB series
No additional parts needed
- STGi series
No additional parts needed
-
HD series (humidified)
No additional parts needed -
STO
No additional Parts needed
Additional parts needed
92940755 4288231 9110072?2)(), 929309 9293096
92940695, 4288231 9110072(2x), 929309 5203006
Not for TR gas !!
NOTICE –
This manual is prepared for the use of trained STGi series Service Technicians and should not be used by those not properly qualified. If you have attended a training for this product, you may be qualified to perform all the procedures in this manual
This manual is not intended to be all encompassing. If you have not attended a training for this product, you should read, in its entirety, the repair procedure you wish to performto determine if you have the necessary tools, instruments and skills required to perform the procedure. Procedures for which you do not have the necessary tools, instruments and skills should be performed by a trained technician.
Reproduction or other use of this Manual, wit- parts needed hout the express written consent of Fri-Jado, is prohibited.
EXCHANGING THE PT1000 TEMPERATURE PROBE IN A TDR
Not applicable for the TDR gas !!
The mounting bracket for the TDR rotisseries has been improved. Therefore the new Pt1000 probe comes with a new mounting bracket which has to be exchanged with the one in the unit. (if not already done !)
Note that the brackets in the unit can differ from the picture.
-
Remove both screws and pull out the assembly of old bracket and both temperature probes (Pt1000 and hi-limit).
-
Also remove the spacer if applicable.
-
Disconnect the wiring and pull the hi-limit probe from the old bracket. Dispose the old bracket and old probe according local rules. The description below is with the TDR7 bracket as an example.
-
Click both clips into the bracket and push them forward.
-
Put the Pt1000 probe in the hole and push down into the clip.
-
Push the Pt1000 forward and secure it with the screw.
-
Put the hi-limit probe into the hole and push down into the clip.
-
Push the probe back untill the upstanding side of the bracket.
-
Slide seal silicon @10 x @4 over the Pt1000 probe and position it against the bracket.
-
Slide seal silicon @12 x @3 over the hi-limit probe and position it against the bracket.
-
Gently push the probes with the seals into the sidewall and mount the bracket.
-
Bend the capillar from the hi-limit probe underneath the bracket as shown.