IDEAL 32 Red 2-Port Push-In Wire Connectors Instruction Manual

June 12, 2024
IDEAL

32 Red 2-Port Push-In Wire Connectors
Instruction Manual

Installation Instructions – Push-In Wire Connectors

Models 32, 33, 34, 87, 88 & 90

  • Do not exceed the rating of these connectors.
  • Turn OFF power before removing or installing connectors.
  • Wiring must comply with all applicable electrical regulations.
  • COPPER TO COPPER ONLY. Do not use on aluminium wire.
  • Incorrect use of these connectors can cause electrical fires, personal injury or death.
  • These connectors are suitable for solid and semi-rigid (<7 strands) conductors. They are not suitable or rated for use with flexible cable with >7 strands.
  • Strip wires back 13mm.
  • Grip wire firmly and push conductor into open port.
  • Use only one conductor per port.
  • Connectors are reusable on solid wires of the same wire gauge or larger. If reusing connectors, cut and re-strip conductors.
  • In order to remove a wire, pull and twist the wire back and forth.
  • DO NOT RE-USE connector on stranded wire.

IDEAL 32 Red 2-Port Push-In Wire Connectors - fig 1

Specifications

| Model 32 Red
2-Port| Model 33 Orange
3-Port| Model 34 Yellow
4-Port| Model 87 Grey
5-Port| Model 88 Blue
6-Port| Model 90 Black
8-Port
---|---|---|---|---|---|---
Rating| 32 Amp / 450V / 105°C maximum| 24 Amp / 450V / 105°C maximum
Depth| 19.81 mm| 18.52 mm| 18.52 mm| 18.21 mm
Width| 13.21 mm I| 17.53 mm| I 20.83 mm| 23.03 mm| 15.32 mm| 35.03 mm
Height| 9.65 mm| 9.02 mm| 15.42 mm| 9.02 mm
Wire
Combination
Range| Solid wire| 0.75mm2 to 4.0mm2| 0.75mm2 to 4.0mm2
Stranded wire*| 1.5mm2 to 2.5mm2| 1.5mm2 to 2.5mm2

  • Stranded wire is limited to ≤ 7 strand