PHILIPS TT150, TT280 TC TT Downlight Emergency Lighting Instruction Manual

October 30, 2023
Philips

TT150, TT280 TC TT Downlight Emergency Lighting

Product Information

  • Product Name: TC TT Downlight Emergency Lighting
  • Model Numbers: TT150, TT155, TT160, TT165, TT170, TT175, TT180, TT185, TT190, TT195, TT200, TT205, TT210, TT215, TT220, TT225, TT230, TT235, TT240, TT245, TT250, TT255, TT260, TT265, TT270, and TT280
  • Indoor Use Only
  • Power Supply: 220V 50Hz or 240V 60Hz
  • Optional Polycarbonate Cover (PCC) Available
  • Optional Connector GST18i3, 3 pole, male, mains cable with cable length of 0.5m
  • Optional Connector BST14i2, 2 pole, male
  • IP20 Rated
  • GLOW Functionality
  • Dimensions in mm: A and B vary by model number
  • Battery: 288
  • Driver: PSD-E or PSU-E

Product Usage Instructions

  1. Ensure that the luminaire is used only indoors and is not covered with thermal insulation matting or similar material.
  2. Connect the luminaire to a power supply of either 220V 50Hz or 240V 60Hz
  3. Optional: Install the polycarbonate cover (PCC) or connector GST18i3 or BST14i2 as needed.
  4. If available, activate the GLOW functionality.
  5. Place the luminaire in the desired location according to the dimensions specified in the user manual.
  6. Connect the battery and driver according to the instructions provided in the user manual.
  7. Optional: If using a DALI system, connect the DALI system LED driver using the provided wiring diagram.
  8. Turn on the luminaire using the switch provided.
  9. In case of emergency, the luminaire will automatically switch to emergency operation mode with a specified emergency flux output. Refer to the user manual for emergency operation mode specifications.

BOX CONTENT

PHILIPS-TT150,-TT280-TC-TT-Downlight-Emergency-Lighting-
fig-2

SPECIFICATION

PHILIPS-TT150,-TT280-TC-TT-Downlight-Emergency-Lighting-
fig-3
PHILIPS-TT150,-TT280-TC-TT-Downlight-Emergency-Lighting-
fig-4

SAFETY INSTRUCTION

PHILIPS-TT150,-TT280-TC-TT-Downlight-Emergency-Lighting-
fig-5

INSTALLATION INSTRUCTION

PHILIPS-TT150,-TT280-TC-TT-Downlight-Emergency-Lighting-
fig-6 PHILIPS-TT150,-TT280-TC-TT-
Downlight-Emergency-Lighting-fig-7 PHILIPS-TT150,-TT280-TC-TT-Downlight-Emergency-Lighting-
fig-8 PHILIPS-TT150,-TT280-TC-TT-
Downlight-Emergency-Lighting-fig-9 PHILIPS-TT150,-TT280-TC-TT-Downlight-Emergency-Lighting-
fig-10 PHILIPS-TT150,-TT280-TC-TT-
Downlight-Emergency-Lighting-fig-11 PHILIPS-TT150,-TT280-TC-TT-Downlight-Emergency-
Lighting-fig-12 PHILIPS-
TT150,-TT280-TC-TT-Downlight-Emergency-Lighting-fig-13 PHILIPS-TT150,-TT280-TC-TT-Downlight-Emergency-
Lighting-fig-14

Light output in emergency operation mode BLF:

PHILIPS-TT150,-TT280-TC-TT-Downlight-Emergency-Lighting-
fig-15

Inrush current

PHILIPS-TT150,-TT280-TC-TT-Downlight-Emergency-Lighting-
fig-16

Service: (Driver/battery replacement)

  • The battery should be replaced when it no longer meets the rated duration of operation after the corresponding recharge period. The batteries have a life time expectancy of 6 years.
  • Light source (LED) is not replaceable.
    1.  Disconnect the old battery
    2. Reconnect the new battery

LiFePO4 batteries will be charged before shipment and need to be used before the date indicated on the battery packing due to self-discharging when stored at tstorage ≤ 30°C.
These batteries will be charged by the TrustSight driver per the CC-CV method.

  • Battery: LFP 3000 mAh (2S2P)
  • Inrush current (Ipeak): 5 A
  • Ipeak (half peak time): 110 µs
  •  Battery storage temp:
  •  at -20 – 25 C: max 12 months

Luminaire classificatioin:

  • X: self-contained
  • 1: maintained
  • A: Including test device
  • E: non replaceable lamp/battery
  • 180: duration of emergency mode [min]

Test button:

  • An optional test switch can be connected to the TrustSight emergency driver.
  • This switch can be connected in parallel to the indicator LED and be used in the following ways:
    • Press 0 < time < 10s to initiate functional test as long as switchis pressed.
    • Press > 10s will complete the FT when the battery is not fully charged.
    • Press > 10s when battery is fully charged: a DT will be performed (indicator stays green).
  • When the TrustSight is in Emergency mode there is a possibility to disconnect the battery by pressing the test switch for 3 seconds.
  • This is intended to be able to switch o the emergency system after a light up test in Luminaire factory.

To assure the lighting quality of this unique LED lighting concept there are only a few instructions regarding the maintenance of this
LED luminaire:

  • Do not touch electronic components! Electronic components maybe under high voltage.
  • Do not stare into LED light beam.
  • The luminaire shall be installed by a qualied electrician and wired in accordance with the latest IEE electrical regulations or the national requirements.
  • The batteries have a life time expectancy of 6 years.
  •  Only to be installed outside arms reach as recessed ceiling luminaire.

Charging

After rst installation (and after each emergency mode operation), the batteries need to be charged for at least 24 hours to become suciently charged again. If the battery is not completely discharged the required charge time is shorter accordingly. The status of the battery is given by the indicator LED.

Periodic testing

Periodic tests of emergency lighting luminaires must be performed according to EN50172 clause 7.2.3 and 7.2.4. Switch on in the emergency mode each month by simulation of a failure of the supply to the normal lighting for a period sucient to ensure that each lamp is illuminated. Twice per year, each luminaire shall be tested for its full rated duration (at least 3hrs).

Self-Test

  • The TrustSight Pro version is equipped with a self-test functionality according IEC62034. 28 days after power-up the driver will perform a functional test of 30 seconds. Every 6th test (after half a year) will be a duration test. This test will run until the battery is fully discharged and the driver will verify if the capacity of the battery is sucient to provide 3hrs emergency time.
  • This will result in 2 full duration tests every year. A duration test will only be performed if the battery is sucient charged. In case of a failure, an error will be indicated by the LED indicator.
  • The TrustSight DALI version is equipped with a self-test functionality according IEC62034. Automatic tests will be preformed according the duration test (DT) and functional test (FT) programmable interval times. The DT Interval Time can be set at “0”, disabling the duration tests. This means that there will be no DT initiated by the driver and the DT must be initiated by ATS (lighting management system). The same holds for the FT interval time. Via DALI interface the FT and DT can be initiated with DALI commands.
  • In DALI standard operating mode the DT will be performed as long as the rated duration time (default 3 hour for TrustSight).
  • When via OEM specic mode a DT is initiated also when a self-test DT is performed the test will take until the battery is fully empty.
  • Full discharges are recommend for battery maintenance.

Conditions for Self-test

For both, DT and FT the TrustSight, permanent mains must be available and the battery must be charging or fully charged. A DT will only be performed when the battery is fully charged. A FT can be performed when the battery is partially charged. When scheduling a test (functional or duration test) the operation of the AC-driver is also checked. When the AC-driver is active (so normal lighting turned on), the test will be postponed for a maximum of 3 days. When the AC-driver is o for at least 2 hours the test will be started.

Manual Test

The TrustSight basic version must be tested manually according regulations. This can be done by disconnecting the permanent mains and observing the performance of the system. It is also possible to initiate a DT of FT with the test switch function.

LED indicator status

LED indicator (colour/flashing) Error condition Cause Solution
Green/no   System OK, battery fully charged
No indication   Mains off, EM mode, Rest mode, test in progress
Green/slow   System OK, battery is charging
Green/fast   System OK, recently tested (x 5 days, Australia mode only
Red/no Battery voltage too high or too low No battery connected Connect a

battery
 |  | Wrong or bad battery connected| Replace battery
Red/fast| Output voltage too low or too high| Wrong LED load connected| Connect a right load and perform funtional test
 | No load connected or output shorted| Wrong load connected| Connect a right load and perform funtional test
Red/slow| Failed test due to battery| Battery end of life| Replace battery and perform a duration test
 |  | Charger failure| Replace driver
Red-green/fast|  | DALI identify device|

Disconnect before servicing

  • Luminaire has basic insulation between Low Voltage supply and control conductors.
  • The control gear and/or the external flexible cable contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person. The light source contained in this luminaire is not replaceable, in case of damage replace the luminaire.
  • Storage, installation, use, operation and maintenance of the products needs to be performed exactly according the instructions in this manual and/or other instructions as may be provided by us to guarantee safe use of the product over its entire lifetime. Failure to adhere to these instructions will invalidate your entitlement to warranty. Bolts with indication of torque strength on the drawing need to be tightened using a calibrated torque wrench. Pre-assembled bolts need to be retightened again to the required torque specification to assure maximum strength over lifetime.
  • This product contains a light source of energy efficiency class: see table or label.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals