Altronix AL642ULADA NAC Power Extender Installation Guide
- June 4, 2024
- Altronix
Table of Contents
- Altronix AL642ULADA NAC Power Extender
- Overview
- Specifications
- Installation Instructions
- Sync Mode Selection
- Terminal Identification
- LED Diagnostics
- Battery Calculation Worksheet
- Hookup Diagram
- Maintenance
- Appendix
- Enclosure Dimensions
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Altronix AL642ULADA NAC Power Extender
Overview
Altronix AL642ULADA is an extremely cost-effective 6.5A remote power supply/battery charger. It may be connected to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support system accessories. The unit delivers electronically regulated and filtered 24-volt power to Class B or Class A NAC loop circuits. The 6.5A max. alarm current can be divided between the four (4) outputs for powering NAC devices. Each output is rated at 2.5A max., and can be independently programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may be programmed for Input to Output Follower Mode (output will follow input. i.e. March Time Input, March Time Output). In non-alarm conditions, independent loop supervision for Class A and/or Class B FACP NAC circuits is provided. In the event of loop trouble, the FACP will be notified via the steered input (Input 1 or Input 2). In addition, there are common trouble output terminals [NC, C, NO] that are used to indicate general loop/system trouble. A common trouble input is provided for optional [NC] (normally closed) devices to report trouble to the FACP. Two (2) FACP signaling outputs can be employed and directed to control supervision and power delivery to any combination of the four (4) outputs.
Specifications
Agency Listings:
- UL Listed Control Units and Accessories for Fire Systems (UL 864).
- MEA – NYC Department of Buildings Approved.
- CSFM – California State Fire Marshal Approved.
- FM – Factory Mutual Approved.
- NFPA 72 Compliant.
Input:
- Power input 120VAC, 60Hz, 4A.
- Two (2) Class A or two (2) Class B FACP inputs.
- Two (2) NC dry contact trigger inputs.
- Input Ratings:
INP1 and INP2: 8-30VDC 6.5mA max from FACP. 12V 6.5mA, 24V 6.5mA from FACP.
Output:
- Power-limited outputs.
- 24VDC voltage-regulated power-limited outputs.
- 6.5A max total alarm current.
- 2.5A max current per output.
- Two auxiliary outputs rated at 1A each (1A continuous, 1A AC disconnect).
- Programmable supervised indicating circuit outputs: Four (4) Class B or Four (4) Class A or Two (2) Class A and Two (2) Class B (see 42 Application Guide).
- Thermal and short circuit protection with auto reset.
Battery Backup:
- Charging voltage is 26.2-26.4VDC.
- Built-in charger for sealed lead acid or gel type batteries.
- Automatic switchover to stand-by battery when AC fails.
- Zero voltage drop when switching over to battery backup.
Visual Indicators:
- Input and output status LED indicators.
Supervision:
- AC fail supervision (form “C” contact, 1A/28VDC). Factory set for 30 seconds with optional 2.5 to 3 hour delay setting (field selectable).
- Instant local AC trouble reporting relay (form “C” contact, 1A / 28VDC).
- Battery presence and low battery supervision (form “C” contact, 1A / 28VDC).
Special Features:
-
2-wire horn/strobe Sync mode allows audible notification appliances (horns) and visual notification appliances (strobes) to be silenced/deactivated at the same time.
-
Sync protocols include Potter/Amseco, Gentex®, System Sensor®, and CooperWheelock®.
-
Temporal Code 3, Steady Mode, Input to Output Follower Mode (maintains synchronization of notification appliances circuit).
-
Compatible with 24VDC fire panels.
-
Output loop supervision directed to Input 1 or Input 2.
-
Signal Circuit Trouble Memory – facilitates quick identification of an intermittent/fault (short circuit, open or ground) that has previously occurred on one or more signaling circuit outputs.
LEDs indicate/identify which output the fault has occurred. -
Common trouble input and output for external trouble signals tie-in.
-
Ground fault detection.
-
Unit includes power supply, logic board, enclosure, cam lock, and battery leads.
Enclosure Dimensions (approx. H x W x D):
- 18” x 14.5” x 4.625” (457mm x 368mm x 118mm).
WARNING:
To reduce the risk of fire or electric shock, do not expose the unit to rain
or moisture. This installation should be made by qualified service personnel
and should conform to all local codes.
Power Supply Specifications
AC Input: | 120VAC, 60Hz, 4A. |
---|
Output:
| Four (4) regulated supervised NAC output circuits, 24VDC, 2.5A maximum
current. One (1) aux. special application 24VDC power output circuit 1A, non-
supervised total output current must not exceed current 6.5A in Alarm
Condition.
Battery| Use two (2) 12VDC / 7AH, two (2) 12VDC / 12AH or two (2) 12VDC / 40AH
batteries connected in series.
Stand-by/Alarm Current Consumption:| 90mA/175mA
EOL Resistor (end of line):| 2.2K (2200 Ohm), Altronix Model # AL-EOL22
(included).
Ground fault maximum test impedance:| 1000 Ohm.
Stand-by Specifications
Stand-by Batteries| Stand-by Time Total (A/Minutes)| Alarm Output Current|
Aux. Output
---|---|---|---
24VDC/7AH| 24 Hours| 6.5A/5 minutes| –
24VDC/12AH (use two 12VDC batteries in series)| 24 Hours| 6.5A/5 minutes| 50mA
24VDC/40AH| 24 Hours| 6.5A/5 minutes| 1A
Note: Unit is equipped with two (2) 1A max. auxiliary outputs: “AUX1” will automatically disconnect when AC is lost. “AUX2” will remain battery backed up during a power outage. For loads connected to “AUX2” please, refer to battery “Stand-by Specifications” above for ratings. When loads are connected to the “AUX1” and or “AUX2” outputs during alarm conditions, the remaining outputs may not exceed 6.5A total alarm current (example: AUX1 = 1A, AUX2 = 1A, outputs up to 6.5A).
Installation Instructions
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction.
PRODUCT IS INTENDED FOR INDOOR DRY USE ONLY.
Carefully review:
Application Guide for AL642ULADA, AL842ULADA, AL1042ULADA
- Power Supply Specifications (pg. 4)
- Stand-by Specifications (pg. 4)
- Output Programming Selection Table (pg. 5)
- Sync Mode Selection Table (pg. 6)
- Terminal Identification Table (pgs. 7-8)
- LED Status Indication Table (pg. 8)
-
Mount the unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pg. 16). Secure enclosure to earth ground (Fig. 1, pg. 4). Small terminal block wire gauges range from 16 AWG to 24 AWG, all others range from 14 AWG to 24 AWG. -
Connect the line (L) and neutral (N) terminals to a separate unswitched AC circuit (120VAC, 60Hz) dedicated to the Fire Alarm System.
-
Measure output voltage before connecting devices.This helps avoid potential damage.
-
Connect battery to the terminals marked [+ BAT –] on the Power Supply Board (battery leads included). Use two (2) 12VDC batteries connected in series.
-
Set output selection switches marked [OUT1] through [OUT4] to follow corresponding Input [IN1] and [IN2] and desired output signal type (Output Programming Selection Table, pg. 5).
-
Connect FACP output to the desired AL842LGK logic board inputs, and notification appliances to the desired AL842LGK logic board outputs (see 42 Application Guide).
Note: The 2-wire horn/strobe sync mode will only synchronize horns, horns/strobes, and strobes with synchronization capability. -
WARNING: Emergency control or nonfire equipment cannot be connected on the same circuitry as fire alarm equipment.
Output Programming Selection Table:
Outputs must be programmed independently (OUT1 – OUT4)
Function | Switch Positions | Descriptions |
---|---|---|
ON | OFF | |
Input to Output Follower Mode | 1 | 2, 3 |
the corresponding input (i.e. FACP Sync module – maintains synchronization of
notification appliance circuit).
Temporal Code 3 Mode| 3| 1, 2| Enables Temporal Code 3 signal generation
output. This mode will accept a steady or a pulsing input.
Steady Mode| | 1, 2, 3| A steady output signal will be generated.
This mode will accept steady or pulsing input.
For the above modes DIP Switch 4 determines which Input controls the corresponding output: Switch 4 in the ON position causes output(s) to be controlled by Input 1. Switch 4 in the OFF position causes output(s) to be controlled by Input 2.
Note:
It is required to control visual notification appliances (strobes) via Input 1
(IN1) and audible notification appliances (horns) via Input 2 (IN2). This
allows audible notification appliances (horns) and visual notification
appliances (strobes) to be silenced/ deactivated at same time.
The FACP must be capable of a visual annunciation to the silencing status of the output or zone(s) to which the AL642ULADA (NAC Power Extender) is connected.
AL800LGK9E Board
Output DIP Switches
Sync Mode Selection
Function | Switch Positions | Descriptions |
---|---|---|
ON | OFF |
Amseco Sync Mode*
| ****
1, 3,
4
| ****
2
| This mode is designed to work with the Amseco series of horns, strobes, and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the flash timing of the strobe, allowing audible notification appliances (horns) and visual notification appliances (strobes) to be silenced/ deactivated at the same time.
Gentex® Sync Mode* Gentex is a registered trademark
of Gentex Corporation.
| ****
1, 2,
3, 4
| | This mode is designed to work with the Gentex® series of horns, strobes,
and horn/strobes to provide a means of synchronizing the Temporal-coded horns,
synchronizing the flash timing of the strobe, allowing audible notification
appliances (horns) and visual notification appliances (strobes) to be
silenced/ deactivated at the same time.
System Sensor® Sync Mode* System Sensor is a
registered trademark of Honeywell.
| ****
1, 2, 4
| ****
3
| This mode is designed to work with the System Sensor® series of horns,
strobes, and horn/strobes to provide a means of synchroniz- ing the Temporal-
coded horns, synchronizing the one-second flash timing of the strobe, allowing
audible notification appliances (horns) and visual notification appliances
(strobes) to be silenced/ deacti- vated at the same time.
CooperWheelock® Sync Mode* CooperWheelock is a registered trademark of Cooper
Wheelock.| ****
2, 3, 4
| ****
1
| This mode is designed to work with the CooperWheelock® series of horns, strobes, and horn/strobes to provide a means of synchro- nizing the Temporal- coded horns, synchronizing the one-second flash timing of the strobe, allowing audible notification appliances (horns) and visual notification appliances (strobes) to be silenced/ deactivated at the same time.
Note:
The AL642ULADA will only synchronize horns, horn/strobes, and strobes that
contain synchronization capability. The same synchronization mode must be
selected for all outputs.
Amount of Notification Appliances per NAC:
Amseco | 27 per NAC* |
---|---|
Gentex® | 32 per NAC* |
System Sensor® | 32 per NAC* |
--- | --- |
CooperWheelock® | 32 per NAC* |
Not to exceed a maximum of 2.5A per NAC.
Terminal Identification
AL842LGK Logic Board
Terminal Legend | Function/Description |
---|
– IN1 +
– IN2 +
(Supervised)
| These terminals connect to the 24VDC FACP notification appliance circuit outputs (Class A or Class B). Input trigger voltage is 8-33VDC @ 6.5mA min. Terminal polarity is shown in alarm condition. During an alarm condition these inputs will cause the selected outputs chosen to drive notification appliances. The designated outputs are set by output switches [OUT1 through OUT4] (Output Programming Selection Table, pg. 5). A trouble condition on an output loop will cause the corresponding input to trip the FACP by opening the FACP loop. An alarm condition will always override trouble to drive notification appliances. Rated 12V 6.5mA, 24V 6.5mA.
– RET1 +
– RET2 +
(Supervised)
| For Class A, hookups these terminal pairs return to FACP NAC1 and/or NAC2.
For Class B hookups the FACP EOL resistor from the NAC1 and/or NAC2 outputs are ter- minated at these terminals. Optionally, other notification appliances or additional signaling circuit power supplies may be connected to these terminals. If this option is chosen, the EOL resistor must be terminated at the last device.
NC “DRY1” C NC “DRY2” C
(Dry input trigger)
| An open across these inputs, will cause the selected outputs chosen to drive
notification appliances. The designated outputs are set by output switches
[OUT1 through OUT4] (Output Programming Selection Table, pg. 5). Note these
inputs are unidirectional and will not report a trouble condition to the FACP.
– OUT1 +
– OUT2 +
– OUT3 +
– OUT4 +
(Supervised)
| Notification appliances are connected to these regulated outputs (see
Application Guide pg. 2-4). Each power-limited output will supply 2.5A. Total
supply current is 8A (see note below). Outputs are controlled by designated
Input 1 [IN1] or Input 2 [IN2] (Output Programming Selection Table, pg. 5).
Maximum line loss or voltage drop (tested with 2.5V).
– Loop 1 +
– Loop 2 +
– Loop 3 +
– Loop 4 +
| ****
Used for Class A hook-ups to terminate loops originating on [OUT1], [OUT2], [OUT3], and [OUT4] respectively.
C “FAULT” NC
(Common trouble input)
| An open circuit across this pair of terminals will cause [INP1 and INP2] LEDs to simultaneously signal a trouble condition back to the FACP.
Typically used to report AC or BAT Fail. (Fig. 2a, pg. 10).
NC, C, NO
(Common trouble output)
| These are dry contact trouble outputs that report any general loop/system
trouble conditions. (Typically used to trigger a digital communicator or other
reporting devices). Form “C” contact 1A / 28VDC 0.35 Power Factor (Fig. 2, pg.
10).
– AUX1 +| This separate 1A max. auxiliary Special Application Power output
circuit is disconnected from load during AC power failure. See attached list
of devices (Appendix A, pgs. 12-14).
– AUX2 +
| This separate auxiliary special application output supplies up to 1A during
stand-by and alarm condition. Since this output is not disconnected from its
load during AC power failure use the (Battery Calculation Worksheet, pg. 9) to
determine battery size and/or allowable stand-by and alarm current.
+ DC –| 24VDC from power supply.
Note:
Unit is equipped with two (2) 1A max. auxiliary outputs: “AUX1” will
automatically disconnect when AC is lost. “AUX2” will remain battery backed up
during a power outage. For loads connected to “AUX2” please, refer to battery
“Stand-by Specifications” pg. 4 for ratings. When loads are connected to the
“AUX1” and or “AUX2” outputs during alarm conditions, the remaining outputs
may not exceed 6.5A total alarm current. Example: AUX1 = 1A, AUX2 = 1A,
outputs up to 6.5A.
Terminal Identification Table:
AL600ADA Power Supply Board
Terminal Legend | Function/Description |
---|---|
L, G, N | Connect 120VAC to these terminals: L to hot, N to neutral. |
– DC + | 24VDC @ 6.5A in alarm non power-limited output. |
AC FAIL NO, C, NC | Form “C” dry contacts used to instantaneously signal the |
loss AC to local annunciation devices, with AC present terminals marked NO and
C are open, NC and C are closed. When loss of AC occurs terminals marked NO
and C are closed, NC and C are open.
AC LOCAL NC, NO, C| Form “C” dry contacts used to instantaneously signal the
loss AC to local annunciation devices, with AC present terminals marked NO and
C are open, NC and C are closed. When loss of AC occurs terminals marked NO
and C are closed, NC and C are open.
BAT FAIL NO, C, NC| Form “C” dry contacts used to signal low battery voltage
or loss of battery voltage.
Under normal conditions terminals marked NO and C are open, NC and C are closed. During a trouble condition terminals marked NO and C are closed, and NC and C are open (Fig. 2, pg. 10).
+ BAT –| Stand-by battery input (leads provided) (Fig. 2, pg. 10).
Power Board Parameter Specifications:
-
AC Fail condition will report approximately 30 seconds after loss of AC. To delay report for 2.5 to 3 hours cut jumper AC DELAY on the Power Supply Board (AC trouble output delay option).
If this mode is selected the Power Supply Board must be reset by removing all power to it for 30 seconds. -
Low battery condition will report at approximately 21VDC.
-
Battery presence detection will report within 180 seconds after the battery remains undetected (missing or removed). A restored battery will report within 30 seconds.
LED Diagnostics
AL600ADA – Power Supply Board
Red (DC) | Green (AC) | Power Supply Status |
---|---|---|
ON | ON | Normal operating condition. |
ON | OFF | Loss of AC. Stand-by battery is supplying power. |
OFF | ON | No DC output. |
OFF | OFF | Loss of AC. Discharged or no stand-by battery. No DC output. |
AL842LGK – Logic Board
LED | OFF | ON | BLINK (LONG)* | BLINK (SHORT)** |
---|---|---|---|---|
ON | Normal | Alarm Condition | Trouble Condition | Trouble Condition Memory |
ON | Normal | Alarm Condition | Trouble Condition | Trouble Condition Memory |
OFF | Normal | Alarm Condition | Trouble Condition | Trouble Condition Memory |
OFF | Normal | Alarm Condition | Trouble Condition | Trouble Condition Memory |
Input 1 | Normal | Alarm Condition | Trouble Condition | – |
Input 2 | Normal | Alarm Condition | Trouble Condition | – |
Fault | Normal | Alarm Condition | – | – |
- Indicates existing trouble condition. When a trouble condition (open, short or ground) occurs on a specific output, the corresponding red output LED [OUT1-OUT4] will blink. The corresponding green input LED will blink as well.
- Indicates trouble condition memory. When a trouble condition restores, the units red output LEDs [OUT1] -[OUT4] will blink with a shorter and distinctly different duration. The green input LEDs will be off (normal condition). To reset the memory depress the reset button located on the AL842LGK logic board (Fig. 2b, pg. 10). The LED(s) will extinguish.
Note: When indicating circuits have restored, trouble memory reset is not required for normal operation.
Battery Calculation Worksheet
Device | Number of Devices | Current per Device | Stand-by Current | Alarm Current |
---|---|---|---|---|
For each device use this formula: | This column x This column = Equals | Current |
per number of devices.
AL642ULADA
(Current draw from battery)
| 1| Stand-by:| 90mA| 90mA|
Alarm:| 175mA| | 175mA
A| AL642 Current| 90mA| 175mA
Auxiliary Devices| | Refer to device manual for current ratings.
| | Alarm/Stand-by| mA| mA| mA
| | Alarm/Stand-by| mA| mA| mA
| | Alarm/Stand-by| mA| mA| mA
B| Auxiliary Devices Current (must not exceed 1A)
| | Refer to device manual for current ratings.
| | Alarm:| mA| 0mA| mA
| | Alarm:| mA| 0mA| mA
| | Alarm:| mA| 0mA| mA
| | Alarm:| mA| 0mA| mA
C| Notification Appliances Current must not exceed 6.5A (6500mA) 0mA| | mA
D| Total alarm current| mA| mA
E| Total current ratings converted to amperes (line D x .001)| A| A
F| Number of standby hours (24 for NFPA 72, Chapter 1, 1-5.2.5).| H|
G| Multiply lines E and F. Total stand-by
AH| AH|
H| Alarm sounding period in hours.
(For example, 5 minutes = 0.0833 hours.)
| | H
I| Multiply lines E and H. Total alarm
AH| | AH
J| Add lines G and I. Total stand-by and alarm
AH| AH|
K
| Multiply line J by 1.30.
(30% extra insurance to meet desired performance) Total ampere – hours required
| ****
AH
|
Units are capable of recharging 40AH battery max. If total ampere – hour required exceeds 40AH, decrease AUX current to provide enough stand-by time for the application.
Hookup Diagram
Optional Hookups:
-
Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input [C “FAULT” NC] to report back to the FACP via Input 1 and Input 2. The common trouble input may also be used for other optional supervisory monitoring. (see Power Board Parameter for use of AC Delay, pg. 8) To report AC and Battery Trouble connect the battery and AC Fail relay output shown in Fig. 2a to the common trouble input.
-
Dry contact input (C “DRY1” NC) (C “DRY2” NC) can be used to alarm output from an addressable module (these inputs are uni-direction and cannot report back to the trigger module).
Connection to triggering devices must be made within 20ft of distance and using conduit for wiring. -
Auxiliary output [– AUX +] 24VDC at 1A max.
-
AC Local [NC, NO, C] should connect to the host control panel for local annunciation of the trouble condition.
Note:
If common trouble input, terminals marked [C “FAULT” NC] are not used, these
terminals must be shorted (connect jumper) to remain inactive. For optional
hookups see Fig. 2a.
Maintenance
Unit should be tested at least once a year for the proper operation as follows:
- Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level (26.2-26.4VDC recommended range).
- Battery Test: Under normal load conditions check that the battery is fully charged. Check specified voltage both at battery terminal and at the board terminals marked [+ BAT –] to ensure that there is no break in the battery connection wires.
- Fuses: Check input fuse on the power supply board, and replace if necessary. Input fuse rating is 5A @ 250V.
- Note: Maximum charging current is 650mA.
- Note: Expected battery life is 5 years; however, it is recommended to change batteries in 4 years or less if needed.
Appendix
Appendix A:
Compatible UL/cUL Listed Devices for Synchronization A-1 Strobes, Horns,
and Horn/Strobes Table A-1 below lists Strobes, Horns, and Horn/Strobes
compatible with AL642ULADA NAC outputs.
System Sensor:
CHSR – UL | P4R-SP – UL | PC4RH-P – UL | SPSCW – UL | SPSWK-CLR-ALERT-UL |
---|---|---|---|---|
CHSW – UL | P4RH – UL | PC4RH-SP – UL | SPSCW-CLR-ALERT – UL | SPSWK-P – UL |
HR/HRK/HW – UL | P4RH-P – UL | PC4W – UL | SPSCW-P – UL | SPSWK-R – UL |
MHR – UL | P4RH-SP – UL | PC4W-P – UL | SPSCWH – UL | SPSWV – UL |
MHW – UL | P4RK – UL | PC4W-SP – UL | SPSCWH-P – UL | SPSWV-P – UL |
P1224MC – UL | P4RK-R – UL | PC4WH – UL | SPSCWHK – UL | SR – UL |
P2R – UL | P4W – UL | PC4WH-P – UL | SPSCWHK-P – UL | SR-P – UL |
P2R-P – UL | P4W-P – UL | PC4WH-SP – UL | SPSCWK – UL | SR-SP – UL |
P2R-SP – UL | P4W-SP – UL | PC4WHK – UL | SPSCWK-CLR-ALERT – UL | SRH – UL |
P2RH – UL | P4WH – UL | PC4WK – UL | SPSCWK-R – UL | SRH-P – UL |
P2RH-LF – UL | P4WH-P – UL | SCR – UL | SPSCWV – UL | SRH-SP – UL |
P2RH-P – UL | P4WH-SP – UL | SCR-P – UL | SPSCWV-P – UL | SRHK – UL |
P2RH-SP – UL | P4WK – UL | SCR-SP – UL | SPSCWVH – UL | SRHK-P – UL |
P2RHK – UL | PC2R – UL | SCRH – UL | SPSCWVH-P – UL | SRHK-R – UL |
P2RHK-P – UL | PC2R-P – UL | SCRH-P – UL | SPSR – UL | SRK – UL |
P2RHK-R – UL | PC2RH – UL | SCRH-SP – UL | SPSR-P – UL | SRK-P – UL |
P2RK – UL | PC2RH-P – UL | SCRHK – UL | SPSRH – UL | SRK-R – UL |
P2RK-P – UL | PC2RH-SP – UL | SCRK – UL | SPSRH-P – UL | SW – UL |
P2RK-R – UL | PC2RHK – UL | SCW – UL | SPSRHK – UL | SW-ALERT – UL |
P2W – UL | PC2RK – UL | SCW-CLR-ALERT – UL | SPSRK – UL | SW-CLR-ALERT – UL |
P2W-P – UL | PC2W – UL | SCW-P – UL | SPSRK-P – UL | SW-P – UL |
P2W-SP – UL | PC2W-P – UL | SCW-SP – UL | SPSRK-R – UL | SW-SP – UL |
P2WH – UL | PC2W-SP – UL | SCWH – UL | SPSRV – UL | SWH – UL |
P2WH-LF – UL | PC2WH – UL | SCWH-P – UL | SPSRV-P – UL | SWH-ALERT – UL |
P2WH-P – UL | PC2WH-P – UL | SCWH-SP – UL | SPSW – UL | SWH-P – UL |
P2WH-SP – UL | PC2WH-SP – UL | SCWHK – UL | SPSW-ALERT – UL | SWH-SP – UL |
P2WHK – UL | PC2WHK – UL | SCWK – UL | SPSW-CLR-ALERT – UL | SWHK – UL |
P2WHK-P – UL | PC2WK – UL | SPSCR – UL | SPSW-P – UL | SWHK-P – UL |
P2WK – UL | PC4R – UL | SPSCRH – UL | SPSWH – UL | SWK – UL |
P2WK-P – UL | PC4R-P – UL | SPSCRV – UL | SPSWH-P – UL | SWK-P – UL |
P4R – UL | PC4R-SP – UL | SPSCRVH – UL | SPSWK – UL | P2GRL |
P4R-P – UL | PC4RH – UL | P2RL | P2WL | P2GWL |
P2RL-P | P2WL-P | P2RL-SP | P2WL-SP | P4RL |
P4WL 4 | SRL | SWL | SGRL | SGWL |
SRL-P | SWL-P | SRL-SP | SWL-CLR-ALERT | SPSCWL |
SPSCRL | SPSCWL-P | SPSCWL-SP | SPSCWL-CLR-ALERT | SPSWL |
SPSRL | SPSWL-P | SPSRL-P | SPSWL-Alert | SPSWL-CLR-Alert |
SPSRL-SP |
Gentex:
GCS24CR – UL | GCCB24PCR / W – UL | GEC24-15/75WR – UL |
---|---|---|
GCS24CW – UL | GCCG24PCR / W – UL | GEC24-15/75WW – UL |
GCS24PCR – UL | GCCR24PCR / W – UL | SSPK24CLPR – UL |
GCS24PCW – UL | WGESA24-75PWR / W – UL | SSPK24CLPW – UL |
GCC24CR – UL | WGESB24-75PWR / W – UL | SSPK24WLPR – UL |
GCC24PCR – UL | WGESG24-75PWR / W – UL | SSPK24WLPW – UL |
GCC24CW – UL | WGESR24-75PWR / G – UL | SSPK24AWR – UL |
GCC24PCW – UL | WGECA24-75PWR / W – UL | SSPK24AWW – UL |
GES3-24WR – UL | WGECB24-75PWR / W – UL | SSPK24-15/75WLPR – UL |
GEC3-24WR – UL | WGECG24-75PWR / W – UL | SSPK24-15/75WLPW – UL |
GEH24-R – UL | WGECR24-75PWR / G – UL | SSPK24-15/75AWR – UL |
GEH24-W – UL | WGESA24-75PWLPR / W – UL | SSPK24-15/75AWW – UL |
WGES24-75WR / WW – UL | WGESB24-75PWLPR / W – UL | SSPKA24-15/75PWR – UL |
WGES24-75PWR / PWW – UL | WGESG24-75PWLPR / W – UL | SSPKA24-15/75PWW – UL |
WGES24-75WRLP / WWLP – UL | WGESR24-75PWLPR / W – UL | SSPKA24-15/75AWR – UL |
WGEC24-75WR / WW – UL | WGECA24-75PWLPR / W – UL | SSPKA24-15/75AWW – UL |
WGEC24-75PWR / PWW – UL | WGECB24-75PWLPR / W – UL | SSPKB24-15/75PWR – UL |
WGEC24-75WRLP / WWLP – UL | WGECG24-75PWLPR / W – UL | SSPKB24-15/75PWW – UL |
WGEC24-75PWRLP / WWLP – UL | WGECR24-75PWLPR / W – UL | SSPKG24-15/75PWR – UL |
GESA24PWR / W – UL | GX91-R / W – UL/cUL | SSPKG24-15/75PWW – UL |
GESB24PWR / W – UL | GX91-PR / W – UL/cUL | SSPKR24-15/75PWR – UL |
GESG24PWR / W – UL | GX93-R / W – UL/cUL | SSPKR24-15/75PWW – UL |
GESR24PWR / W – UL | GX93-PR / W – UL/cUL | WSSPKA24-15/75AWR – UL |
GECA24PWR / W – UL | WSSPK24-15/75WR / WW – UL | WSSPKA24-15/75AWW – UL |
GECB24PWR / W – UL | WSSPK24-15/75PWR / PWW – UL | WSSPKA24-15/75PWR – UL |
GECG24PWR / W – UL | WSSPK24-15/75AWR / AWW – UL | WSSPKA24-15/75PWW – UL |
GECR24PWR / W – UL | GES24-177WR – UL | WSSPKB24-15/75PWR – UL |
GCSA24PCR / W – UL | GES24-177WW – UL | WSSPKB24-15/75PWW – UL |
GCSB24PCR / W – UL | GES24-15/75WR – UL | WSSPKG24-15/75PWR – UL |
GCSG24PCR / W – UL | GES24-15/75WW – UL | WSSPKG24-15/75PWW – UL |
GCSR24PCR / W – UL | GEC24-177WR – UL | WSSPKR24-15/75PWR – UL |
GCCA24PCR / W – UL | GEC24-177WW – UL | WSSPKR24-15/75PWW – UL |
Potter/Amseco:
CM24CR – UL | CSL-1224W-BW – UL/cUL | MH-12/24W – UL/cUL | SSC8-177R – UL |
---|---|---|---|
CM24CW – UL | CSL-1224W-GR – UL/cUL | SCM24C-177R – UL | SSC8-177W – UL |
CSH-1224W-AR – UL/cUL | CSL-1224W-GW – UL/cUL | SCM24C-177W – UL | SSC8-3075110R |
– UL
CSH-1224W-AW – UL/cUL| CSL-1224W-RR – UL/cUL| SCM24C-3075110R – UL|
SSC8-3075110W – UL
CSH-1224W-BR – UL/cUL| CSL-1224W-RW – UL/cUL| SCM24C-3075110W – UL| SSR2-177R
– UL
CSH-1224W-BW – UL/cUL| CSL24CAW – UL/cUL| SH-1224R – UL/cUL| SSR2-177W – UL
CSH-1224W-GR – UL/cUL| CSL24C-BW – UL/cUL| SH-1224W – UL/cUL| SSR2-3075110R –
UL
CSH-1224W-GW – UL/cUL| CSL24C-GW – UL/cUL| SH-1224WP-R – UL/cUL| SSR2-3075110W
– UL
CSH-1224W-RR – UL/cUL| CSL24C-RW – UL/cUL| SH-1224WP-W – UL/cUL| SSR8-177R –
UL
CSH-1224W-RW – UL/cUL| CSL24C-AR – UL/cUL| SH24C-177R – UL/cUL| SSR8-177W – UL
CSH24C-AW – UL/cUL| CSL24C-BR – UL/cUL| SH24C-177W – UL/cUL| SSR8-3075110R –
UL
CSH24C-BW – UL/cUL| CSL24C-GR – UL/cUL| SL-1224R – UL/cUL| SSR8-3075110W – UL
CSH24C-GW – UL/cUL| CSL24C-RR – UL/cUL| SL-1224W – UL/cUL| SSS2-1530R – UL
CSH24C-RW – UL/cUL| H-1224R – UL/cUL| SL-1224WP-R – UL/cUL| SSS2-1530W – UL
CSH24C-AR – UL/cUL| H-1224W – UL/cUL| SL-1224WP-W – UL/cUL| SSS2-75110R – UL
CSH24C-BR – UL/cUL| HP-25TR – UL/cUL| SL-24W – UL/cUL| SSS2-75110W – UL
CSH24C-GR – UL/cUL| HP-25TW – UL/cUL| SSC2-177R – UL| SSS8-1530R – UL
CSH24C-RR – UL/cUL| MH-12/24R – UL/cUL| SSC2-177W – UL| SSS8-1530W – UL
CSL-1224W-AR – UL/cUL| MH-12/24TR – UL/cUL| SSC2-3075110R – UL| SSS8-75110R –
UL
CSL-1224W-AW – UL/cUL| MH-12/24TW – UL/cUL| SSC2-3075110W – UL| SSS8-75110W –
UL
CSL-1224W-BR – UL/cUL| | |
Cooper/Wheelock:
50-241575W-FR – UL/cUL| E70-24MCW-FN – UL/cUL| ET90-24MCCH-FN – UL/cUL|
LSTW-A – UL/cUL
---|---|---|---
AH-24WP-R – UL| E70-24MCW-FR – UL/cUL| ET90-24MCCH-FW – UL/cUL| LSTW-ALA –
UL/cUL
AMT-12/24-R – UL/cUL| E70-24MCW-FW – UL/cUL| HNR – UL/cUL| LSTW-NA – UL/cUL
AMT-12/24-W – UL/cUL| E70-24MCWH-FN – UL/cUL| HNRC – UL/cUL| LSTW-NA – UL/cUL
AMT-241575W-FR – UL/cUL| E70-24MCWH-FR – UL/cUL| HNW – UL/cUL| MIZ-24S-R –
UL/cUL
AMT-241575W-FR-NYC – UL| E70-24MCWH-FR – UL/cUL| HNWC – UL/cUL| MIZ-24S-W –
UL/cUL
AMT-241575W-FW – UL/cUL| E70-24MCWH-FW – UL/cUL| HS-24-R – UL/cUL| MT-12/24-R
– UL
AMT-24MCW-FR – UL/cUL| E70H-241575W-FR – UL/cUL| HS-24-W – UL/cUL| MT-241575W-
FR – UL/cUL
AMT-24MCW-FW – UL/cUL| E70H-241575W-FW – UL/cUL| HS4-241575W-FR – UL/cUL| MT-
241575W-FW – UL/cUL
AS-12100C – UL/cUL| E70H-24MCW-FR – UL/cUL| HS4-24MCC-FR – UL| MT-24MCW-FR –
UL/cUL
AS-24100C – UL/cUL| E70H-24MCW-FW – UL/cUL| HS4-24MCC-FW – UL/cUL| MT-24MCW-FW
– UL/cUL
ASWP-2475C-FR – UL| E70H-24MCWH-FN – UL/cUL| HS4-24MCW-FR – UL/cUL| MTWP-
2475C-FR – UL
ASWP-2475C-FW – UL| E70H-24MCWH-FW – UL/cUL| HS4-24MCW-FW – UL/cUL| MTWP-
2475C-FW – UL
ASWP-2475W-FR – UL| E90-24MCC-FN – UL/cUL| HSR – UL/cUL| MTWP-2475W-FR – UL
ASWP-2475W-FW – UL| ET90-24MCC-FW – UL/cUL| HSRC – UL/cUL| MTWP-2475W-FW – UL
ASWP-24MCCH-FR – UL| ET90-24MCC-FN – UL/cUL| HSW – UL/cUL| MTWP-24MCCH-FR – UL
ASWP-24MCCH-FW – UL| E90-24MCC-FR – UL/cUL| HSWC – UL/cUL| MTWP-24MCCH-FW – UL
ASWP-24MCWH-FR – UL| E90-24MCC-FW – UL/cUL| LHNR – UL/cUL| MTWP-24MCWH-FR –
UL
ASWP-24MCWH-FW – UL| E90-24MCCH-FN – UL/cUL| LHNW – UL/cUL| MTWP-24MCWH-FW –
UL
CH70-24MCW-FR – UL/cUL| E90-24MCCH-FR – UL/cUL| LHSR – UL/cUL| RSS-241575W-FR
– UL/cUL
CH70-24MCW-FW – UL/cUL| E90-24MCCH-FW – UL/cUL| LHSR-A – UL/cUL| RSS-241575W-
FW – UL/cUL
CH70-24MCWH-FR – UL/cUL| E90H-24MCC-FR – UL/cUL| LHSR-AL – UL/cUL| RSS-24MCW-
FR – UL/cUL
CH70-24MCWH-FW – UL/cUL| E90H-24MCC-FW – UL/cUL| LHSR-N – UL/cUL| RSS-24MCW-
FW – UL/cUL
CH90-24MCC-FR – UL/cUL| E90H-24MCCH-FR – UL/cUL| LHSW – UL/cUL| RSS-24MCWH-FR
– UL/cUL
CH90-24MCC-FW – UL/cUL| E90H-24MCCH-FW – UL/cUL| LHSW-A – UL/cUL| RSS-24MCWH-
FW – UL/cUL
CH90-24MCCH-FR – UL/cUL| EET90-24MCCH-FR – UL/cUL| LHSW-AL – UL/cUL| RSSA-
24MCC-NW – UL
CH90-24MCCH-FW – UL/cUL| ET-1010-R – UL| LHSW-N – UL/cUL| RSSA-24MCCH-NW – UL
E50-241575W-FW – UL/cUL| ET-1010-W – UL| LSPSTR – UL/cUL| RSSB-24MCC-NW – UL
E50-24MCWH-FR – UL/cUL| ET70-241575W-FR – UL/cUL| LSPSTR-AL – UL/cUL| RSSB-
24MCCH-NW – UL
E50-24MCWH-FW – UL/cUL| ET70-241575W-FW – UL/cUL| LSPSTR-ALA – UL/cUL| RSSG-
24MCC-NW – UL
E50H-241575W-FR – UL/cUL| ET70-24MCW-FN – UL/cUL| LSPSTR-N – UL/cUL| RSSG-
24MCCH-NW – UL
E50H-241575W-FW – UL/cUL| ET70-24MCW-FR – UL/cUL| LSPSTR-NA – UL/cUL| RSSR-
24MCC-NW – UL
E50H-24MCW-FR – UL/cUL| ET70-24MCW-FW – UL/cUL| LSPSTW – UL/cUL| RSSR-24MCCH-
NW – UL
E50H-24MCW-FW – UL/cUL| ET70-24MCWH-FN – UL/cUL| LSPSTW-AL – UL/cUL| RSSWP-
2475C-FR – UL
E50H-24MCWH-FR – UL/cUL| ET70-24MCWH-FR – UL/cUL| LSPSTW-ALA – UL/cUL| RSSWP-
2475C-FW – UL
E50H-24MCWH-FW – UL/cUL| ET70-24MCWH-FW – UL/cUL| LSPSTW-N – UL/cUL| RSSWP-
2475W-AR – UL
E60-24MCC-FR – UL/cUL| ET70WP-24185W-FR – UL| LSPSTW-NA – UL/cUL| RSSWP-
2475W-FR – UL
E60-24MCC-FW – UL/cUL| ET70WP-24185W-FW – UL| LSTR – UL/cUL| RSSWP-2475W-FW –
UL
E60-24MCCH-FR – UL/cUL| ET70WP-2475C-FR – UL| LSTR-A – UL/cUL| RSSWP-2475W-NW
– UL
E60-24MCCH-FW – UL/cUL| ET70WP-2475C-FW – UL| LSTR-AL – UL/cUL| RSSWP-24MCCH-
FR – UL
E60H-24MCC-FR – UL/cUL| ET80-24MCW-FR – UL/cUL| LSTR-ALA – UL/cUL| RSSWP-
24MCCH-FW – UL
E60H-24MCC-FW – UL/cUL| ET80-24MCW-FW – UL/cUL| LSTR-NA – UL/cUL| RSSWP-
24MCWH-FR – UL
E60H-24MCCH-FR – UL/cUL| ET80-24MCWH-FR – UL/cUL| LSTRW-ALA – UL/cUL| RSSWP-
24MCWH-FW – UL
E60H-24MCCH-FW – UL/cUL| ET80-24MCWH-FW – UL/cUL| LSTW* – UL/cUL| S8-24MCC-FW
– UL/cUL
S8-24MCCH-FW – UL/cUL| STH-3R24MCCH-NR – UL| STR-ALB – UL| STW-ALB – UL
SA-S70-24MCW-FR – UL| STH-4M30WC – UL| STR-NA – UL| STW-NA – UL
SA-S70-24MCW-FW – UL| STH-4MS-R – UL| STR-NB – UL| STW-NB – UL
SA-S90-24MCC-FR – UL| STH-4R – UL| STR-NG – UL| STW-NG – UL
SA-S90-24MCC-FW – UL| STH-4R24MCCH-NW – UL| STR-NR – UL| STW-NR – UL
STH-2G – UL| STH-4R24MCCH110B-NR – UL| STRC-NA – UL| STWC-AB – UL
STH-2MS-R – UL| STH-4R24MCCH110R-NA – UL| STRC-NB – UL| STWC-ALA – UL
STH-2R – UL| STH-4R24MCCH110R-NR – UL| STRC-NG – UL| STWC-ALB – UL
STH-2R24MCCH-NR – UL| STH-90-4R24MCCH-NW – UL| STRC-NR – UL| STWC-NA – UL
STH-3MS-R – UL| STR-AB – UL| STW-AB – UL| STWC-NB – UL
STH-3R – UL| STR-ALA – UL| STW-ALA – UL| STWC-NG – UL
| | | STWC-NR – UL
Appendix B – UL Listed Compatible Devices
B-1 Relays
Table B-2 below lists relays compatible with AL642ULADA AUX output and Outputs
1-8 when programmed as AUX.
Manufacturer | Model | Current (mA) |
---|
System Sensor
| PR-1| 15
PR-2| 30
PR-3| 30
EOLR-1| 30
R-10T| 23
R-14T| 23
Manufacturer| Model| Current (mA)
---|---|---
System Sensor
| R-20T| 40
R-24T| 40
R-10E| 23
R-14E| 23
R-20E| 40
R-24E| 40
Enclosure Dimensions
18” x 14.5” x 4.625” (457mm x 368mm x 118mm)
Altronix is not responsible for any typographical errors.140 58th Street,
Brooklyn, New York 11220 USA | phone:
718-567-8181 | fax:
718-567-9056. website:
www.altronix.com.
e-mail: info@altronix.com. | Lifetime Warranty
IIAL642ULADA I24U.