klaxon Nexus 110 AC Sounder and Sounder Beacon Instruction Manual

October 30, 2023
KLAXON

klaxon Nexus 110 AC Sounder and Sounder Beacon

Product Information

The Nexus 110 AC Sounder & Sounder-Beacon is a device designed to produce various tones for alerting and evacuation purposes. It comes with 64 tone options that are compliant with different standards, such as BS5839-1:2002, Apollo Fire Systems Alert Tone, Apollo Fire Systems Evacuate Tone, ISO 8201 Low tone, ISO 8201 High tone, Australia AS1670 Alert tone, and more. The device also has a peak sound level of 116dBA@1m and can be connected to a controller, beacon, and common N.

Product Usage Instructions

  1. Before installation, ensure that the unit is fitted with a fused spur incorporating an all-pole disconnection device providing 3mm contact separation in all poles. Also, ensure that the fuse, cable size, and gland type are rated sufficiently for the total load on the sounder circuit.
  2. Isolate the unit from the electricity supply before removing the cover. Only suitably qualified personnel should gain access to the unit to perform adjustments to the tone or volume. WARNING: no user serviceable parts contained within the unit.
  3. To install the sounder, mount the base unit first and make the external wiring connections to the base. The head unit then automatically connects when it is attached to the base.
  4. Note that the head only fits onto the base one way around. If a beacon is fitted, care should be taken when mounting the base to ensure that the beacon will be positioned in the desired orientation after the sounder is attached.
  5. Refer to the dip switch (S1/S2) settings for selecting the desired tone option.
  6. Refer to the peak sound level (dBA@1m) for adjusting the volume level of the sounder.
  7. Connect the device to a controller, beacon, and common N as per the installation diagram provided in the manual.
  8. Test the device after installation to ensure that it is functioning properly.

Tone Description

klaxon-Nexus-110-AC-Sounder-and-Sounder-Beacon-fig-
\(1\) klaxon-Nexus-110-AC-Sounder-and-
Sounder-Beacon-fig- \(2\)

IMPORTANT

  • The unit should be fitted with a fused spur incorporating an all pole disconnection device providing 3mm contact separation in all poles. Ensure fuse, cable size and gland type are rated sufficiently for the total load on the sounder circuit.

  • Isolate the unit from the electricity supply before removing the cover. Only suitably qualified personnel should gain access to the unit to perform adjustments to the tone or volume.
    WARNING: no user-serviceable parts contained within the unit.

  • The sounder is installed by first mounting the base unit and making the external wring connections to the base. The head unit then automatically connects when it is attached to the base.

  • The sounder head is separated from the base by unlocking the four ¼-turn fasteners in the corners of the sounder. (Recommended screwdriver: Philips No. 2, min 100mm long).

  • Note that the head only fits onto the base one way around. If a beacon is fitted, care should be taken when mounting the base to ensure that the beacon will be positioned in the desired orientation after the sounder is attached.

Wiring

klaxon-Nexus-110-AC-Sounder-and-Sounder-Beacon-fig-
\(3\)

  • Power: Note that the sounder and beacon have separate power terminals, marked as follows:klaxon-Nexus-110-AC-Sounder-and-Sounder-Beacon-fig- \(4\)
  • Remote Tone Switching (If required): Externally link control terminals as shown below.klaxon-Nexus-110-AC-Sounder-and-Sounder-Beacon-fig- \(5\)

Controls

  • Tone Selection
    The first and second-stage alarm tones are independently set using 6-way dipswitches S1 and S2 respectively. The required settings are shown in the table overleaf. The third stage alarm tone is pre-set to complement the selected first stage tone as shown in the table.

  • Volume Control
    The sound output of the unit can be reduced by up to 20dBA by adjusting the potentiometer.

Technical Specification

  • Supply Voltage Range 110/230V 50/60Hz
  • Current
    • Sounder – 40mA max.
    • Beacon (where fitted) – 70mA
  • Peak Sound Level 103-115 dBA at 1m*
  • Number of Tones 64
  • Frequency Range 340 – 2900 Hz*
  • Volume Control 20 dBA typical
  • Remote Tone Switching Provision for 3 volt-free contact activated alarm stages
  • Operating Temperature – 25°C to +55°C
  • Casing High Impact Polycarbonate/ABS
  • IP Rating IP66 with suitable cable glands
  • Synchronisation Automatic with Klaxon Nexus and Sonos Sounders

depends on the selected tone.

The European directive “Waste Electrical and Electronic Equipment” (WEEE) aims to minimize the impact of electrical and electronic equipment waste on the environment and human health. To conform with this directive, electrical equipment marked with this symbol must not be disposed of in European public disposal systems. European users of electrical equipment must now return end- of-life equipment for disposal. Further information can be found on the following website: http://www.recyclethis.info/.