klaxon SLM-0001 Master Blaster Siren Instruction Manual
- June 10, 2024
- KLAXON
Table of Contents
SLM-0001 Master Blaster Siren
Instruction Manual Master Blaster Siren
Installation Instructions
SPECIFICATIONS
Model No. | SLM-0001 |
---|---|
Supply Voltage V (AC) | 230 |
Supply Frequency (Hz) | 50/60 +/- 0.5Hz |
Voltage Tolerance | +/-10% |
Rated Current (A) | 2 |
Rated Operating Duration (on/off) minutes | 15/120 |
Rated Temperature (°C) | -30°/+40° |
Ingress Protection (EN60529) | IP21A |
Frequency (Hz) | 1800 |
Maximum sound output level @ 1m | 120 dB(A) |
Weight (Kg) | 1.8 |
DIMENSIONS
NOTE: The Master Blaster siren is only suitable for installations with a
security or fire system control panel that provides a DC trigger signal.
IMPORTANT
The unit should be fitted with a fused spur incorporating an all pole
disconnection device providing 3mm contact separation in all poles. Ensure the
fused spur is fitted with the 5 amp fuse supplied. Isolate the unit from the
electricity supply before removing the cover.
WARNING: No user serviceable parts contained within the unit.
WARNING: The siren generates very high sound levels.
Unprotected exposure could lead to permanent hearing damage. Ensure
appropriate hearing protection is used when working in close proximity to the
siren.
WARNING: The siren contains rotating parts. Mount the unit at least 1.5m
clear of normally accessible areas. Keep hands well clear of the siren when in
operation.
The siren will operate in any orientation and may be mounted on any flat
surface or conduit box. Ensure that airflow around the rotating impellor is
not impaired.
NOTE: If the unit is to be used outdoors, or where water may drip onto it, the
siren must be mounted with the impellor downwards, and should only be sited in
sheltered locations not directly exposed to the effects of adverse weather
conditions. A functional earth terminal is provided on the bracket for
connection to the earth supply. The siren is double insulated and should not
be earthed.
INSTALLATION
Loosen the two retaining screws and slide the bracket out of its retaining
slots. Position the bracket on the surface required, allowing enough space
above the final position for
the movement of the siren during assembly. A “keyhole” slot is provided to
assist in vertical mounting of the bracket. Select two diagonally opposite
fixing holes of the four rovided.
(The other two are provided for fitting to a horizontal or vertical conduit
box).
Mark their position, drill as required (including a 20mm hole if the cables
are to pass through the wall) and fix the bracket. Connect to the supply earth
if required.
Offer the siren into position, passing the cables though the wall or through
the triangular aperture between the bracket and the siren – left or right as
required – and engage the retaining slots onto the bracket and slide into
position.
Tighten the retaining screws and complete the wiring.
The brown and blue cores should be connected to a 5 A fused AC supply.
BROWN – LIVE BLUE – NEUTRAL.
The twin flex is connected to the D.C supply that is to control the operation
of the siren i.e. the alarm bell circuit of a security system or sounder
circuit of a fire system. The D.C supply should be connected as follows:
WHITE – POSITIVE
WHITE WITH A BLACK STRIPE – NEGATIVE.
The siren is protected against reverse polarity connection and the relay will
not operate if wrongly connected.
OPERATION
Connect the permanent AC supply. The siren will activate when the appropriate
trigger voltage is applied the trigger input.
Fuse rating: 5A
The European directive “Waste Electrical and Electronic Equipment” (WEEE) aims
to minimise the impact of electrical and electronic equipment waste on the
environment and human health. To conform with this directive, electrical
equipment marked with this symbol must not be disposed of in European public
disposal systems. European users of electrical equipment must now return end-
of-life equipment for disposal. Further information can be found on the
following website: http://www.recyclethis.info/.
Texecom Ltd (Incorporating Klaxon Signals)
St Crispin Way, Haslingden, BB4 4PW, UK
**** +44 1706 233879
(June 2022) 18-182186-9
Copyright © Texecom Ltd
Email: sales@klaxonsignals.com
www.klaxonsignals.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>