klaxon Sonos DC Sounder Beacon
PRODUCT INFORMATION
PThe Sonos DC Sounder Beacon is a fire alarm device that produces both sound and light to alert individuals in case of a fire emergency. It comes in two types – Type A for indoor use with a shallow base and Type B for outdoor use with a deep base. The sounder has been tested and declared to meet the EN54-3:2001+A1:2002 A2:2006 standard for operational performance, durability, and enclosure protection.
Installation Instructions
To install the sounder, activate the mechanism for locking the sounder to the base by removing the thin section of plastic shown in Fig. 1a with side cutters or a similar tool. The sounder and beacon 0V terminals can be linked together for simultaneous control of sound and light using a 2-core connection. A separate earth terminal is provided on the deep base for connecting the screen or functional earth. On the shallow base, terminal 5 can be used for this purpose.
Tone Selection and Volume Control
The tone is selected using the 5-way dipswitch on the bottom of the sounder.
There are 32 tone types to choose from, each with a corresponding tone
description/application, dBA @ 1m, and mA values listed in the table. To
adjust the volume, adjust the power supply voltage.
Disclaimer: These instructions are a summary and should not replace the
full product manual. Always refer to the manual forcomplete and accurate
information.
TONE DESCRIPTION/ APPLICATION
Type | CPR Reference | CPD Number |
---|---|---|
PSS-0068 | Reference 0832-CPR-0297 | PSS-0068/73/79/80 & PSC-0055 :0832-CPD-0297 |
PSC-0045 | Reference 0832-CPR- 0546 | PSC-0045/54/62/63/51 |
:0832-CPD-0546
- Technical Data Doc.18-186215
- Fire Alarm Device – Sounder
- Type A: For indoor use (Shallow Base)
- Type B: For outdoor use (Deep Base)
Declared Performance
Essential Characteristics| EN54-3:2001+A1:2002
A2:2006 Subclause
---|---
Reproducibility| 5.2
Operational performance| 5.3
Durability| 5.4
Dry Heat (operational)| 5.5
Dry Heat (endurance)| 5.6
Cold (operational)| 5.7
Damp heat, cyclic (operational)| 5.8
Damp heat, steady state (endurance)| 5.9
Damp Heat, cyclic (endurance)| 5.10
SO2 corrosion (endurance)| 5.11
Shock (operational)| 5.12
Impact (operational)| 5.13
Vibration (operational)| 5.14
Vibration (endurance)| 5.15
Electrostatic discharge (operational)| 5.16
Radiated electromagnetic fields (operational)| 5.16
Voltage transients, fast transient bursts (operational)| 5.16
Enclosure Protection| 5.17
Installation
- If required, the mechanism for locking the sounder to the base can be activated by removing the thin section of plastic shown in Fig. 1a with side cutters or a similar tool. To open a locked head, remove the small rubber bung from the hole on the side of the sounder, insert a tool into the hole and depress the clip whilst twisting the head. The O-ring and bung must be re-fitted to maintain the weatherproofing.
- An alternative locking method is shown in Fig. 1b. Drive the hexagonal locking screw forward by turning a 1.5mm hexagonal key clockwise until the head is locked.
Wiring
Line Terminal Marking
Common Positive Supply| (3) IN+
Sounder Negative Supply| (2) – or COM –
Beacon Negative Supply| (1)
-
The sounder and beacon 0V terminals can be linked together for simultaneous control of sound and light using a 2-core connection.
(Common-Operation models are supplied with terminals 1 & 2 already linked by a permanent internal connection.) -
A separate earth terminal is provided on the deep base for connecting the screen or functional earth. On the shallow base, terminal 5 can be used for this purpose.
Tone Selection and Volume Control
- The tone is selected using the 5 way dipswitch on the bottom of the sounder head. Refer to the table overleaf for details of the available tones and the switch settings required to select them.
- The sound output of the unit can be reduced by adjusting the potentiometer on the bottom of the sounder.
Technical Specification
Supply Voltage | 17 – 60V DC |
---|---|
Current | Sounder: 4- 45mA* |
Beacon: 5mA | |
Peak Sound Level | 94 – 106 dBA at 1m* |
Number of tones | 32 |
Frequency Range | 400 – 2850 Hz* |
Rating | Continuous |
Operating Temperature | – 25˚C to + 70˚C |
Casing | High Impact Polycarbonate |
IP Rating | IP21/IP65 (deep base) |
Syncronisation | Automatic |
*depends on selected tone and input voltage. See tone table for details. EN54-3 certified on tones 1,2,3,6,7 & 13 & > 17v DC only.
DISPOSAL
The European directive “Waste Electrical and Electronic Equipment” (WEEE) aims to minimise the impact of electrical and electronic equipment waste on the environment and human health. To conform with this directive, electrical equipment marked with this symbol must not be disposed of in European public disposal systems. European users of electrical equipment must now return end- of-life equipment for disposal. Further information can be found on the following website: http://www.recyclethis.info/.