INTRODUCTION

The Verdant VX Series Thermostat delivers unprecedented energy savings without compromising guest comfort. An Integrated occupancy sensor reduces HVAC and Lighting energy use when rooms are unoccupied. Energy-saving presets eliminate guesswork and make it easy to adjust the energy-saving settings. A patented “Night Occupancy” feature ensures comfort while guests are sleeping. Built-in wireless mesh networking enables optional remote management features. Fully configurable settings allow for the customization of energy savings to fit any situation.

  • Temperature Setback automatically adjusts the temperature when rooms are unoccupied to save energy.
  • Temperature Recovery allows for setting a maximum time permitted for establishing a comfortable room temperature.
  • Setback Optimization monitors the temperature recovery rate and optimizes setback temperatures.
  • Setback Limits control the maximum and minimum room temperature when a room is in setback mode.
  • Set Point Limits prevent guests from setting the room temperature to extreme, energy-wasting levels.

SPECIFICATION

  • Easy-to-use Thermostat
  • Unparalleled Energy Savings
  • Uncompromising Guest Comfort
  • Quick-and-Easy Installation
  • Aux Output For Control Of External Devices
  • Remote Management Capabilities*

Installation

Verdant -VX-TL-KT -Energy -Management- Thermostat-
FIG-1

Control Card Installation – Wiring Table (A)

Wiring Table – 24V AC

Wire Color Terminal Letter Terminal Connection
BLACK C COMMON
RED R 24V
YELLOW Y COMPRESSOR
WHITE W HEAT
ORANGE O/B REVERSE VALVE
GREEN GH FAN HIGH
PURPLE GL FAN LOW
BROWN AUX AUXILIARY

Wiring Table – 24V DC

Wire Color Terminal Letter Terminal Connection
BLACK R 24V
RED C COMMON
YELLOW Y COMPRESSOR
WHITE W HEAT
ORANGE O/B REVERSE VALVE
GREEN GH FAN HIGH
PURPLE GL FAN LOW
BROWN AUX AUXILIARY

Thermostat to Control Card Installation (Optional) – Wiring Table (B)

Wiring Table – 24V AC

Wire Color Terminal Letter Terminal Connection
BLACK C COMMON
RED R 24V

Wiring Table – 24V DC

Wire Color Terminal Letter Terminal Connection
BLACK R 24V
RED C COMMON

Thermostat to Lighting Relay Installation – Wiring Table (C)

Wiring Table – 24V AC

Wire Color Terminal Connection
BLACK COMMON
PURPLE LIGHT RELAY

Wiring Table – 24V DC

Wire Color Terminal Connection
RED COMMON
PURPLE LIGHT RELAY

COMPATIBLE TABLE

Case Dimensions (Imperial) 4.02 x 5.51” x 0.93” 3.875” x 2.125” x 0.75”
Case Dimensions (Metric) 102mm x 140mm x 23.5mm 98mm x 54mm x 19mm
Screen Dimensions (Imperial) 3.63” x 2.13” N/A
Screen Dimensions (Metric) 92mm x 54mm N/A
Operating Voltage 3V DC – 2 “AA” Cell Batteries 24V AC/DC (HVAC Unit)
Control Outputs Fan High (GH)
Fan Low (GL)
Compressor (Y)
Heat Pump (OB)
Heat (W)
Occupancy Out (Aux)
Occupancy Sensor Beam Width ±47° (94°) N/A
Wireless Frequency 902-928MHz 902-928MHz
Temperature Accuracy ±1°F N/A
FCC ID XEYWX XEYV8ACCC
IC 8410A-WX 8410A-V8ACCC