Verdant VX-TL-KT Energy Management Thermostat Product Specifications Guide

October 30, 2023
Verdant

Verdant VX-TL-KT Energy Management Thermostat

Verdant -VX-TL-KT- Energy -Management- Thermostat-PRO

View all Verdant thermostat manual

INTRODUCTION

The Verdant VX Series Thermostat delivers unprecedented energy savings without compromising guest comfort. An Integrated occupancy sensor reduces HVAC and Lighting energy use when rooms are unoccupied. Energy-saving presets eliminate guesswork and make it easy to adjust the energy-saving settings. A patented “Night Occupancy” feature ensures comfort while guests are sleeping. Built-in wireless mesh networking enables optional remote management features. Fully configurable settings allow for the customization of energy savings to fit any situation.

  • Temperature Setback automatically adjusts the temperature when rooms are unoccupied to save energy.
  • Temperature Recovery allows for setting a maximum time permitted for establishing a comfortable room temperature.
  • Setback Optimization monitors the temperature recovery rate and optimizes setback temperatures.
  • Setback Limits control the maximum and minimum room temperature when a room is in setback mode.
  • Set Point Limits prevent guests from setting the room temperature to extreme, energy-wasting levels.

SPECIFICATION

  • Easy-to-use Thermostat
  • Unparalleled Energy Savings
  • Uncompromising Guest Comfort
  • Quick-and-Easy Installation
  • Aux Output For Control Of External Devices
  • Remote Management Capabilities*

Installation

Verdant -VX-TL-KT -Energy -Management- Thermostat-
FIG-1

Control Card Installation – Wiring Table (A)

Wiring Table – 24V AC

Wire Color Terminal Letter Terminal Connection
BLACK C COMMON
RED R 24V
YELLOW Y COMPRESSOR
WHITE W HEAT
ORANGE O/B REVERSE VALVE
GREEN GH FAN HIGH
PURPLE GL FAN LOW
BROWN AUX AUXILIARY

Wiring Table – 24V DC

Wire Color Terminal Letter Terminal Connection
BLACK R 24V
RED C COMMON
YELLOW Y COMPRESSOR
WHITE W HEAT
ORANGE O/B REVERSE VALVE
GREEN GH FAN HIGH
PURPLE GL FAN LOW
BROWN AUX AUXILIARY

Thermostat to Control Card Installation (Optional) – Wiring Table (B)

Wiring Table – 24V AC

Wire Color Terminal Letter Terminal Connection
BLACK C COMMON
RED R 24V

Wiring Table – 24V DC

Wire Color Terminal Letter Terminal Connection
BLACK R 24V
RED C COMMON

Thermostat to Lighting Relay Installation – Wiring Table (C)

Wiring Table – 24V AC

Wire Color Terminal Connection
BLACK COMMON
PURPLE LIGHT RELAY

Wiring Table – 24V DC

Wire Color Terminal Connection
RED COMMON
PURPLE LIGHT RELAY

COMPATIBLE TABLE

Case Dimensions (Imperial) 4.02 x 5.51” x 0.93” 3.875” x 2.125” x 0.75”
Case Dimensions (Metric) 102mm x 140mm x 23.5mm 98mm x 54mm x 19mm
Screen Dimensions (Imperial) 3.63” x 2.13” N/A
Screen Dimensions (Metric) 92mm x 54mm N/A
Operating Voltage 3V DC – 2 “AA” Cell Batteries 24V AC/DC (HVAC Unit)
Control Outputs Fan High (GH)
Fan Low (GL)
Compressor (Y)
Heat Pump (OB)
Heat (W)
Occupancy Out (Aux)
Occupancy Sensor Beam Width ±47° (94°) N/A
Wireless Frequency 902-928MHz 902-928MHz
Temperature Accuracy ±1°F N/A
FCC ID XEYWX XEYV8ACCC
IC 8410A-WX 8410A-V8ACCC

Verdant VX-TL-KT Energy Management Thermostat Product Specifications Guide

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Verdant User Manuals

Related Manuals