Verdant VX-T6-KT Energy Management Thermostat Product Specifications Guide

October 30, 2023
Verdant

Verdant VX-T6-KT Energy Management Thermostat

View all Verdant thermostat manual

  • Easy-to-use Thermostat
  • Unparalleled Energy Savings
  • Uncompromising Guest Comfort
  • Quick-and-Easy Installation
  • The auxiliary output allows for integration with make-up air units, lighting, and other devices.
  • Can Connect to HVAC unit Wired or Wirelessly
  • Remote Management Capabilities*

The Verdant VX Series Thermostat delivers unprecedented energy savings without compromising guest comfort.
An integrated occupancy sensor allows for energy saving when rooms are unoccupied.
Energy-saving presets eliminate guesswork and make it easy to adjust the energy-saving settings.
A patented “Night Occupancy” feature ensures comfort while guests are sleeping.
Built-in wireless mesh networking enables optional remote management features.
Fully configurable settings allow for the customization of energy savings to fit any situation.

  • Temperature Setback automatically adjusts the temperature when rooms are unoccupied to save energy.
  • Temperature Recovery allows for setting a maximum time permitted for establishing a comfortable room temperature.
  • Setback Optimization monitors the temperature recovery rate and optimizes setback temperatures.
  • Setback Limits control the maximum and minimum room temperature when a room is in setback mode.
  • Set Point Limits prevent guests from setting the room temperature to extreme, energy-wasting levels.

Verdant-VX-T6-KT-Energy-Management-Thermostat-fig.1

Control Card Installation – Wiring Table

Wiring Table – 24V AC

Wire Color Terminal Letter Terminal Connection
BLACK C COMMON
RED R 24V
YELLOW Y COMPRESSOR
WHITE W HEAT
ORANGE O OR B REVERSE VALVE
GREEN GH FAN HIGH
PURPLE GL FAN LOW
BROWN AUX OCCUPANCY OUT

Wiring Table – 24V DC

Wire Color Terminal Letter Terminal Connection
BLACK R 24V
RED C COMMON
YELLOW Y COMPRESSOR
WHITE W HEAT
ORANGE O OR B REVERSE VALVE
GREEN GH FAN HIGH
PURPLE GL FAN LOW
BROWN AUX OCCUPANCY OUT

Optional Wired Thermostat Installation

Wiring Table – 24V AC

Wire Color Terminal Letter Terminal Connection
BLACK C COMMON
RED R 24V

Wiring Table – 24V DC

Wire Color Terminal Letter Terminal Connection
BLACK R 24V
RED C COMMON
Case Dimensions (Imperial) 4.02 x 5.51” x 0.93” 3.875” x 2.125” x 0.75”
--- --- ---
Case Dimensions (Metric) 102mm x 140mm x 23.5mm 98mm x 54mm x 19mm
Screen Dimensions (Imperial) 3.63” x 2.13” N/A
Screen Dimensions (Metric) 92mm x 54mm N/A
Operating Voltage 3V DC – 2 “AA” Cell Batteries 24V AC/DC (HVAC Unit)
Control Outputs Fan High (GH)
Fan Low (GL)
Compressor (Y)
Heat Pump (OB)
Heat (W)
Occupancy Out (Aux)
Occupancy Sensor Beam Width ±47° (94°) N/A
Wireless Frequency 902-928MHz 902-928MHz
Temperature Accuracy ±1°F N/A
FCC ID XEYWX XEYV8ACCC
IC 8410A-WX 8410A-V8ACCC

FCC

THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS:

  1. THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND
  2. THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.

PURSUANT TO PART 15.21 OF THE FCC RULES, ANY CHANGES OR MODIFICATIONS TO THIS EQUIPMENT NOT EXPRESSLY APPROVED BY VERDANT ENVIRONMENTAL TECHNOLOGIES, INC. MAY VOID VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.

US PATENTS: 8,369,994; 8,141,791; 7,918,406; 7,841,542; 7,838,803; RE40,437; 7,232,075; 7,185,825; 7,156,318; 7,152,806; 7,145,110; 7,058,477; 7,050,026; 7,028,912; 6,902,117; 6,789,739; 6,786,421; 6,619,555; 6,581,846; 6,578,770; CANADIAN PATENTS: CA2615065; CA2633113; CA2633121; CA2633200; OTHER PATENTS PENDING.
Verdant Environmental Technologies, Inc. reserves the right to make changes, without notice, in design or components as progress in engineering and manufacturing methods may warrant. Product appearance may vary.
© Verdant Environmental Technologies, Inc. 2021

Requires a network access license for each thermostat (Part Number: XMF) and one “Online Connection Kit” (Part Number: OL-KT). Additional fees apply.
020421 Emerson is a trademark of Emerson Electric Co. ©2020 Emerson Climate Technologies, Inc. All rights reserved

Verdant VX-T6-KT Energy Management Thermostat Product Specifications Guide

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Verdant User Manuals

Related Manuals