Verdant VX-TW-HCR-B Wireless Room Thermostat
View all Verdant thermostat manual
INTRODUCTION
The Verdant VX Series Hilton Connected Room Thermostat allows guests to control temperature directly from the Hilton Honors app. An Integrated occupancy sensor allows for optional energy saving when rooms are unoccupied. A patented “Night Occupancy” feature ensures comfort while guests are sleeping. Fully confi gurable settings allow for customization of energy savings to fi t any situation.
- Temperature Setback automatically adjusts the temperature when rooms are unoccupied to save energy.
- Temperature Recovery allows for setting a maximum time permitted for establishing a comfortable room temperature.
- Setback Optimization monitors the temperature recovery rate and optimizes setback temperatures.
- Setback Limits control the maximum and minimum room temperature when a room is in setback mode.
- Set Point Limits prevent guests from setting the room temperature to extreme, energy-wasting levels.
SPECIFICATION
- Compatible with Hilton Connected Room
- Allows guests to control room temperature from Hilton Honors app.
- Uncompromising Guest Comfort
- Quick-and-Easy Installation
- Auxiliary output that allows for integration with make-up air units, lighting, and other devices.
- Connects to HVAC unit Wired or Wirelessly
- Powerful Energy Management Features
- Remote Management Capabilities
Control Card Installation – Wiring Table
Wiring Table – 24V AC
Wire Color | Terminal Letter | Terminal Connection |
---|---|---|
BLACK | C | COMMON |
RED | R | 24V |
YELLOW | Y | COMPRESSOR |
WHITE | W | HEAT |
ORANGE | O OR B | REVERSE VALVE |
GREEN | GH | FAN HIGH |
PURPLE | GL | FAN LOW |
BROWN | AUX | OCCUPANCY OUT |
Wiring Table – 24V DC
Wire Color | Terminal Letter | Terminal Connection |
---|---|---|
BLACK | R | 24V |
RED | C | COMMON |
YELLOW | Y | COMPRESSOR |
WHITE | W | HEAT |
ORANGE | O OR B | REVERSE VALVE |
GREEN | GH | FAN HIGH |
PURPLE | GL | FAN LOW |
BROWN | AUX | OCCUPANCY OUT |
Optional Wired Thermostat Installation
Wiring Table – 24V AC
Wire Color | Terminal Letter | Terminal Connection |
---|---|---|
BLACK | C | COMMON |
RED | R | 24V |
Wiring Table – 24V DC
Wire Color | Terminal Letter | Terminal Connection |
---|---|---|
BLACK | R | 24V |
RED | C | COMMON |
Case Dimensions (Imperial) | 4.02 x 5.51” x 0.93” | 3.875” x 2.125” x 0.75” |
--- | --- | --- |
Case Dimensions (Metric) | 102mm x 140mm x 23.5mm | 98mm x 54mm x 19mm |
Screen Dimensions (Imperial) | 3.63” x 2.13” | N/A |
Screen Dimensions (Metric) | 92mm x 54mm | N/A |
Operating Voltage | 3V DC – 2 “AA” Cell Batteries | 24V AC/DC (HVAC Unit) |
Control Outputs | Fan High (GH) | |
Fan Low (GL) | ||
Compressor (Y) | ||
Heat Pump (OB) | ||
Heat (W) | ||
Occupancy Out (Aux) | ||
Occupancy Sensor Beam Width | ±47° (94°) | N/A |
Wireless Frequency | 902-928MHz | 902-928MHz |
Temperature Accuracy | ±1°F | N/A |
FCC ID | XEYWX | XEYV8ACCC |
IC | 8410A-WX | 8410A-V8ACCC |
FCC
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS:
- THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND
- THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
PURSUANT TO PART 15.21 OF THE FCC RULES, ANY CHANGES OR MODIFICATIONS TO THIS EQUIPMENT NOT EXPRESSLY APPROVED BY VERDANT ENVIRONMENTAL TECHNOLOGIES, INC. MAY VOID VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT..
Verdant Environmental Technologies, Inc.
- 1850 55th Avenue, Montreal, QC, Canada, H8T 3J5
- TEL: 888.430.8539
- FAX: 514.344.5977
- EMAIL: hilton@verdant.info
- Requires an optional “Online Connection Kit” (Part Number: OL-KT). Additional fees apply.
Verdant VX-TW-HCR-B Wireless Room Thermostat Product Specifications Guide
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>