Verdant VX-TW-HCR-B Wireless Room Thermostat Product Specifications Guide

October 30, 2023
Verdant

Verdant VX-TW-HCR-B Wireless Room Thermostat

Verdant- VX-TW-HCR-B -Wireless- Room- Thermostat-PRO

View all Verdant thermostat manual

INTRODUCTION

The Verdant VX Series Hilton Connected Room Thermostat allows guests to control temperature directly from the Hilton Honors app. An Integrated occupancy sensor allows for optional energy saving when rooms are unoccupied. A patented “Night Occupancy” feature ensures comfort while guests are sleeping. Fully confi gurable settings allow for customization of energy savings to fi t any situation.

  • Temperature Setback automatically adjusts the temperature when rooms are unoccupied to save energy.
  • Temperature Recovery allows for setting a maximum time permitted for establishing a comfortable room temperature.
  • Setback Optimization monitors the temperature recovery rate and optimizes setback temperatures.
  • Setback Limits control the maximum and minimum room temperature when a room is in setback mode.
  • Set Point Limits prevent guests from setting the room temperature to extreme, energy-wasting levels.

Verdant- VX-TW-HCR-B- Wireless- Room- Thermostat-
FIG-1

SPECIFICATION

  • Compatible with Hilton Connected Room
  • Allows guests to control room temperature from Hilton Honors app.
  • Uncompromising Guest Comfort
  • Quick-and-Easy Installation
  • Auxiliary output that allows for integration with make-up air units, lighting, and other devices.
  • Connects to HVAC unit Wired or Wirelessly
  • Powerful Energy Management Features
  • Remote Management Capabilities

Control Card Installation – Wiring Table

Wiring Table – 24V AC

Wire Color Terminal Letter Terminal Connection
BLACK C COMMON
RED R 24V
YELLOW Y COMPRESSOR
WHITE W HEAT
ORANGE O OR B REVERSE VALVE
GREEN GH FAN HIGH
PURPLE GL FAN LOW
BROWN AUX OCCUPANCY OUT

Wiring Table – 24V DC

Wire Color Terminal Letter Terminal Connection
BLACK R 24V
RED C COMMON
YELLOW Y COMPRESSOR
WHITE W HEAT
ORANGE O OR B REVERSE VALVE
GREEN GH FAN HIGH
PURPLE GL FAN LOW
BROWN AUX OCCUPANCY OUT

Optional Wired Thermostat Installation

Wiring Table – 24V AC

Wire Color Terminal Letter Terminal Connection
BLACK C COMMON
RED R 24V

Wiring Table – 24V DC

Wire Color Terminal Letter Terminal Connection
BLACK R 24V
RED C COMMON
Case Dimensions (Imperial) 4.02 x 5.51” x 0.93” 3.875” x 2.125” x 0.75”
--- --- ---
Case Dimensions (Metric) 102mm x 140mm x 23.5mm 98mm x 54mm x 19mm
Screen Dimensions (Imperial) 3.63” x 2.13” N/A
Screen Dimensions (Metric) 92mm x 54mm N/A
Operating Voltage 3V DC – 2 “AA” Cell Batteries 24V AC/DC (HVAC Unit)
Control Outputs Fan High (GH)
Fan Low (GL)
Compressor (Y)
Heat Pump (OB)
Heat (W)
Occupancy Out (Aux)
Occupancy Sensor Beam Width ±47° (94°) N/A
Wireless Frequency 902-928MHz 902-928MHz
Temperature Accuracy ±1°F N/A
FCC ID XEYWX XEYV8ACCC
IC 8410A-WX 8410A-V8ACCC

FCC

THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS:

  • THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND
  • THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.

PURSUANT TO PART 15.21 OF THE FCC RULES, ANY CHANGES OR MODIFICATIONS TO THIS EQUIPMENT NOT EXPRESSLY APPROVED BY VERDANT ENVIRONMENTAL TECHNOLOGIES, INC. MAY VOID VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT..

Verdant Environmental Technologies, Inc.

  • 1850 55th Avenue, Montreal, QC, Canada, H8T 3J5
  • TEL: 888.430.8539
  • FAX: 514.344.5977
  • EMAIL: [email protected]
  • Requires an optional “Online Connection Kit” (Part Number: OL-KT). Additional fees apply.

Verdant VX-TW-HCR-B Wireless Room Thermostat Product Specifications Guide

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Verdant User Manuals

Related Manuals