Hyfire HFI-PA-05 Analogue Photo Detector User Manual
- October 30, 2023
- Hyfire
Table of Contents
HFI-PA -05
ANALOGUE PHOTO DETECTOR
ALTAIR SERIES
GENERAL DESCRIPTION
This type of detector (figure 1) continuously samples the air in the protected area to provide the earliest warning of fire, offering, at the same time, a high level of false alarm rejection.
The particular design of the smoke entry ports limits potential contamination,
extends maintenance periods and does not compromise smoke response
sensitivity.
These detectors are designed for an open area protection and must only be
connected to control panels that use the Altair analogue-intelligent
addressable communication protocol for monitoring and control, providing high
rates of information exchange and fast and secure responses.
Note: Before installing this device please thoroughly read this leaflet
and refer to the applicable European Standards and National Codes of Practice
(e.g. BS5839-1:2002 for UK) for guidance on location, spacing and acceptable
use. Also seek guidance from the compatible control panel instructions to
ensure appropriate design criteria and configuration specifications are
followed.
INSTALLATION
For the installation to the ceiling, the detector must be mounted only on the compatible adaptor bases listed in the “TECHNICAL SPECIFICATIONS” table. Refer to the specific base’s literature for further details.
WIRING
After having installed the base to the ceiling, wiring has to be carried out
in order to connect the base to the analogue loop and, so, to the
installation.
Analogue loop wires must be correctly connected to the base’s terminals: check
the performed wiring by referring to the figure 2 diagram.
REMOTE OUTPUT CAPABILITY
Remote output capability is available as a standard feature, so a remote indication lamp or a compatible platform sounder (check power requirements and loop drive limits) may be wired to the base terminals (Figure 3). If other equipment is connected to the remote output, its supply current must be eventually limited by using an adequate resistor. Consult the TECHNICAL SPECIFICATIONS table and assess the external device current absorption’s value.
SHORT CIRCUIT ISOLATORS
The detector is equipped with bi-directional short-circuit isolators to
help protect against wiring faults that may otherwise result in loop failure.
In the event of a short circuit isolators either side should open to maintain
most functions.
Normal operation can be restored after the fault has been corrected.
DEVICE PROGRAMMING – ADDRESS SETTING
Detectors can be addressed using a special hand-held programming unit or
they can be automatically addressed from the control panel (if this feature
exists for the model used) after they havebeen installed.
Addresses may be selected from a range from 1 to 240, although,of course, each
device on the loop must have a unique address.
DEVICE PROGRAMMING – SENSITIVITY SETTING
A choice of four sensitivity levels is available; if such feature is
provided, this level can be set through the control panel.
Level 1 is most sensitive and level 4 is the least sensitive.
DETECTOR PLACEMENT
- Position the detector centrally on its adaptor base ensuring it is level.
- Rotate clockwise applying gentle pressure. The detector will drop into its keyed location.
- Continue to rotate clockwise a few degrees until the detector has fully engaged in the adaptor base.
- When the detector is firmly engaged, check the alignment of the raised reference marks on the detector and on the base (figure 5).
IMPORTANT NOTES ON DETECTORS PLACEMENT
Disconnect loop power before installing the detector.
Dust covers help to protect the devices during shipping and when first
installed. They are not intended to provide complete protection against
contamination, therefore, detectors should be removed before construction,
major re-decoration or other dust producing work is started. Dust covers must
be removed before the system can be made operational.
ANTI -TAMPER DETECTOR LOCK
The detector can be locked to its base as a deterrent to intentional
removal performed by non authorized personnel.
Using a cutter, remove the anti-tamper plastic detail, as illustrated in
figure 6.
To unlock the detector, insert the tip of a screwdriver into the side slot of the base by exerting only a light pressure (figure 7), and release the detector by turning it anticlockwise.
LED INDICATORS
This detector is equipped with dual LEDs that can illuminate Green, Red or
Amber to indicatestatus condition:
Green: blinking, indicates the normal operative status of the detector.
Red: indicates an alarmed condition of the detector.
Amber: if implemented in panel software, indicates a fault condition of
the detector.
LED indicators are managed directly by the control panel and the green
blinking can be disabledby the installer either from the control panel itself
or through the programming unit.
Positioning of these LEDs is illustrated in figure 8.
IDENTIFICATION TAB
The adaptor base is equipped with a plastic tab where identification data can
be visibly displayed.
Detach the tab from the base; write or label it with the required information,
then insert it into its adaptor base’s slot.
TESTING THE DETECTORS – PRELIMINARY NOTE
Detectors should be tested after installation and during periodic
maintenance visits; it is recommended each device should be tested at least
once per year.
After each test reset the system and allow at least one minute for power
stabilisation.
MAGNET TEST
Position the test magnet next to the detector, in correspondence of the
raised mark, then move it 45 degrees anticlockwise (figure 10).
The magnet test simulates smoke in the optical chamber and verifies the function of all electronic circuits of the detector and its communication with the control panel. The detector should trigger an alarm message to the control panel, and, successively, the detector’s red LED should be activated by the control panel itself.
AEROSOL TEST (SIMULATED SMOKE TEST)
For this test only use test aerosols from an approved manufacturer, in
accordance with their application instructions, in order to prevent
contamination or possible damage to the detector. We suggest to spray the
aerosol into the detector by using a recommended applicator. The detector
should trigger an alarm message to the control panel, and, successively, the
detector ’s red LED should be activated by the control panel itself.
If the detector does not respond to the tests correctly it may be necessary to
clean it: in this case follow the instructions indicated in the “MAINTENANCE”
paragraph.
If testing fails again after maintenance then replace the detector with a new
one and return the faulty one for servicing.
MAINTENANCE
Before starting any maintenance work, isolate and disable the system in order
to avoid accidental and unwanted alarm or fault conditions.
Remove the detector from its mounting base to allow inspection in good light
at ground level. Inspect the smoke entry ports around the detector and use a
small, soft bristle brush to dislodge any evident contaminants such as
insects, spider webs, hairs, etc. Use a small vacuum tube or clean, dry and
compressed air to suck up or blow away any remaining small particles from the
smoke entry screen area. Wipe the exterior housing of the detector with a
clean, damp, lint free cloth to remove any surface film that can later attract
airborne contaminants. Use the hand-held programming unit to read the
pollution percentage of the chamber; please, refer to the programming unit
instruction manual.
After all detectors have been inspected, repositioned on their mounting bases
and power has been re-applied, check correct operation by testing the device.
TECHNICAL SPECIFICATIONS **
Power supply * | from 18 V (min) to 40 V (max) |
---|---|
Average standby current consumption | 55 uA @ 24 V |
Remote output max current consumption (externally limited) | 20 mA |
Compatible adaptor bases | HFI-DMBS-05 – “Low Profile Adaptor Base” |
Operating temperature range | -30 °C / +70 °C (no icing) |
Humidity | 95% RH (no condensation) |
IP rating | 40 (42 with base’s waterproof protection) |
*Product operates down to 15 V, but without LED indication.
**Check latest version of document TDS-A1000 for further data, obtainable from
your supplier.
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that
are highly resistant to environmental deterioration. However, after 10 years
of continuous operation, it is advisable to replace the devices in order to
minimize the risk of reduced performance caused by external factors. Ensure
that this device is only used with compatible control panels. Detection
systems must be checked, serviced and maintained on a regular basis to confirm
correct operation.
Smoke detectors may respond differently to various kinds of smoke particles,
thus application advice should be sought for special risks. Detectors cannot
respond correctly if barriers exist between them and the fire location and may
be affected by special environmental conditions.
Refer to and follow national codes of practice and other internationally
recognized fire engineering standards. Appropriate risk assessment should be
carried out initially to determine correct design criteria and updated
periodically.
WARRANTY
All devices are supplied with the benefit of a limited 5 years warranty
relating to faultymaterials or manufacturing defects, effective from the
production date indicated on eachproduct.
This warranty is invalidated by mechanical or electrical damage caused in the
field byincorrect handling or usage.
Product must be returned via your authorized supplier for repair or
replacement togetherwith full information on any problem identified.
Full details on our warranty and product’s returns policy can be obtained upon
request.
Hyfire Wireless Fire Solutions Limited – Unit
B12a, Holly Farm Business Park, Honiley,
Warwickshire, CV8 1NP – United Kingdom
www.hyfirewireless.com
info@hyfirewireless.co.uk
L20-A1000-1400 (vA.7)
EN 54-7:2018
EN 54-17:2005
HFI-PA-05
For use in compatible fire detection and alarm system