WATTS 70608 Gas Filter for Wall Boilers Instruction Manual
- June 4, 2024
- WATTS
Table of Contents
WATTS 70608 Gas Filter for Wall Boilers
Installation
- This filter, by reason of its limited dimensions, is particularly suitable for installation on boilers (fixed to wall or ground) and water heaters (instant or storage models).
- Check that the filter suits the proper use and that all technical data are not exceeded.
- Do not install the filter on plastered walls.
- To install the filter use suitable tools and operate on the threading hubs.
- Assemble the filter in such a way that the cover can be easily removed for inspection or cleaning.
- Ensure that the gas flow direction is that indicated on the filter.
- It can be assembled both on horizontal and vertical piping.
Maintenance
- Change the filter element when Δp between the pressure taps connections exceeds 10 mbar; anyway it is recommended to replace the filter element at least once a year.
- To replace the filter element you need to:
- cut off the gas flow by closing the cut off cock;
- unscrew the screws and remove the cover;
- remove the filter element and clean the filter housing carefully;
- replace the old filter element with a new one;
- reassemble the filter cover ensuring that the guides inside the cover are aligned with the filter element and then tight the screws again;
- check for any gas leak from the filter cover.
Technical Specifications
- Threaded connections: Rp UNI EN 10226-1
- Maximun inlet pressure: 0.5 bar
- Filtration degree: ≤ 50 µm
- Working temperature: -20°C÷+80°C
- Mechanical strength: according to UNI-EN 13611 (group 1)
- Materials: body in aluminium; cover in galvanized steel; filter element with long-life Viledon P15/500S panels with remarkable dust absorption in according to UNI EN ISO 16890 specifications; cage for filters in synthetic material; NBR cover o-ring.
- Fuels: gas of the following groups: manufactured gases (town gas); natural gases (group H – methane); liquid petrol gas (lpg); nonaggressive gases
The descriptions and photographs contained in this product specification sheet are supplied by way of information only and are not binding. Watts Industries reserves the right to carry out any technical and design improvements to its products without prior notice. Warranty: All sales and contracts for sale are expressly conditioned on the buyer’s assent to Watts terms and conditions found on its website at www.wattswater.eu Watts hereby objects to any term, different from or additional to Watts terms, contained in any buyer communication in any form, unless agreed to in a writing signed by an officer of Watts
DIAGRAM OF FLOW RATES
- Natural gas
- Town gas
- AIR
- LPG
Guarantee
Watts products are thoroughly tested. The said guarantee covers solely
replacement or – at the full sole discretion of WATTS – repair, free of
charge, of those components of the goods supplied which in the sole view of
Watts present proven manufacturing defects. The period of limitation for
claims based on defects and defects in title is two years from delivery/the
passage of risk. This warranty excludes any damage due to normal product usage
or friction and does not include any modified or unauthorized repair for which
Watts will not accept any request for damage (either direct or indirect)
compensation (for full details see our website). All sales subject to the
Watts terms to be found on www.wattswater.eu
References
- ter.it
- Home | Watts Europe
- Инженерная сантехника Watts: системы отопления, системы водоснабжения и водоподготовки для жилых, коммерческих и общественных зданий.
- Watts Industries Deutschland GmbH
- Allgemeine Geschäftsbedingungen | Watts Industries Deutschland GmbH
- Home | Watts Europe
- Watts Industries Italia S.r.l. | Watts Water Technologies.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>