FIREBIRD Lowara Electronic Circulation Pumps User Guide

October 30, 2023
Firebird

FIREBIRD Lowara Electronic Circulation Pumps

Firebird Pump Setting Guide

The Firebird NZ boilers come with Lowara electronic circulation pumps that use less energy than the previous series of pumps. These pumps have three modes that can be selected during commissioning.

Purging Mode

When the boiler is first installed, the pump can be set on the ‘start’/’mode select’ position, and the LED will blink white while this mode is active. Use this mode to purge the system and remove air from the system and boiler.

Manual Constant Speed Mode

In this mode, the LED will be solid white. If the light is blue, turn the dial back to the mode select position and then to the desired setting. This mode is similar to older style 3-speed circulation pumps and is recommended for most applications. For most applications, a pump pressure of 30-40kPa will be sufficient.

Recommended settings by boiler capacity:

Boiler Capacity Pump Pressure
20-26kW 35kPa
35-44kW 40kPa
58-70kW 45kPa

Variable Pressure Mode

In this mode, the LED will be illuminated blue. If the LED is white, turn the dial back to the mode select position and then to the desired pump setting. In this mode, the pump detects changes in the system (e.g., closing of radiator TRVs) and reduces the pump pressure. This mode is suggested for radiator systems where it is likely that only a few radiators will be open in some situations or where the client has complained about noise from some radiators.

Recommended settings by boiler capacity

Boiler Capacity Pump Pressure
20-26kW 35-45kPa
35-44kW 40-50kPa
58-70kW 45-55kPa

If you have any questions or concerns, please contact us at 0800 357 1233 or email us at [email protected]. You can also visit our website at trade. central heating.co.nz.

Product Usage Instructions

  1. When installing a new Firebird NZ boiler, set the pump on the ‘start’/’mode select’ position to activate the purging mode. Use this mode to remove air from the system and boiler.
  2. Once the system has been purged, switch to manual constant speed mode by turning the dial to the desired setting. For most applications, a pump pressure of 30-40kPa will be sufficient. Refer to the recommended settings by boiler capacity table for specific settings.
  3. If you have a radiator system where only a few radiators will be open in some situations or where the client has complained about noise from some radiators, switch to variable pressure mode by turning the dial to the desired setting. In this mode, the pump detects changes in the system and reduces the pump pressure accordingly. Refer to the recommended settings by boiler capacity table for specific settings.
  4. If you need further assistance, please contact us at 0800 357 1233 or email us at [email protected]. You can also visit our website at trade.centralheating.co.nz.

Firebird Pump Setting Guide

Firebirds new NZ boilers are supplied with Lowara electronic circulation pumps, these pumps use lower energy than the previous series of pump and have 3 modes than can be selected during commissioning.

Purging Mode
When the boiler is first installed the pump can be set on the ‘start’ / ’mode select’ position and the led will blink white while this mode is active. Use this mode while purging the system to help remove air from the system and boiler.

Manual Constant Speed Mode
In this mode the LED will be solid white, if the light is blue turn the dial back to the mode select position and then to the desired setting. This mode is similar to older style 3 speed circulation pumps and is recommended for most applications.

For most applications a pump pressure of 30-40kPa will be sufficient, please see below recommended settings by boiler capacity:

  • 20kW = 4-5
  • 26kW = 5-6
  • 35kW = 6-7

Variable Pressure Mode

In this mode the LED will be illuminated blue, if the LED is white turn the dial back to the mode select position and then to the desired pump setting. In this mode the pump detects changes in the system (e.g. closing of radiator TRV’s) and reduces the pump pressure. This mode is suggested for radiator systems where it is likely only a few radiators will be open in some situations or where the client has complained about noise from some radiators.
For most applications a pump pressure of 30-40kPa will be sufficient, please see below recommended settings by boiler capacity:

  • 20kW = 4-5
  • 26kW = 5-6
  • 35kW = 6-7

0800 357 1233 | [email protected] | trade.centralheating.co.nz

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Firebird User Manuals

Related Manuals