BALBOA BP7 Series Control System Instruction Manual
- June 10, 2024
- BALBOA
Table of Contents
- IMPORTANT SAFETY INSTRUCTIONS
- Electrical Installation
- GFCI Wiring Detail
- Power Connection
- Pump Cord Connections
- SPASIDE CONTROL INSTALLATION
- WIFI MODULE INSTALLATION KIT (OPTIONAL)
- AUXILIARY PANEL OPTIONS
- Circuit Board Configurations
- Wiring Diagram
- SYSTEM SETUP & CONNECTION CHART
- TP600 / TP400 / TP200 Programming Procedure
- TP500/TP500S Programming Procedure
- TP800 / TP900 / spaTouch™ Menued Panel Programming Procedure
- System Start-Up
- Operation Considerations
- System Functions / Features
- System Plug Pinouts
- Testing / Replacing the Sensor Set
- Troubleshooting
- System Data Label
- Warranty Information
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Operation Manual
BALBOA ® BP SERIES
ByHYDRO QUIP™
IMPORTANT SAFETY INSTRUCTIONS
! DANGER To reduce the risk of injury, do not permit children to use this
product unless they are closely supervised at all times.
! WARNING – RISK OF CHILD DROWNING. Extreme caution must be exercised o
prevent unauthorized access by children. To avoid accidents, ensure that
children cannot use a spa or hot tub unless they are supervised at all times.
! DANGER To reduce the risk of injury to persons, do not remove suction
fittings.
Spa location must accommodate sufficient drainage of water around the base of
the structure, as well as the power source compartment.
Prolonged immersion in water that is warmer than normal body temperature can
result in a dangerous condition known as HYPERTHERMIA. The causes, symptoms,
and effects of hyperthermia may be described as follows: Hyperthermia occurs
when the internal temperature of the body reaches a level several degrees
above the normal body temperature of 98.6BF. The symptoms of hyperthermia
include dizziness, fainting, drowsiness, lethargy, and an increase in the
internal temperature of the body. The effects of hyperthermia include
- unawareness of impending hazard,
- failure to perceive heat,
- failure to recognize the need to exit spa,
- physical inability to exit spa,
- fetal damage in pregnant women,
- unconsciousness resulting in danger of drowning.
WARNING The use of alcohol, drugs or medication can greatly increase the
risk of fatal hyperthermia in hot tubs and spas.
! DANGER – RISK OF ELECTRICAL SHOCK.
A spa may be installed within 5 feet of metal surfaces if each metal surface
is permanently connected by a solid copper conductor attached to the wire
connector on the terminal box . Refer to NEC and local codes in effect at the
time of installation.)
A bonding lug is provided on the control box to permit connection of a solid
copper bonding conductor between this point and any equipment, metal
enclosures of electrical equipment, metal water pipe, or conduit within 5
feet(1.5m) of the unit as needed to comply with local requirements.
Bond accessible metal to the dedicated connector on the equipment grounding
bus, bond the equipment ground bus to the local common bonding grid as part of
the installation in the form of (1) a reinforced concrete slab for support,
(2) a ground plate provided beneath the hot tub or spa, or (3) a permanent
ground connection that is acceptable to the local inspection authority.
! DANGER RISK OF ELECTRICAL SHOCK. Do not permit any electrical appliance,
such as a light, telephone, radio, or television, within 5 feet (1.5m) of a
spa or hot tub.
To reduce the risk of injury:
The water in a spa or hot tub should never exceed 104BF (40BC). Water
temperatures between 100BF (38BC) and 104BF (40BC) are considered safe for a
healthy adult. Lower water temperatures are recommended for extended use
(exceeding 10-15 minutes) and for young children.
Excessive water temperatures have a high potential for causing fetal damage
during the early months of pregnancy, pregnant or possibly pregnant women
should limit spa or hot tub water temperatures to 100BF(38BC). Before entering
the spa or hot tub, the user should measure the water temperature with an
accurate thermometer.
The use of alcohol, drugs, or medication before or during spa or hot tub use
may lead to unconsciousness with the possibility of drowning. Persons
suffering from obesity or with a medical history of heart disease, low or high
blood pressure, circulatory system problems, or diabetes should consult a
physician before using a spa or hot tub.
IMPORTANT SAFETY INSTRUCTIONS
Persons using medication should consult a physician before using a spa or hot
tub since some medication may affect heart rate, blood pressure, and
circulation.
For Cord and Plug Connected Units
Must be connected to a grounded, grounding type receptacle only. NEVER connect
the spa to an extension cord. Do not bury the cord.
For Permanently Installed Units
A terminal marked “G” or “ground” is provided in the wiring box located inside
the equipment compartment. To reduce the risk of electric shock, connect the
terminal or connector to the grounding terminal of your electrical service or
supply panel with a continuous green insulated copper wire in accordance with
National Electric Code Table 250-95 and any other local codes in effect at the
time of the installation.
For Permanently Installed Units not Provided with an Internal Disconnecting
Method
The electrical supply for this product must include a suitably rated switch or
circuit breaker to open all ungrounded supply conductors to comply with
Section 422-30 of the National Electric Code, ANSI/NFPA 70 1987. The
disconnecting means must be readily accessible to the tub occupant but
installed at least 5 feet (1.5m) from the tub water.
For Units with Gas Heaters
WARNING – Do not install indoors. This unit uses a gas heater that requires
proper ventilation and is intended for outdoor use only.
High Voltage Warning HIGH VOLTAGE CAN SERIOUSLY INJURE OR KILL! ONLY
EXPERIENCED TECHNICIANS SHOULD SERVICE THIS EQUIPMENT.DO NOT remove the
protective covers from any electrical enclosure, or attempt to service any
related electrical device, unless you are a qualified electrician or service
professional.
DANGER
Risk of electric shock. Before working with any electrical connections, make
certain that the Main Power breaker from the house breaker box has been turned
off.
WARNING
All electrical work must be performed by a qualified electrician and must
conform to all local codes.
IMPORTANT
Due to the danger of severe electrical shock, locate all power disconnects
before servicing a spa. Precautions must be taken whenever working with
breaker boxes, G.F.C.I.’s, or service disconnects
Electrical Installation
A licensed electrician must accomplish the electrical installation in
accordance with the National Electric Code(NEC) Article 680, and any local
codes in effect at the time of installation.
Refer to the System Data Label for equipment voltage and maximum amperage
draws. The GFCI (Ground Fault Circuit Interrupter) is a mandatory electrical
safety device required for all portable spas and hot tubs as specified in the
National Electrical
Code Article 680-42. The GFCI in your particular installation may be installed
at the electrical service panel or a separate sub-panel.
Use copper conductors ONLY. The ground must be sized following the National
Electric Code, Table 250-122. For Power conductor size, refer to the
NationalElectric Code Table 310-16.
A bonding lug has been provided on the control box to allow connection to
local ground points. To reduce the risk of electrical shock, a solid copper
bonding wire should be connected from this lug to any metal objects within 5
feet of the spa.
The NEC and most local codes require that a “disconnect” be installed within
“line-of-site” of the spa.
Circuit & Breaker
Rating| 15A| 20A| 30A| 40A| 50A| 60A
---|---|---|---|---|---|---
aximum Amps| 12A| 16A| 24A| 32A| 40A| 48A
Minimum WireSize| 14| 12| 10| 8| 6| 4
The above table is a wiring chart representation.
IMPORTANT – If your electrician is not absolutely sure how to connect
your system correctly, call your local dealer. Any mistake may be costly and
void your equipment warranty.
CAUTION : Do not connect or disconnect any components while the power is
on.
All connections must be done with the power off as it may cause damage to the
system.
Any resulting damages are not covered under manufacturer’s warranty **
CAUTION: Damage may occur to the circuit board and spaside if the spaside
plug is not properly aligned to the receptacle on the circuit board or if the
spaside plug is connected or disconnected while the power is on.
Any resulting damages are not covered under manufacturer’s warranty **
Electrical Installation
OPTION 1
ELECTRICAL CONNECTIONS GFCI Installed in Main Service Panel
20-60AMP HARDWIRED
Option 1 shows the power from GFCI breaker installed into main service panel to a service disconnect within line-of-site of the spa. If the manufacturer of your homes main breaker panel makes a GFCI breaker, you may be able to add it to an open slot in the panel.
OPTION 2
Option 2 shows the power from main service panel to a GFCI subpanel within line-of-site of the spa. (Note: Most local codes will allow a GFCI subpanel to be a disconnect. If this is not the case in your installation, a disconnect must be provided.)
If your system was configured to include a 120VAC power cord, ensure that the
proper receptacle has been installed (a dedicated circuit is required). DO NOT
under any circumstances modify a 20 Amp plug to fit into a 15 Amp receptacle
or use an extension
cord. Doing so will create hazardous conditions and/or invalidate the
warranty.
OPTION 3
Units with 15A / 20A GFCI Plug Connection
15/20AMP CORD END GFCI
GFCI Wiring Detail
It is important that the GFCI circuit breaker is installed correctly. Often
this component has been improperly installed causing the breaker to instantly
trip when the system is turned on. Below is an illustration of a typical GFCI
breaker installation.
WARNING: Refer to the circuit breaker manufacturers installation
instructions. This illustration is meant to be a guide for Field Technicians
and is not intended to override or substitute the instructions supplied with
the circuit breaker.
Power Connection
IMPORTANT: Always refer to the product data label (located on top of the control box) for specific electrical information.
- Use copper conductors only as required by the NEC.
- Secure wires as defined by the NEC and in compliance with any local codes in effect at the time of installation.
If supply circuit allows move DIP switches A2 & A3 to the on or up position to place the system in high amp mode. High amp mode allows the heater to stay on when high speed pump(s) or blower is turned on.
120-VOLT ELECTRICAL SERVICE REQUIREMENTS**
Step 1: Convert transformer to allow 120V input by installing an additional
jumper (sold separately) at J24 located above the transformer
**NOTE: 120V JUMPER HQ PT#: 34-20564
Pump Cord Connections
2-SPEED PUMP CORD CONFIGURATION
The following wiring configuration is for two-speed pump circuits.
SINGLE SPEED PUMP / ACCESSORY CORD CONFIGURATION
The following wiring configuration is for single-speed pump circuits,
circulation pumps, ozones, blowers and accessories.
SPASIDE CONTROL INSTALLATION
If required, you may have to cut out a hole in the spa shell to install spaside control.
- The mounting area must be above the maximum water level of the spa and in an area with good drainage to prevent any standing water on or around the spaside.
- The spaside should never be submerged.
- The spaside should be protected from extended periods of exposure to sunlight.
- Do not step or stand on the spaside
Step 1 – Clean area and insert spaside control. (Fig.1)
Step 2 – Remove the double sided adhesive from the back of the spaside. Make certain the spaside is straight and adhere to the spa shell. (Fig.2)
Step 3 – Remove protective film from display window then clean the face of the spaside. Now carefully align and apply the label. (Fig.3)
Step 4 – Connect spaside to an empty connection marked MAIN. (Fig.4)
CONNECTING SPASIDE & EXTENSION
*Must align Locking Clip on spaside plug with Locking Tab on circuit board for proper function.
When utilizing a spaside extension cord, the clip and tab must also be aligned
at all connections. Fig.5
Cord plugs are labeled to insure proper plug alignment as shown in Fig.6
CAUTION: Damage may occur to the circuit board and spaside if the spaside
plug is not properly aligned to the receptacle on the circuit board or if the
spaside plug is connected or disconnected while the power is on.
Any resulting damages are not covered under manufacturer’s warranty ****
WIFI MODULE INSTALLATION KIT (OPTIONAL)
Your new system has the capability to connect with the internet using a wifi
module.
If Provided with your system, please make sure to install the module following
these few steps:
Step 1 – Insert wifi cable connector into an empty connection mark “Main”
* If no
main connections are available, you may use the “Y” cable provided with the
wi-fi module kit (34-51159-K)
Step 2 – You may mount the wifi module inside the lower control system
enclosure.
Step 3 – Please follow the instructions provided with the wifi module kit
to properly install your BWA App ™
Note: If you experience poor operation via the wifi module, it may be
necessary to relocate the module closer to your wifi router.
AUXILIARY PANEL OPTIONS
Circuit Board Configurations
All component outputs are pre-configured for 240V. If 120V output is required,
please utilize the illustration below and the wiring diagram that was included
with your unit for the correct component location to properly convert to 120V.
Component | Volts | Amps | From | To |
---|---|---|---|---|
P1 1 or 2-spd | 120V | 12A | Area 2 | Area 4 |
P2, P3, P4, BL | 120V | 10A | Area 2 | Area 4 |
Ozone | 120V | 1A | Area 2 | Area 4 |
Circ Pump | 120V | 2A | Area 2 | Area 4 |
AV | 120V | 2A | Area 2 | Area 4 |
Expander Board (Optional)
Wiring Diagram
SYSTEM SETUP & CONNECTION CHART
Setup #| Circ Pump| Pump 1| Pump 2| Pump 3| Pump 4| Blower| MicroSilk®| Temp
Scale
---|---|---|---|---|---|---|---|---
1| Yes (321)| J9 (2-Spd)| 31 (2-Spd)| None| None| 314 (1-Spd)| None| °F
2| Yes (J21)| J9 (2-Spd)| 31 (1-Spd)| None| None| 314 (1-Spd)| None| °F
3| Yes (J21)| J9 (1-Spd)| 31 (1-Spd)| None| None| 314 (1-Spd)| None| °F
4| Yes (J21)| J9 (2-Spd)| None| None| None| 314 (1-Spd)| None| °F
5| Yes (J21)| J9 (1-Spd)| None| None| None| 314 (1-Spd)| None| °F
6| None| J9 (2-Spd)| 31 (2-Spd)| None| None| 314 (1-Spd)| None| °F
7| None| J9 (2-Spd)| 31 (1-Spd)| None| None| 314 (1-Spd)| None| °F
8| None| J9 (2-Spd)| None| None| None| J14 (1-Spd)| None| °F
9| Yes (J21)| J9 (2-Spd)| 31 (2-Spd)| J14 (1-Spd)| None| None| None| °F
10| Yes (J21)| J9 (2-Spd)| 31 (1-Spd)| 314 (1-Spd)| None| None| None| °F
11| Yes (J21)| J9 (1-Spd)| 31 (1-Spd)| 314 (1-Spd)| None| None| None| °F
12| Yes (J21)| J9 (2-Spd)| 31 (2-Spd)| None| None| None| None| of
13| Yes (J21)| J9 (2-Spd)| 31 (1-Spd)| None| None| None| None| °F
14| Yes (J21)| J9 (1-Spd)| 31 (1-Spd)| None| None| None| None| °F
15| Yes (J21)| J9 (2-Spd)| None| None| None| None| None| °F
16| Yes (J21)| J9 (1-Spd)| None| None| None| None| None| °F
J1 = Receptacle on expander board
NOTE: Component operation dependent on number of pump & accessory buttons
on keypad.
SYSTEM SETUP & CONNECTION CHART (cont)
Setup U| Circ Pump| Pump 1| Pump 2| Pump 3| Pump 4| Blower| MicroS8109| Temp
Scale
---|---|---|---|---|---|---|---|---
17| None| 39 (2-Spd)| J1 (2-Spd)| J14 (1-Spd)| None| None| None| °F
18| None| 39 (2-Spd)| 31 (1-Spd)| J14 (1-Spd)| None| None| None| °F
19| None| 39 (2-Spd)| 31 (2-Spd)| None| None| None| None| °F
20| None| 39 (2-Spd)| 31 (1-Spd)| None| None| None| None| °F
21| None| 39 (2-Spd)| None| None| None| None| None| °F
22| Yes (321)| 39 (2-Spd)| 31 (2-Spd)| None| None| None| 314 (1-Spd)| °F
23| Yes (321)| 39 (2-Spd)| 31 (1-Spd)| None| None| None| 314 (1-Spd)| °F
24| Yes (321)| 39 (1-Spd)| J1 (1-Spd)| None| None| None| 314 (1-Spd)| °F
25| Yes (321)| 39 (2-Spd)| None| None| None| None| 314 (1-Spd)| °F
26| Yes (321)| 39 (1-Spd)| None| None| None| None| 314 (1-Spd)| °F
27| None| 39 (2-Spd)| 31 (2-Spd)| None| None| None| 314 (1-Spd)| °F
28| None| 39 (2-Spd)| 31 (1-Spd)| None| None| None| 314 (1-Spd)| °F
29| None| 39 (2-Spd)| None| None| None| None| 314 (1-Spd)| °F
30*| Yes (321)| 39 (2-Spd)| 31 (1-Spd)| J14 (1-Spd)| 31 (1-Spd)| None| None|
°F
31•| Yes (321)| 39 (1-Spd)| 31 (1-Spd)| J14 (1-Spd)| 31 (1-Spd)| None| None|
°F
32•| None| 39 (2-Spd)| 31 (1-Spd)| J14 (1-Spd)| 31 (1-Spd)| None| None| °F
- = Setups 30-32 require splitter harness PT# 25801 for pumps 2 & 4 @ J1 expander connection
J1 = Receptacle on expander board
NOTE: Component operation dependent on number of pump & accessory buttons on keypad.
TP600 / TP400 / TP200 Programming Procedure
Test Menu Access (S1, Switch 1 ON) Service Technician ONLY.
With system on or OFF move DIP Switch 1 (on S1 on the Main circuit board) to
ON.
The system will enter Test Mode.
Moving DIP Switch 1 to OFF will exit Test Mode.
Software Setups
Under the TEST Menu, the Setup screen will allow changing the Setup from 1 to
any number established by the Manufacturer. Changing the Setup may require
wiring changes as well.
You will have 1 minute to complete the setup change after you manually exit
Priming Mode. (Once familiar with the process, the Setup change should take
less than 15 seconds.)
Immediately after exiting Priming Mode, press this sequence of buttons: Warm,
Light, Warm, Warm, Warm, Warm. Continue to press Warm until the diplay shows
the Setup Number (S-01, S-02, etc.) you want to switch to. When the correct
setup number is showing, press Light once, and the system will reset, using
the newly-selected Setup from that point on. Move DIP Switch 1 to the OFF
position to take the spa out of Test Mode. °F or °C will replace °T.
NOTE: Changing the Setup may require wiring changes as well – refer to
the wiring diagram or wiring diagram addendum.
TP500/TP500S Programming Procedure
Test Menu Access (S1, Switch 1 ON) Service Technician ONLY.
With system on or OFF move DIP Switch 1 (on S1 on the Main circuit board) to
ON.
The system will enter Test Mode.
Moving DIP Switch 1 to OFF will exit Test Mode.
Software Setups
Under the TEST Menu, the Setup screen will allow changing the Setup from 1 to
any number established by the Manufacturer.
Changing the Setup may require wiring changes as well.
You will have 1 minute to complete the setup change after you manually exit
Priming Mode. (Once familiar with the process, the Setup change should take
less than 15 seconds.)
NOTE: Changing the Setup may require wiring changes as well – refer to
the wiring diagram or wiring diagram addendum.
If the
Control Panel does not have a Warm (Up) button, but rather a single Temp
button, use the Temp button in place assumes a single Temperature Button.) of
the Warm button in the instruction above. (The flow chart
TP800 / TP900 / spaTouch™ Menued Panel Programming Procedure
Test Menu Access (S1, Switch 1 ON) Service Technician ONLY.
DANGER! HIGH VOLTAGE WILL BE ACCESSIBLE! SERVICE TECHNICIAN ONLY!
While the system is running, move DIP Switch 1 (on S1 on the Main circuit
board) to ON.
The system will enter Test Mode.
Moving DIP Switch 1 to OFF will exit Test Mode.
Software Setups
Under the TEST Menu, the Setup screen will allow changing the Setup from 1 to
any number established by the Manufacturer. Changing the Setup may require
wiring changes as well.
spaTouch™
Icon-Driven Panels Programming Procedure
Test Menu Access (S1, Switch 1 ON) Service Technician ONLY.
DANGER! HIGH VOLTAGE WILL BE ACCESSIBLE! SERVICE TECHNICIAN ONLY!
While the system is running, move DIP Switch 1 (on S1 on the Main circuit
board) to ON.
The system will enter Test Mode.
Moving DIP Switch 1 to OFF will exit Test Mod
As soon as Switch #1 is placed in the ON position, the temperature will show
10 “T” after it instead of F or C, indicating the System is in Test Mode een.
To Change Software Setups :
While in Test Mode, press the indicated icons to move from screen to screen.
As soon as Switch #1 is placed in the ON position, the temperature will show “T” after it instead of F or C, indicating the System is in Test Mode
Once on the Setup Selection screen, press the Up or Down icon to select the
desired Setup Number, then press the Check Mark icon to confirm and to have the
spa restart.
After the system restarts, you may see a message that “The settings have been
reset”; this is normal after changing Setups with DIP Switch 6 in the OFF
position. Press “Clear” to dismiss this message.
The example screens shown here are from the spaTouch 1 Icon-Driven Panel, but
the screens on the spaTouch 2 Panel are similar. The main difference is that
the spaTouch 2 display is wider.
System Start-Up
Preparation and Filling Fill the spa to its correct operating level. Be sure
to open all valves and jets in the plumbing system before filling to allow as
much air as possible to escape from the plumbing and the control system during
the filling process. After turning the power on at the main power panel, the
top-side panel display will go through specific sequences. These sequences are
normal and display a variety of information regarding the configuration of the
hot tub control.
Priming Mode
This mode will last for 4-5 minutes or you can manually exit the priming mode
after the pump(s) have primed. Regardless of whether the priming mode ends
automatically or you manually exit the priming mode, the system will
automatically return to normal heating and filtering at the end of the priming
mode. During the priming mode, the heater is disabled to allow the priming
process to be completed without the possibility of energizing the heater under
low-flow or no-flow conditions. Nothing comes on automatically, but the pump(s)
can be energized by pushing the “Jet” buttons. If the spa has a Circ Pump, it
can be activated by pressing the “Light” button during Priming Mode. Priming
the Pumps As soon as the priming mode has started, push the “Jet” button once
to start Pump 1 in low-speed and then again to switch to high-speed. Also,
push the Pump 2 or “Aux” button, if you have a 2nd pump, to turn it on. The
pumps will now be running in high-speed to facilitate priming. If the pumps
have not primed after 2 minutes, and water is not flowing from the jets in the
spa, do not allow the pumps to continue to run. Turn off the pumps and repeat
the process.
Note: Turning the power off and back on again will initiate a new pump
priming session. Sometimes momentarily turning the pump off and on will help it
to prime. Do not do this more than 5 times. If the pump(s) will not prime,
shut off the power to the spa and call for service. Important: A pump should
not be allowed to run without priming for more than 2 minutes. Under NO
circumstances should a pump be allowed to run without priming beyond the end
of the 4-5 minute priming mode. Doing so may cause damage to the pump and
cause the system to energize the heater and go into an overheat condition.
Exiting Priming Mode
You can manually exit Priming Mode by pressing a “Temp” button (Up or Down).
Note that if you do not manually exit the priming mode as described above, the
priming mode will be automatically terminated after 4-5 minutes. Be sure that
the pump(s) have been primed by this time. Once the system has exited Priming
Mode, the top-side panel will momentarily display the set temperature but the
display will not show the temperature yet, as shown below. This is because the
system requires approximately 1 minute of water flowing through the heater to
determine the water temperature and display it.
Operation Considerations
The following describes situations you may encounter and situations to be aware of.
Warm Weather Conditions
Since your spa will normally be expected to maintain warm to hot water ready
for use, a great deal of attention has been directed to the energy
conservation detail of insulation to keep electrical cost down. Energy
conservation efficiency may be achieved by extensive insulation of the spa
cabinet, plumbing, WARM WEATHER CONDITIONS spa shell and in some climates full
foam insulation may have been provided. This energy conservation feature may
cause an inconvenience during warmer times of the year. During warm periods of
the year, the temperature within the equipment compartment can elevate to a
point that the pump will automatically turn off for a short amount of time
(15-30 minutes) to allow the pump to cool down before automatically
restarting. This cool down feature will not harm your spa, but serves only to
protect the pump from damage ad as and indicator that it is too hot. To
minimize this occurrence, refrain from using your Hydrotherapy Jets for
prolonged periods of time during warm seasons. The jet pump chosen for your
spa has been specifically sized for maximum performance and your Hydrotherapy
enjoyment.
Filtration System
Please refer to your Spa Manufactures Owner’s Manual regarding the operation,
maintenance and cleaning of your filtration system.
IMPORTANT – Heater pump must provide a minimum flow of 23 GPM through
heater. Winterizing When freezing weather and/or power losses are expected,
contact your local spa dealer for freeze protection or winterizing
recommendations for both the spa and the equipment system. Freeze related
damage is not covered by the warranty.
Chemical Water Treatment
Your dealer is familiar with local water conditions and which chemicals are
compatible with and designed specifically for your spa. This is the best
person to advise you on proper water quality management. The one thing you can
do to insure years of trouble free equipment operations is to maintain proper
water chemistry. Two basic goals of the chemical water treatment are
sanitizing and balancing the water. Sanitizing simply means keeping the water
free from microorganisms including algae, bacteria and viruses. The current
most popular chemicals for sanitizing include chlorine, bromine and ozone.
Balancing water means establishing a balance among pH, total alkalinity and
total hardness. Water that is unbalanced can corrode the spa and it’s support
equipment or leave deposits of minerals. Properly balanced water is essential
to allow the sanitizing chemical to work effectively. There are numerous
chemical additives to help you in controlling pH, total hardness and
alkalinity. Never use softened water when filling you spa. Softened water is
extremely corrosive to the metal parts of the spa equipment and may lead to an
unforeseen failure. Sometimes, despite your most diligent efforts, your water
may become to far out of balance to be managed chemically. At this point it is
probably better to drain and clean the spa and start over with fresh water.
Equipment failure caused be improper water chemistry will not be covered under
warranty. Saltwater purification systems can potentially damage your
equipment. Any related failures will not be covered under warranty.
System Functions / Features
Spaside Control
Pump 1 Key: Pressing this key when the pump is OFF will turn it ON to
Low Speed, a second press switches the pump to High speed, a third press turns
the pump OFF. If the pump is ON from manual activation, the pump low speed
will time out after 30 minutes and the high speed will time out after 15
minutes. If the pump cannot be turned OFF a filter cycle is active.
Pump 2 Key: Press this key to turn Pump 2 ON and OFF. An automatic timer
will turn the pump off after 15 minutes of operation. Jet 2 indicator will
illuminate when it isactive.
Blower / AUX Key: Press this key to turn the blower ON and OFF. An
automatic timer will turn the blower off after 15 minutes of operation.
Light Key: Press this key to turn the light ON and OFF. An automatic
timer will turn the light off after 4 hours of operation. The Light indicator
will illuminate when it is active.
Temperature Set Keys : Press the “Cool/Down” button or “Warm/Up” button
to display the current set water temperature. Pressing either button while the
set
temperature is displayed will increase or decrease the set temperature by 1°F.
The temperature is adjustable between 80°F – 104°F / 26°C – 40°C or 50°F –
99°F /10°C – 37°C. See Dual Temp Range page 19
Filtration and Ozone**
On non-circ systems, Pump 1 low and the ozone generator will run during
filtration. On circ systems, the ozone will run with the circ pump.
The system is factory-programmed with one filter cycle that will run in the
evening (assuming the time-of day is properly set) when energy rates are often
lower. The filter time and duration are programmable. A second filter cycle
can be enabled as needed.
At the start of each filter cycle, the blower (if there is one) or Pump 2 (if
there is one) will run briefly to purge its plumbing to maintain good water
quality.
Freeze Protection
If the temperature sensors within the heater detect a low enough temperature
(44°F), then the pump(s) and blower automatically activate to provide freeze
protection. The pump(s) and blower will run either continuously or
periodically depending on conditions.
**See provided Spaside Control Operation
Guide for programming procedures.
System Functions / Features
Dual Temperature Ranges**
This system incorporates two temperature range settings with independent set
temperatures. The High Range designated in the display by an “up” arrow or
“High Range”, and the Low Range designated in the display by a “down” arrow or
“Low Range”.
These ranges can be used for various reasons, with a common use being a “ready
to use” setting vs. a “vacation” setting. The Ranges are chosen using the menu
structure. Each range maintains its own set temperature as programmed by the
user. This way, when a range is chosen, the spa will heat to the set
temperature associated with that range. High Range may be set between 80°F and
104°F Low Range may be set between 50°F and 99°F Freeze Protection is active
in either range
Mode – Ready and Rest**
In order for the spa to heat, a pump needs to circulate water through the
heater. The pump that performs this function is know as the “heater pump.”
READY MODE – Will circulate water every 1/2 hour, using Pump1 Low, in order to
maintain a constant water temperature, heat as needed, and refresh the
temperature display. This is known as “polling.” “Ready” will be displayed.
REST MODE – Will only allow heating during programmed filter cycles. The
temperature display may not show a current temperature until the heater pump
had been running for a minute or two. “REST” will be displayed.
READY-IN-REST MODE – Appears in the display if the spa is in Rest Mode and Jet
1 is pressed. It is assumed that the spa is being used and will heat to set
temperature. While Pump 1 High can be turned ON and OFF, Pump 1 Low will run
until set temperature is reached, or 1 hour has passed. After 1 hour, the
system will revert to Rest Mode. This mode can also be reset by entering the
Mode Menu and changing the Mode.
Time of Day**
Setting the time-of-day can be important in determining filtration times and
other background features.
NOTE:
If power is interrupted to the system, Time-of-Day is not stored. The system
will still operate and all other user settings will be stored. If filtered
cycles are required to run at a particular time of day, resetting the clock
will return the filter times to the actual programmed periods.
**See provided Spaside Control Operation Guide for programming procedures.
System Plug Pinouts
Testing / Replacing the Sensor Set
IMPORTANT: For the following set of instruction, the power must be off when plugging in or unplugging sensors.
- Check sensor wires for cracks or damage that may indicate the presence of a rodent.
- Inspect connections of both sensors on the circuit board. The plugs must be clean.
- If the spaside has the error message of Sa or Sb, this is an indication of a faulty sensor or possibly a faulty circuit board.
- With the power off to the spa, unplug the two sensors from the circuit board and exchange their positions (i.e., plug the one that was in the “Sen. A jack into the “Sen. B jack and vice versa).
- Power up the spa, if the error message did not change (i.g. original error message was Sa and still displays Sa) this is an indication of a faulty circuit board. If the error message changed (i.g., original error message was Sa and now displays Sb) replace the sensor in the corresponding plug on the circuit board.
- When replacing sensors, please keep in mind that the heater assembly will contain water pressure even with the spa’s power off. Close available slice valves and proceed with caution not to allow water on the surrounding electronics.
Troubleshooting
The following describes situations and possible solutions to common problems
you may encounter as a spa owner. TroubleShooting
Nothing Operates
Main Breaker is OFF – Set to On.
Sub-Panel Breaker Off – Set to On.
Equipment GFCI Off – Set to On.
Power switch in Off position – Set to On.
Components not plugged in – Plug in components.
Power cord not plugged in – Plug in power cord.
Over or High Temperature Protection On – Refer to Spa Side Messages.
No, Low or Surging Water Flow
Air Lock in Plumbing System – “Bleed” the system.
Restricted Flow – Insure that the water shut-off valves are open and that
suction fittings are not blocked by debris.
Dirty Filter – Clean or replace filter.
Low Water Level – Increase water level to recommended level.
Low Speed Pump Not Operational
Circuit board configuration is Incorrect – Contact your local dealer.
Pump Not Plugged-In – Plug in the Pump.
Blown Fuse – Contact your local dealer.
Jets or Blower Not Operational
Blower or Pump Not Plugged-In – Plug in the Blower or Pump.
Blown Fuse – Contact your local dealer.
Over or High Temperature Protection On – Refer to Spa Side Messages.
Therapy Jet Not Operational
Water Shut-Off Valves are Closed – Open Shut-Off valves.
Dirty Filter – Clean or replace filter.
Jets Not Properly Adjusted – Adjust Jets properly.
Diverter Valve Not Properly Adjusted – Adjust diverter valve properly.
Thermal Overload Tripping – Check for restricted flow of water.
Water Leaks
Spa Overfilled – Adjust water level.
Too Many People in the Spa – Adjust water level.
Drain-Valve Left Open – Close drain valve.
Couplings or Unions Loose – Tighten or contact your local dealer.
Pump Seal Leaking – Contact your local dealer.
Plumbing / Connections Leaking – Contact your local dealer.
Water Leaking from Spaside Control – Contact your local dealer.
Water in Air Blower Plumbing – Contact your local dealer.
No Heat
Temperature Not Set Correctly – Adjust Set Point.
Over or High Temperature Protection On – Refer to Spa Side Messages
Current Limiting On – 120V Systems will not heat if High Speed or Blower is
on.
Contact your local dealer.
No Power – Reset breaker at service panel.
Low Water Flow – Clean or Replace filter.
System is in Rest Mode – Refer to Modes on page 19.
Light Not Operation
Light Bulb Defective – Replace bulb or contact your local dealer.
Reflector has Fallen Off – Replace deflector or contact your local dealer.
Light Not Plugged-In – Plug in the Light.
High Heat
Filter Cycles Running Too Long – Adjust filter cycles down.
Temperature Set Too High – Adjust Set Point.
High Ambient Temperature – Remove spa cover.
GFCI Breaker Trips Occasionally
Lightning / Electrical Storm or Power Surge – Reset GFCI Breaker.
NOTE: The GFCI breaker must be properly installed by a licensed electrician.
GFCI Breaker Trips Immediately
Defective Component or Improper GFCI Breaker Installation – Contact a
qualified service technician or the factory for assistance.
System Data Label
Note: This information will be necessary if you should ever have to
request warranty or any other type of service.
The system data label is located on the control box. This label is very
important and contains information you will need to establish your electrical
service. The voltage and amperage ratings are shown on the bottom of the
label. Product, Model, Serial and Code numbers are also shown on the label.
Warranty Information
Hydro-Quip warrants its products to the original purchaser to be free from
defects in material and workmanship for a period of 1 year (12 months) from
the original date of purchase, except as noted below.
Products which become defective within the warranty period will be repaired or
replaced (at the option of Hydro-Quip) except for damage due to freezing,
water chemistry, negligence, abuse, misuse, misapplication, unauthorized
modification, improper installation, normal wear and tear or chemical attack.
This warranty extends only to normal, personal (non-commercial) usage by the
original purchaser. Pump seals, o-rings, gaskets, air blower brushes are only
covered for 90 days from original date of purchase.
Hydro-Quip will not be responsible for labor incurred in removing, inspecting
or reinstalling of warrantable products. Hydro-Quip will not be responsible
for any travel related charges or labor costs attributable to disassembly and
reassembly of the spa, skirt, decking or any other materials enclosing the
product, or attributable to difficulties in gaining access to the product.
Hydro-Quip will not be responsible for labor incurred for routine maintenance,
adjustments or alterations to the calibration of electrical devices.
Any products which are claimed to be defective must be shipped freight prepaid
to HydroQuip and the repaired or replaced product will be returned to the
sender freight collect.
When sent to Hydro-Quip, the product must be accompanied by the sales receipt
or other proof of the purchase date as well as the sender’s name, mailing
address, daytime phone number and a detailed description of the defect as well
as any other information relating to this claim.
Unless state law expressly provides otherwise, Hydro-Quip will only be
responsible for repair or replacement of any of its products that are found to
be defective as provided above, and will not bear the cost of any
consequential damages. This warranty gives you specific legal rights but you
may have other rights which vary from state to state.
HYDROQU I V THE SMART CHOICE’
510A N. Sheridan St – Corona, CA 92878
PH: 951-273-7575 – Fax:
951-273-7550
www.hydroquip.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>