APsystems DS3-L and DS3 Microinverters User Manual
- June 10, 2024
- APsystems
Table of Contents
- Important Safety Instructions
- APsystems Microinverter System Introduction
- APsystems Microinverter DS3 series Introduction
- Systems Microinverter System Installation
- APsystems micro inverter system operating instructions
- Troubleshooting
- Replace a micro inverter
- Technical Data
- DS3 series – Wiring Diagram
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
APsystems Microinverter
User Manual
APsystems DS3 series
DS3-L and DS3 Microinverters
(For APAC)
Important Safety Instructions
This manual contains important instructions to follow during installation and
maintenance of the APsystems Photovoltaic Grid-connected Microinverter. To
reduce the risk of electrical shock and ensure a safe installation and
operation of the APsystems Microinverter, the following symbols appear
throughout this document to indicate dangerous conditions and important safety
instructions.
Specifications are subject to change without notice. Please ensure you are
using the most recent update found at https://global.apsystems.com/resources
/library-landing/
WARNING
This indicates a situation where failure to follow instructions may cause a
serious hardware failure or personnel danger if not applied appropriately. Use
extreme caution when performing this task.
NOTICE
This indicates information that is important for optimized micro inverter
operation.
Follow these instructions closely.
1.1 Safety Instructions
-
Only qualified professionals should install and/or replace APsystems Microinverters.
-
Perform all electrical installations in accordance with local electrical codes.
-
Before installing or using the APsystems Microinverter, please read all instructions and cautionary markings in the technical documents and on the APsystems Microinverter system and the solar array.
-
Do NOT disconnect the PV module from the APsystems Microinverter without first disconnecting the AC power.
-
Be aware that the body of the APsystems Microinverter is the heat sink and can reach a temperature of 80°C. To reduce risk of burns, do not touch the body of the Microinverter.
-
Do NOT attempt to repair the APsystems Microinverter. If the micro inverter is suspected to be faulty, please contact your local APsystems Technical Support to start troubleshooting and obtain a RMA (Return Merchandise Authorization) number to start the replacement process if needed. Damaging or opening the APsystems Microinverter will void the warranty.
-
Caution!
When connecting a micro inverter, it is recommended to first connect the AC Bus cable to the ground then connect the AC connector to ensure proper earthing of the micro inverter, then do the DC connections. When disconnecting a micro inverter disconnect the AC by opening the branch circuit breaker first but maintain the protective earthing conductor in the branch circuit breaker connected to the micro inverter, then disconnect the DC inputs. -
Please install AC breakers on the AC side of the inverter.
1.2 Radio Interference Statement
EMC Compliance :The APsystems Microinverter can radiate radio frequency
energy. If not installed and used in accordance with the instructions, it may
cause harmful interference to radio communication.
APsystems Microinverter complies with EMC regulations, which are designed to
provide reasonable protection against harmful interference in a residential
installation.
Nonetheless, if the Microinverter does cause harmful interference to radio or
television reception, you are encouraged to try to correct the interference by
one of more of the
following measures:
A) Reorient or relocate the receiving antenna
B) Increase the separation between the Microinverter and the receiver
C) Connect the Microinverter into an outlet on a circuit different from that
to which the receiver is connected
If none of the recommendations suggested above bring significant improvement
in terms of interference, please contact your local APsystems Technical
Support.
1.3 Symbols replace words on the equipment, on a display, or in manuals
Trademark.
| Caution, risk of electric shock
---|---
| Caution, hot surface.
| Symbol for the marking of electrical and electronics devices according to
Directive 2002/96/EC. Indicates that the device, accessories and the packaging
must not be disposed as unsorted municipal waste and must be collected
separately at the end of the usage. Please follow Local Ordinances or
Regulations for disposal or contact an authorized representative of the
manufacturer for information concerning the decommissioning of equipment.
| CE mark is attached to the solar inverter to verify that the unit
follows the provisions of the European Low Voltage and EMC Directives.
| Refer to the operating instructions.
Qualified personnel| Person adequately advised or supervised by an
electrically skilled person to enable him or her to perceive risks and to
avoid hazards which electricity can create. For the purpose of the safety
information of this manual, a “qualified person” is someone who is familiar
with requirements for safety, electrical system and EMC and is authorized to
energize, ground, and tag equipment, systems, and circuits in accordance with
established safety procedures. The inverter and photovoltaic system may only
be commissioned and operated by qualified personnel.
APsystems Microinverter System Introduction
The APsystems Microinverter is used in utility-interactive grid-tied applications, comprised of three key elements:
- APsystems Microinverter
- APsystems Energy Communication Unit (ECU)
- APsystems Energy Monitor and Analysis (EMA) web-based monitoring and analysis system
This integrated system improves safety; maximizes solar energy harvest;
increases system reliability, and simplifies solar system design,
installation, maintenance, and management.
Safety with APsystems Microinverters
In a typical string inverter installation, PV modules are connected in series.
The voltage adds-up to reach high voltage value (from 600Vdc up to 1000Vdc) at
the end of the PV string. This extreme high DC voltage brings a risk of
electrical shocks or electrical arcs which could cause fire.
When using an APsystems micro inverter, PV modules are connected in parallel.
Voltage at the back of each PV module never exceeds PV modules Voc, which is
lower than 60Vdc for most of PV modules used with APsystems micro inverters.
This low voltage is considered “safe to touch” by fire departments and negates
the risk of electrical shock, electrical arcs and fire hazards.
APsystems Microinverters maximize PV energy production
Each PV module has individual Maximum Peak Power Tracking (MPPT) control,
which ensures that the maximum power is produced to the utility grid
regardless of the performance of the other PV modules in the array. When PV
modules in the array are affected by shade, dust, different orientation, or
any situation in which one module under performs compared with the other
units, the APsystems Microinverter ensures top performance from the array by
maximizing the performance of each module individually within the array.
More reliable than centralized or string inverters
The distributed APsystems Microinverter system ensures that no single point of
system failure exists across the PV system. APsystems Microinverters are
designed to operate at full power at ambient outdoor temperatures of up to 65
deg C (or 149 F). The inverter case is designed for outdoor installation and
complies with the IP67 environmental enclosure rating.
Simple to install
APsystems Micrometeorites are compatible with most of 60 and 72 cell PV
modules or 120 and 144 half-cut cells PV modules. (In order to confirm
compatibility of PV module with APsystems micro inverter, feel free to check
our online “E-decider” module compatibility tool or contact your local
APsystems Technical Support).
Installation requires a minimum number of accessories and micro inverters
offer a lot of versatility to the installer: micro inverters can indeed be
installed on different roofs with different orientation or with modules having
different orientation.
In the same way, end-users can extend their system whenever they want with
micro inverters.
Smart system performance monitoring and analysis
The APsystems Energy Communication Unit (ECU) is installed by simply plugging
it into any wall outlet and providing an Ethernet or Wi-Fi connection to a
broadband router or modem. After installing and setting the ECU (see ECU
Instruction Manual), the full network of APsystems Microinverters
automatically reports to the APsystems Energy Monitor and Analysis (EMA) web
server.
APsystems Microinverter DS3 series Introduction
APsystems 3rd generation of dual micro inverters are reaching unprecedented
power outputs of 730VA or 880VA to adapt to today’s larger power module. With
2 independent MP PT, encrypted Zambezi signals, the DS3-L and DS3 benefit
from an entirely new architecture and are fully backwards compatible with the
QS1 and YC600 micro inverters. The innovative and compact design make the
product lighter while maximizing power production. The components are
encapsulated with silicone to reduce stress on the electronics, facilitate
thermal dissipation, enhance waterproof properties, and ensure maximum
reliability of the system via rigorous testing methods including accelerated
life testing. A 24/7 energy access through Apps or web based portal facilitate
remote diagnosis and maintenance.
The DS3 series is interactive with power grids through a feature referred to
as RPC (Reactive Power Control) to better manage photovoltaic power spikes in
the grid. With a performance and an efficiency of 97%, a unique integration
with 20% less components, APsystems DS3-L and DS3 are a game changer to
residential and commercial PV.
Key Product Feature:
- One micro inverter connects to two PV modules
- Maximum output power reaching 730VA (DS3-L) or 880VA (DS3)
- Two input channels with independent MP PT
- Reactive Power Control
- Maximum reliability, IP67
- Encrypted Zambezi communication
- Safety protection relay integrated
- Single phase micro inverter. Possible to install in a balanced 3-phase system
Systems Microinverter System Installation
A PV system using APsystems Microinverters is simple to install. Each
Microinverter easily mounts on the PV racking, directly beneath the PV
module(s). Low voltage DC wires connect from the PV module directly to the
Microinverter, eliminating the risk of high DC voltage. Installation MUST
comply with local regulations and technical rules.
Special Statement: we advise installation of an RCD breaker only if required
by the local electrical code.
WARNING
- Perform all electrical installations in accordance with local electrical codes.
- Be aware that only qualified professionals should install and/or replace APsystems Microinverters.
- Before installing or using an APsystems Microinverter, please read all instructions and warnings in the technical documents and on the APsystems Microinverter system itself as well as on the PV array.
- Be aware that installation of this equipment includes the risk of electric shock.
- Do not touch any live parts in the system, including the PV array, when the system has been connected to the electrical grid.
NOTICE
Even if not required by local electrical code, we strongly recommend to
install surge protection devices in the dedicated AC box.
4.1 Additional accessories supplied by APsystems
- AC Y3 Bus cable
- AC Y3 Bus Cable End Cap
- AC Y3 Bus Cable CONNY Cap
- AC Y3 Bus Cable Unlock Tool
- ECU
- AC connectors male/female
4.2 Other required accessories not supplied by APsystems
In addition to your PV array and its associated hardware, you may need the
following items:
- An AC connection junction box
- Mounting hardware suitable for module racking
- Sockets and wrenches for mounting hardware
4.3 Installation Procedures
4.3.1 Step 1 – Verify that grid voltage matches micro inverter rating
4.3.2 Step 2 – Y3 AC Bus Cable distribution
a. Each connector drop of the AC Bus cable matches the position of the micro
inverter.
b. One end of the AC bus cable is used to access the junction box into the
power grid.
c. Wire the conductors of the AC bus: L – BROWN ; N – BLUE;PE – YELLOW GREEN.
WARNING
Wiring color code can be different according to local regulations. Check all
the wires of the installation before connecting to the AC bus to be sure they
match. Improper cabling can irreparably damage the micro inverters: such
damage is not covered by the warranty.
WARNING
It is strictly prohibited to hand carry the micro inverter by its AC cable.
4.3.3 Step 3 – Attach the APsystems Microinverters to the Racking
a. Mark the location of the micro inverter on the rack, with respect to the PV
module junction box or any other obstructions.
b. Mount one micro inverter at each of these locations using hardware
recommended by your module racking vendor.
WARNING
Install the micro inverters (including DC and AC connectors) under the PV
modules to avoid direct exposure to rain, UV or other harmful weather events.
Allow a minimum of 1.5 cm (3/4’’) below and above the casing of the micro
inverter to allow proper air flow. The racking must be properly grounded as
per local electrical code.
4.3.4 Step 4 – Ground the system
Y3 AC Bus cable has an embedded PE wire: this might be sufficient to ensure
proper grounding of the whole PV array. However, in areas with special
grounding requirements, external grounding work may still be needed, using the
grounding lug supplied with the Microinverter
4.3.5 Step 5 – Connect the APsystems micro inverter to AC bus cable
Insert the micro inverter AC connector into the trunk cable connector. Make
sure to hear the “click” as a proof of robust connection
Best Practice: Use the AC Bus Cable Unlock Tool to disconnect the connectors.
NOTICE
Check the micro inverter technical data page 19 to confirm maximum allowable
number of micro inverters on each AC branch of the circuit.
AC connector interface as from left to right.
Cover any unused connectors with Bus Cable Y-CONN Cap to protect the unused connectors.
4.3.6 Step 6 – Install a Bus Cable End Cap at the end of AC bus cable
a. Strip cable jacket.
b. Insert the cable end into the seal.
c. Insert the wires into the cable clamps.
d. Rotate the nut with 3.3N·m until the latching mechanism meets the base.
4.3.7 Step 7 – Connect APsystems Microinverters to the PV Modules
NOTICE
When plugging in the DC cables, the micro inverter should immediately blink
red one time and green ten times. This will happen as soon as the DC cables
are plugged in and
will show that the micro inverter is functioning correctly. This entire check
function will start and end within 10 seconds of plugging in the unit, so pay
careful attention to these lights when connecting the DC cables.
WARNING
Double check to make sure all of the AC and DC wiring has been correctly
installed. Ensure that none of the AC and/or DC wires are pinched or damaged.
Make sure that all of the junction boxes are properly closed.
WARNING
Each PV panel must be carefully connected to the same channel. Make sure to
not split positive and negative DC cables into two different input channels:
micro inverter will become damaged and warranty will not apply.
4.3.8 Step 8 – Complete the APsystems installation map
a. Each APsystems Microinverter has 2 removable serial number labels.
b. Complete the installation map by sticking the ID label of each micro
inverter in the right location.
c. The second serial number label, could be stuck on the solar module frame,
which could help later to confirm the position of the micro inverter without
dismantling the
PV module
NOTICE
- The layout of the micro inverters’ serial number installation map is only suitable for a typical installation.
- Installation Map is available in the last page appendix of this manual.
- Use ECU_APP (available in the EMA Manager) to scan the serial numbers on the map when setting up the ECU (see ECU instruction manual for more info).
4.3.9 Step 9 – Warning Notice
A warning notice must be placed in such a way that anyone with access to live
parts is warned in advance of the need to switch off these parts. It is
imperative to verify that the power supply, measurement circuits (sense lines)
and other parts are not isolated from the network when the interface
protection switch is open.
As a minimum, warning labels shall be placed:
- On the switchboard (DNO panel and consumer unit) that has the PV generator connected to it;
- On all switchboards in between the consumer unit and the PV generator itself;
- On, or in the PV generator itself;
- At all points of isolation for the PV generator
APsystems micro inverter system operating instructions
To operate the APsystems micro inverter PV system:
- Turn ON the AC circuit breaker on each micro inverter AC branch circuit.
- Turn ON the main utility-grid AC circuit breaker. Your system will start producing power after approximately one minute of waiting time.
- Microinverter data will be available in the EMA Manager APP or in the EMA web portal.
Alternatively, LED sequences could be an indicator of micro inverters status
(see section 6.1)
NOTICE
Once the ECU has been commissioned properly, the APsystems Microinverters will
start to send performance data to the ECU. The time required for all of the
Microinverters in the system to report to the ECU will vary depending on the
number of Microinverters in the system.
Troubleshooting
Qualified personnel can use the following troubleshooting steps if the PV
system does not operate correctly:
6.1 Status Indications and Error Reporting
Assuming they are easily accessible and visible, Operation LEDs can give a
good indication of the micro inverters status
6.1.1 Start up LED
One short red and ten short green blinks when DC power is first applied to the
Microinverter indicates a successful Microinverter startup.
6.1.2 Operation LED
Flashing Slow Green (5 sec. gap) – Producing power and communicating with ECU
Flashing Slow Red (5 sec. gap) – Not producing power
Flashing Fast Green (2 sec. gap) – Not communicating with ECU over 60mins, but
still producing power.
Flashing Fast Red (2 sec. gap) – Not communicating with ECU over 60mins and
not producing power.
Steady Red – default, DC side ground fault protection, see 6.1.3
6.1.3 GFDI Error
A solid red LED indicates the Microinverter has detected a Ground Fault
Detector Interrupter (GFDI) error in the PV system. Unless the GFDI error has
been cleared, the LED will remain red and the ECU will keep reporting the
fault. Please contact your local APsystems Technical Support.
6.2 ECU_APP
APsystems ECU_APP (available in the EMA Manager APP) is the recommended tool
to do on-site troubleshooting. When connecting the ECU_APP to the ECU hotspot
(please check ECU User Manual for more detailed information), installer can
check every micro inverter status (production, communication) but also Zigbee
signal strength, grid profile and other insightful data helping the
troubleshooting.
6.3 Installer EMA (web portal or EMA Manager APP)
Before going on site for troubleshooting, installer can also check all
information remotely using his installer account, either on the web or using
the EMA Manager APP (see EMA Manager APP User Manual for more detailed
information). Having access to module data (DC, AC, voltages and currents)
gives the first indication on potential issues.
6.4 Trouble Shooting Guide
Professional installers can also refer to our Troubleshooting Guide
(https://global.apsystems.com/resources/library-landing/,section
libraries)for more in depth guidelines on how to troubleshoot and fix PV
installations powered by APsystems micro inverters.
6.5 APsystems Technical Support
The APsystems local Technical Support team is available to support
professional installers in becoming familiar with our products and to
troubleshoot installations when needed.
WARNING
Do not attempt to repair APsystems Microinverters. Please contact your local
APsystems Technical Support.
WARNING
- Never disconnect the DC wire connectors under load. Ensure that no current is flowing in the DC wires prior to disconnecting.
- Always disconnect AC power before disconnecting the PV module wires from the APsystems Microinverter.
- The APsystems Microinverter is powered by PV module DC power. AFTER disconnecting the DC power, when reconnecting the PV modules to the Microinverter, be sure to watch for the quick red light followed by ten short green LED flashes.
6.6 Maintenance
APsystems micro inverters do not require any specific regular maintenance.
Replace a micro inverter
Follow the procedure to replace a failed APsystems Microinverter
A. Disconnect the APsystems Microinverter from the PV Module, in the order
shown below:
- Disconnect the AC by turning off the branch circuit breaker.
- Disconnect the inverter AC connector from the AC Bus.
- Disconnect the PV module DC wire connectors from the micro inverter.
- Remove the Microinverter from the PV array racking.
B. Install a replacement Microinverter to the rack. Remember to observe the
flashing green LED light as soon as the new Microinverter is plugged into the
DC cables.
C. Connect the AC cable of the replacement Microinverter to the AC bus.
D. Close the branch circuit breaker, and verify proper operation of the
replacement Microinverter.
E. Update the micro inverter in the EMA Manager through the “Replace” function
and update the system’s map with new serial number labels.
Technical Data
WARNING
- Be sure to verify that the voltage and current specifications of your PV module are compatible with the range allowed on APsystems Microinverter. Please check the micro inverter datasheet.
- DC operating voltage range of the PV module must be within allowable input voltage range of the APsystems Microinverter.
- The maximum open circuit voltage of the PV module must not exceed the specified maximum input voltage of the APsystems.
8.1 DS3 series Microinverter Datasheet
‘Model | D57-L | DS3 |
---|
Input Data (DC)
Recommended PV Module Power (STC) Range| 255Wp-550Wp+| 300Wp-660Wp+
Peak Power Tracking Voltage| 25V-55V| 32V-55V
I Operating Voltage Range| 16V-60V| 26V-60V
Maximum Input Voltage| 60V
I Maximum Input Current| 18A x 2| 20A x 2
Output Data (AC)
Maximum Continuous Output Power| 730VA| 880VA
Nominal Output Voltage/Range’| 230V/184-253V
Nominal Output Current| 3.2A| 3.8A
Nominal Output Frequency/ Range’| 50Hz/48Hz-51Hz
Power Factor(Default/Adjustable)| 0.99/0.8 leading…0.8 lagging
Maximum Units per 20A Branch’.| 6 I 5
Efficiency
I Peak Efficiency| 97%
CEC Efficiency| 97.%
I Nominal MPPT Efficiency| 100.%
Night Power Consumption| 20mW
Mechanical Data
I Operating Ambient Temperature Range| -40 °C to +65 °C
Storage Temperature Range| -40 °C to +85 °C
Dimensions (W x H x D)| 262mm X 218mm X 41.2mm
Weight| 2.6kg
AC Bus Cable| 2.5mm’
DC Connector Type| Stab!’ MC4 PV-ADBP4-S2&ADSP4-52
Cooling| Natural Convection – No Fans
Enclosure Environmental Rating| IP67
Features
1 Communication (Inverter To ECU)| Encrypted Zambezi
Isolation Design| High Frequency Transformers. Galvanic ally Isolated
Energy Management| Energy Management Analysis (EMA) system
Warranty—| 10 Years Standard : 20 Years Optional
Compliance
Safety. EMC & Grid Compliance| EN 62109-1: EN 62109-2: EN 61000-6-1; EN
61000-6-3:
UNE217002.UNE206007-1.RD647.RD1699.RD413: CEI 0-21:
VDE0126-1-1.VFR2019.UTE C15-712-1.ERDF-NOI-RES_13E:
Nominal voltage/frequency range can be extended beyond nominal if required by the utility.
Limits may vary. Refer to local requirements to define the number of micro
inverters per branch in your area.
To be eligible for the warranty, APsystems micro inverters need to be
monitored via the EMA portal. Please refer to our warranty T&Cs available on
global.apsystems.com.
© All Rights Reserved
Specifications subject to change without notice please ensure you are using
the most recent update found at web :
global.apsystems.com
DS3 series – Wiring Diagram
9.1 Sample Wiring Diagram – Single Phase
APsystems Microinverter & Energy Communication Unit Installation Map
The APsystems Installation Map is a diagram of the physical location of each
micro inverter in your PV installation. Each APsystems micro inverter has two
serial number labels. Peel the one label and affix it to the respective
location on the APsystems installation map.
Installation Map Template
Installer:| PV module type: Qty:|
Sheet __**of
|
---|---|---|---
Owner:| Microcomputer type: Qty:**
| Column 1| Column 2| Column 3| Column 4| Column 5| Column 6| Column 7
Row 1| | | | | | |
Row 2| | | | | | |
Row 3| | | | | | |
Row 4| | | | | | |
Row 5| | | | | | |
Row6| | | | | | |
Row 7| | | | | | |
Row 8| | | | | | |
Row 9| | | | | | |
Row10| | | | | | |
ALT ENERGY POWER SYSTEM Inc.
global.apsystems.com
APsystems Shanghai:
Rm.B305 No.188, Zhang yang Road, Pu dong, Shanghai
200120,P.R.C
Tel: 021-3392-8205 EMAIL:
info.apac@APsystems.com
© All Rights ReservedPlease scan this QR code to have access to our
APPs and Products information
http://q-r.to/1OrC
References
- APsystems Global | The global leader in multi-platform MLPE technology
- Documents Library – APsystems Global | The global leader in multi-platform MLPE technology
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>