PHILIPS EasySense SNS212 IA Fixture Mount Sensors
Wireless Node Part Number
Commercial Product Name | Order Code |
---|---|
EasySense Fixture-Mount Sensor | SNS212/w IA,12NC:929003430613 |
SNS212/b IA, 12NC: 92900340713
LED Drivers
The EasySense SNS212 IA sensors are compatible with Xitanium SR drivers. To find the SR driver that fits your application needs and for product specifications, please visit www.Signify.com/xitaniumsr
Wiring Diagram*
Connection | Color |
---|---|
Green | Ground |
White | Neutral |
Black | Line |
Connection | Color |
--- | --- |
Purple | DA+ |
Brown | DA- |
Red | LED+ |
Blue | LED |
- Wiring diagram for 40W driver shown. Other drivers have different wiring diagrams.
Consult datasheet for driver for applicable wiring diagram
Sensor Dimensions (in/mm)
Mounting Dimensions (in/mm)
Mounting in U-shaped slot in sheet metal (max thickness 1 mm)
Mounting in cut-out in sheet metal (thickness 0.7 mm to 1.0 mm)
Note: Consult factory for accessory mounting ring to secure sensor to cut-out.
Fixture with EasySense installed
Mounting in a slot
Mounting in a cut-out with mounting ring
Accessory Mounting Ring
- Part Number SMR-50 / Set of 50.
- Ordered separately, not included.
Accessory Mounting Bracket
- Part Number SMB-50 / Set of 50.
- Ordered separately, not included.
Note: Below data applicable for SNS212 IA..
Electrical Information
Input Voltage| Powered by SR driver low-voltage interface
Current Consumption| 13mA
Nominal Power Consumption| 200mW
Standby Power| < 1 W on luminaire level, including driver standby power
Occupancy Sensing
Type| Passive infrared (PIR)
Occupancy Based Control| Default enabled and active for SNS211 IA.
Activated upon commissioning for SNS210 IA.
Occupancy Mode| Default Auto on/off. Other options are: Manual on/off,
Manual on/auto off
Eco On Level| 1 – 100%
Hold Time| 5 – 100 minutes
Viewing Angle| X = 62°, Y = 84° ( See detection pattern)
Background Light Level| 1 – 100%
Prolong Time| 7 – 100 minutes + infinite
Grace Fading| 1 – 25 sec
Response Time/Fading to Switch On/Of| 1 sec
Daylight Sensing
Enable/Disable| Default enabled
Viewing Angle| 40° (half value sensitivity); 2% cut-off point at 75°
Task Tuning
Field Task Level| 1%-100%
Environment & Approbation
Operating Ambient Temperature Range| 0°C to 55°C
Operating Humidity| 20% – 85% non condensing
Storage Temperature| -25 °C – 85 °C
Storage Humidity| 0-95% non condensing
Max Case Temperature (Tcase)| 55°C
Agency Approbations| UL, FCC; Tested and approved for use in plenums
Limited Warranty| 5 years
Digital Interface| Xitanium SR
Other
Status Indicators| After commissioning: Red LED on: Motion is detected;
Yellow LED on: Vacancy detected & Sensor is functional
No. Drivers per Sensor| Four (max
Operation and Configuration via Mobile App
SNS212 IA requires commissioning to operate. The node can be commissioned and
configured via the Interact system
FCC and IC Statement
This equipment has been tested and found to comply with the limits for a Class
A digital device, pursuant to part 15 of the FCC Rules for the United States
and Industry Canada (IC) license-exempt RSS standard(s). These limits are
designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment and is intended for
commercial use only. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications.
Operation is subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation. Operation
of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the
interference at his own expense. Any changes or modifications not expressly
approved by Signify could void the user’s authority to operate this equipment.
This equipment should be installed and operated with a minimum distance of 20cm between the radiator and your body.
© 2023 Signify Holding. All rights reserved. The information provided herein is subject to change, without notice. Signify does not give any representation or warranty as to the accuracy or completeness of the information included herein and shall not be liable for any action in reliance thereon. The information presented in this document is not intended as any commercial offer and does not form part of any quotation or contract, unless otherwise agreed by Signify. Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V. All other trademarks are owned by Signify Holding or their respective owners.
Signify North America Corporation
400 Crossing Blvd, Suite 600
Bridgewater, NJ 08807
Tel.855-486-2216
Signify Canada Ltd.
281 Hillmount Rd,
Markham, ON, Canada L6C 2S3
Tel.800-668-9008
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>