beckett CL201ULP Automatic Condensate Removal Pump Instruction Manual

June 11, 2024
beckett


AUTOMATIC CONDENSATE REMOVAL PUMP

BOMBA AUTOMATICA PARA REMOVER CONDENSACION

CAUTION
For plenum installations use only metallic tubing for the intake and discharge, and metal conduit for wiring.
Read all Instructions carefully for safe operation and installation.
Do not handle the pump with wet hands or when standing in water as fatal shock could occur.
Disconnect main power before handling unit for any reason!

Models
CL201ULP
Max water temperature 150°F
beckett CL201ULP Automatic Condensate Removal
Pump

Save this Manual for future reference.

INSTALLATION

  1. Select a location for the pump inside the air handling unit (This pump is UL tested to UL2043 for Plenum Applications). It should be as near as possible to the air conditioning coil. THE  PUMP MUST BE LEVEL. The inlet hole must be below the coil drain.
  2. Carefully unpack the pump. Remove the cover assembly from the tank; check float assembly for free movement.
  3. Run a metal drain line from the evaporator coil drain to the pump inlet. Be sure inlet piping is sloped downward to allow gravity flow. Insert the line below the tank cover and be sure it  does not interfere with the operation of the float.
  4. Connect outlet tubing to discharge of pump. Do not run tubing vertical more than 17’ for each unit. For good flow, slant the horizontal run downward.

WARNING
This pump is supplied with a 3-prong grounding type attachment plug.
To reduce the risk of electric shock connect only to a properly grounded receptacle.

WARNING: Turn off electrical power at the fuse box before making any line voltage connections. The wiring must comply with local codes. Use the National Electrical Code if local code is  nonexistent.
LINE VOLTAGE: If it is necessary to install a receptacle in the furnace/air conditioner area, connect only to a constant source of the nameplate voltage. (Example: The black and white leads in the furnace junction or switch box bringing 120 volt power to the furnace). Be sure that you do not connect into a fan or limit control circuit.
LOW VOLTAGE: Connect the high-level safety switch leads to the thermostat control circuit of the furnace/air conditioner.

PIPING

Also refer to your Furnace Manufacture Instructions.

  • Run a drain line from the evaporator coil drain and furnace to the pump.
  • Use flexible plastic pipe, where the code permits, and insert the pipe ¾” below the pump cover. When multiple drains (main and overflow) are required it may be necessary to tee them  together where they enter the pump.

CAUTION: Do not tee an evaporator coil drain together with a condensate drain from the furnace.

  • Locate the highest point above the pump, but no more than 17 feet, and fasten flexible tubing or 3/8” I.D. maximum pipe to the discharge to prevent excessive back flow to the unit.
  • Be careful not to kink it, for this will block the flow.
  • From this high point, slope discharge line down slightly to a point above the drain area; then turn down and extend to a point below or approximately level with the bottom of the  condensate unit. If it is impossible to slope discharge line down, make an inverted “U” trap directly above the pump at the highest point.
  • Couple the vinyl tubing with a 3” piece of 3/8” O.D. copper tubing. Or you can use 3/8” copper tubing all the way to the drain.
  • This pump does not require use of a condensate neutralizer to protect the pump when used with a condensing gas furnace. However, local codes may require that it be used.

beckett CL201ULP Automatic Condensate Removal Pump - parts
1

TESTING

  • Remove the tubing connecting the drains to the pump and pour water slowly into the pump inlet.
  • The control float will rise until the snap switch turns the pump on.
  • The pump should run and water should flow from the tubing to the drain.
  • To test the safety control, temporarily stop the flow of the discharge line by sharply bending vinyl tubing.
  • Water level will rise beyond high level of control float until safety float switch breaks the “Y” thermostat circuit shutting down air conditioner condensing unit.
  • Unbend the tube and the pump will empty the entire sump.
  • Replace inlet line into pump inlet.
1  Motor/Switch Cover
2 Fan
3 Check Valve
4 Main Switch
5 Safety Switch
6 Tank
7 Wiring Conduit

WIRING

beckett CL201ULP Automatic Condensate Removal Pump -
thermostat

MAINTENANCE & TROUBLE SHOOTING

PROBLEM REMEDY
1) Jammed control or safety float rod. 1) Check for interference with up and

down movement. The lever on the switch should rise and then “click” asthe float is pushed all the way up. It should then lower and “click” as the float is allowed to come all the waydown.
2) Plugged discharge tube.| 2) Unscrew the 3/8” barbed check-valve at the pump discharge and check for obstructions.
3) Floats not operating properly.| 3) Clean the float rod and tank with detergent.
4) Motor fails to run or runs intermittently.| 4) Check for blown fuse. Check for stalled motor due to obstruction in the pump.

NOTE: Motor is protected by an automatic thermal overload. This may cause it to stop. Shut off power and allow 20 minutes for the motor to cool before restarting. If the motor smells burned  or scorched, replace.

  • The pump motor contains permanently lubricated bearings. Under normal operating conditions further lubrications is not necessary.
  • Always replace cover to keep electrical parts clear of dust and grime.
  • Call your Service Technician for conditions you cannot correct.

LIMITED WARRANTY

Each Beckett Corporation (“Beckett”) product is warranted to be free from defects in material and workmanship for the applicable Warranty Period (herein so called) set forth below. The  Warranty Period for each product commences on the date of purchase by the original purchaser. The Warranty Periods are as follows:

Product Type or Name
Warranty Period

Pump Models:
FR Series, DP800-1800, G Series, W Series …………2 Years
UL6500A; XL-6500A………………………. 2 Years
Other Pump Models……………………….. 1 Year
Pre-Formed Poly Ponds………………………. 15 Years
Waterfall Weir & Skimmer………………………… 5 Years
Liner Material:
35 mil PVC…………………………………..20 Years
40 mil EPDM…………………………………20 Years
20 mil PVC…………………………………..15 Years
UV9/UV13 Filter……………………………. 1 Year
All Other Beckett Products…………………90 Days

APPLICATION: The warranty covers only properly installed and maintained Beckett products and is limited to application at normal temperature 32º F to 86º F, (0º C to 30º C) pumping  fluids with a specific gravity up to 1.1 and with a pH range of 5 to 9 (fresh water).
Other liquid applications and extreme temperature uses must be approved in advance by Beckett. The warranty does not apply to or cover damages or defects caused by external causes,  including, but not limited to, improper or faulty installation or unauthorized modification, lightning, electrical surges, abuse, misuse or abnormal use or misapplication, including use in a  manner inconsistent with the product’s intended function. The purchaser is responsible for determining the suitability of the product for its intended use. If products are damaged in transit, a  claim should be filed with the carrier.
REMEDY: If there has been a failure to conform to the warranty, Beckett will, at Beckett’s option, repair, replace or issue a credit or refund for the particular nonconforming product or part.  Repair, replacement, credit or refund, at Beckett’s option, is the exclusive remedy in the event of a failure to conform to the warranty. Warranty claims must be made within 3 months after expiration of the applicable Warranty Period.
ADMINISTRATION: Warranty claims must be made by returning the nonconforming Beckett product, freight prepaid, along with proof of purchase, to: Beckett Corporation, Customer  Service Dept., Irving, Texas, telephone 888-232-5388. Telephone authorization from Beckett is required prior to returning nonconforming products or parts. All products or parts returned will be inspected to determine cause of failure before warranty is approved.
INSTALLATION, REMOVAL AND/OR SHIPPING CHARGES: The warranty does not cover any costs associated with the installation, removal or shipping of products subject to warranty claims.
DISCLAIMER AND LIMITATION: THE EXPRESS WARRANTY AND REMEDIES SET FORTH ABOVE ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES AND  REMEDIES, WHETHER ORAL OR WRITTEN, EXPRESS OR IMPLIED. TO THE FULL EXTENT PERMITTED BY LAW, BECKETT EXPRESSLY DISCLAIMS ANY AND ALL  IMPLIED WARRANTIES, INCLUDING, WITHOUT LIMITATION, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. IF  IMPLIED WARRANTIES CANNOT BE DISCLAIMED, ALL SUCH IMPLIED WARRANTIES ARE LIMITED TO THE DURATION OF THE APPLICABLE EXPRESS WARRANTY.
BECKETT DOES NOT ACCEPT LIABILITY BEYOND THE REMEDIES EXPRESSLY SET FORTH IN THIS WARRANTY. IN NO EVENT SHALL BECKETT BE LIABLE OR  RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. BECKETT’S AGGREGATE LIABILITY UNDER THIS WARRANTY OR WITH RESPECT TO ANY  PRODUCT COVERED HEREBY, UNDER ANY LEGAL THEORY, SHALL NOT EXCEED THE PURCHASE PRICE PAID FOR THE NONCONFORMING PRODUCT. THE  LIMITATIONS CONTAINED IN THIS PARAGRAPH SHALL NOT APPLY TO INJURY TO THE PERSON.
Some States do not allow the exclusion or limitation of incidental or consequential damages or exclusions or limitations on the duration of an implied warranty, so the above limitations or  exclusions may not apply to you. This warranty gives you specific legal rights and you may also have other rights that vary from State to State.

FOR YOUR RECORDS:
Date of Purchase __
Model Number
Name of Dealer

PLEASE KEEP RECEIPT IN CASE OF WARRANTY SERVICE.

BECKETT CORPORATION
Irving, Texas
www.beckettus.com
Toll Free: 1-888-232-5388
© 2019 BECKETT CORPORATION All Rights Reserved

SHOULD YOU ENCOUNTER ANY PROBLEMS WITH THIS PRODUCT,
CONTACT CUSTOMER CARE AT:
1-888-BECKETT
MONDAY THRU FRIDAY, BETWEEN THE HOURS OF 8:00 AM AND 5:00 PM CENTRAL STANDARD TIME. WE ASK THAT YOU DO NOT RETURN THIS PRODUCT TO THE  STORE BEFORE CONTACTING US. YOU CAN ALSO CONTACT US AT OUR WEB SITE: www.beckettus.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals