beckett MS601ULQ Mini Condensate Pump User Manual

June 11, 2024
beckett

MINI CONDENSATE PUMP
Models: MS601ULQ & MS602ULCQ

MS601ULQ Mini Condensate Pump

This MS60 Mini Condensate Pump is designed to be installed within Wall, Ceiling Suspended and Floor Mounted Mini-Split and Chilled Water Fan coil Air Conditioning Units with a maximum rating of 36,000 BTU (3 tons).
This unit is rated for 50% duty cycle. The Pump consists of two parts: Pump Unit and Sump/Detection Unit.

beckett MS601ULQ Mini Condensate Pump -

Pump Unit Supplied with:

  • A self-resetting thermal protector
  • An Earth Ground Connection

WARNING!

  • Do not pump any liquids other than water (Max temp 104 ºF)
  • Do not use this pump in explosive areas.
  • Do not run dry.
  • Do not handle unit with wet hands or while standing in water.
  • Do not connect to any voltage other than that shown on nameplate.
  • Always disconnect this unit from its electrical supply before servicing.
  • Connect safety switch for proper operation.
  • For Indoor use only.

IMPORTANT
The Pump must have an electricity supply that is independent to that of the air conditioner to ensure that it continues to operate if the refrigerating appliance breaks down.
NOTE: Before installation, thoroughly rinse the coil and the condensate collection tray to get rid of any foreign bodies and metal particles.

INSTALLATION
The Pump Unit must be installed, preferably in the vertical position, either within the air handling unit, in an adjacent gutter or in the false ceiling above the unit.

A space must be left around the Pump Unit in order to provide adequate cooling during prolonged operating periods. Do not insulate the Pump Unit.

  • If the mounting pad will not completely seat into the pump slot use a small amount of water.

Flow direction arrow on pump label

  • If the pump discharge tube is installed below the drain pan with no air gap the pump will have to re-prime itself each time which causes loud operation and shorter pump life. beckett MS601ULQ Mini Condensate Pump - discharge tube

Pump Power Supply
Connect Pump Live, Neutral and Earth terminals to the air handling unit’s power supply or to the main’s supply by means of wiring which complies with local National Standards. We suggest use of an interconnecting power cable (HO5 WF 3G 0.75 mm2), which must be fastened securely, to avoid inadvertent disconnection during installation and later servicing. This connection should be equipped with an electrical isolation device (2A Fused Spur – not included) to Live or Neutral.

Pump Safety Function

IMPORTANT: The Pump is equipped with a normally closed (NC) high water safety contact with a maximum rating of 3A/250V.
The connecting cable must be chosen accordingly.
This contact may be used to switch off the refrigeration system where there is a risk of condensate overflow (after thorough verification by the installer of the customer’s specific application and the resultant electric wiring diagram). This contact may also be used to connect an alarm.

The Detection Unit can be connected in 3 ways: (But unit must always be mounted level)beckett MS601ULQ Mini Condensate Pump - mounted
level

Venting Installation
Connect the 4mm plastic Vent Tube to the upper outlet of the Sump/Detection Unit.
The free end of air Vent Tube must be secured as high as possible and must remain free of kinks. The Vent Tube allows the air to be bled from the Detection Unit. You are advised to use the 4mm tube supplied. Its length allows the upper level of the tube to be slightly above the maximum level of the Condensate Drain Tray. In the event of an
alarm or defect, this avoids overspill.![beckett MS601ULQ Mini Condensate Pump

MAINTENANCE

Please ensure that your installation is set up accordingly by the direction of flow (on pump label).

Initial Operational Test:

  • First clean the condensate tray of any debris leftover from manufacture of unpacking of the air handling unit.
  • Pour water into the condensate collection tray.
  • Check that the Pump unit starts and then stops as the water level decreases.
  • Check Safety function by continuing to pour water until the safety switch triggers (cutting off the compressor, generating an audible or visual alarm, etc.).

Cleaning and Servicing:
The Sump/Detection Unit (and the filter) must be cleaned and serviced at regular intervals in accordance with the level of pollution existing within the Pump operating environment.

  • Remove the Sump/Detection Unit cover.
  • Remove the filter.
  • Clean the Sump/Detection Unit body, magnetic float and filter with solution of 95% water and 5% bleach.
  • Reinstall filter and float making sure ring magnet is on top.
  • Replace the filter and Sump/Detection Unit cover.
  • Test Pump Operation as explained in “Initial Operational Test”, above.
  • Ensure that the Vent Tube does not contain water. Do not use a longer tube than the one supplied.
  • Failure to follow these Instructions can lead to poor results, (tank overflow, high noise level, abnormal overheating, etc.) which are both inconvenient for the end user and costly for the installer!

A = SAFETY .83”±.08” (21mm±2mm)
B = START-UP .67”±.08” (17mm±2mm)
C = PUMP SHUTDOWN .43”±.08” (11mm±2mm)

ELECTRICAL CONNECTION

IMPORTANT NOTE: This diagram is for reference only. this pump must be installed by qualified engineers.

beckett MS601ULQ Mini Condensate Pump - IMPORTANT NOTE

  1. Please refer to the wiring diagram of the air conditioner manufacturer within the dashed box.
  2. Pump unit:
    L(Live) Brown
    N(Neutral) Blue
    E(Earth) Green
    N.C.(Normal closed) Orange
    COM(Common) Red

LIMITED WARRANTY

All Beckett pumps are warranted to the user against defective material and workmanship under normal use, for a period of 1 year from the date of purchase by the original purchaser. All other Beckett products are warranted to the user against defective material and workmanship for 3 months from the date of purchase. Replacement liability in all events is limited to the replacing or repairing at Beckett’s sole discretion of any part or parts, which are defective in material or workmanship. Proof of purchase is required on all claims in the form of invoice copy, sales ticket, etc.
APPLICATION: Warranty covers only properly installed and maintained units. Warranty is limited to applications pumping fresh water at temperatures of 32°-104°F (0°-40°C), with a pH range of 5 to 9. Beckett Corporation must approve other liquid applications and extreme temperature uses in advance in writing.
ADMINISTRATION: Warranty claims must be made by calling Beckett Corporation, Customer Service Dept., telephone 888-232-5388. Proof of Purchase is required and a $ 5.00 shipping and handling fee applies to all warranty replacements.
INSTALLATION and/or REMOVAL CHARGES: Warranty does not cover any costs associated with the installation or removal of products subject to warranty claims.
DISPOSITION: Beckett will make a good-faith effort for prompt disposition regarding any item in warranty, which proves to be defective. If products were damaged in transit, please file a claim with the carrier.
DISCLAIMER: Any oral statements about the product made by the seller, the manufacturer, the representatives or any other parties, do not constitute warranties, should not be relied upon by the user, and are not part of the contract for sale. Seller’s and manufacturer’s only obligation and buyer’s and user’s only remedy, shall be for the manufacturer to either replace and/or repair at the manufacturer’s sole discretion the Beckett product as described above. Neither seller nor the manufacturer shall be liable for any injury, loss or damage, direct, incidental or consequential (including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property, or any other incidental or consequential loss), arising from any cause whatsoever, no matter whether based upon warranty, contract, negligence or other misuse, and the buyer and user agree that no other remedy shall be available to them. Before using, the buyer and user shall determine the suitability of the product for the intended use, and assumes all risk and liability whatsoever in connection herewith. The warranty and remedy described in this limited warranty is an EXCLUSIVE warranty and remedy. IN LIEU of any other warranty or remedy, expressed or implied, which other warranties and remedies are hereby expressly EXCLUDED, including but not limited  to any implied warranty of MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. This Warranty gives buyer and user specific legal rights, and buyer and
user may also have other rights that vary from state to state. Some states do not allow the exclusion or limitations of incidental or consequential damages, so the above limitation or exclusion may not apply to you.

BECKETT CORPORATION
3321 E. Princess Ann Rd.
Norfolk, Va. 23502
www.beckettus.com
Toll Free: 888-232-5388
© 2021 BECKETT CORPORATION All Rights Reserved