Before You Begin

Read These Instructions Completely and Carefully

WARNING
Risk of electric shock

  • Disconnect power from the luminaire and follow proper lockout/tagout procedures before beginning installation or maintenance. Contact a qualified electrician for installation.
  • Risk of fire or electric shock. LED retrofit kit installation requires knowledge of luminaires electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.
  • Risk of fire or electric shock. Install this kit only in luminaires that have the construction features and dimensions shown in the photographs and/or drawings and where the input rating of the retrofit kit does not exceed the input rating of the luminaire.
  • Do not make or alter any open holes in an enclosure of wiring or electrical components during kit installation.
  • Warning – To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
  • Installers should not disconnect existing wires from lamp holder terminals. Instead, installers should cut existing lamp holder leads away from the lamp holder and make 6 electrical connections to the lamp holder lead wires by employing applicable connectors.
  • This retrofit kit is accepted as a component of a luminaire where the suitability of the combination shall be determined by authorities having jurisdiction.
  • This device is not intended for use with emergency exits. Added weight of the device may cause instability of a free standing portable luminaire. Use only with a portable table lamp that is provided with a shade.
  • This device is not intended for use with dimmers.
  • This device is suitable for enclosed fixtures, however ensure that there is adequate space around the device for heat dissipation.
  • The modified fixture can no longer operate as was originally intended.
  • Retrofit lamps require 100V-277V input voltage. The installer is responsible to determine whether the proper voltage is run to the luminaire being serviced.
  • Retrofit lamps operate on line voltage and require all ballasts, capacitors and starters to be bypassed and/or removed.

Upgrade Instructions

  • STEP 1: Disconnect power from the luminaire and follow proper lockout/tagout procedures before beginning installation or
    maintenance.

  • STEP 2: Remove the existing lamp(s). Dispose of the lamp(s) per local requirements.

  • STEP 3: Disconnect and remove the existing ballast, capacitor and ignitor. Dispose of the components per local requirements. STEP 4: Connect the Line Live wire (Line/Hot) to the center contact (eyelet) of the lamp holder.

  • STEP 5: Connect Line Neutral wire (Common) to the shell of the lamp holder.

  • STEP 6: Insert and screw in the LED Retrofit lamp into the lamp holder. Rotate the lamp so that lamp lens is oriented towards the fixture lens. (Figure 1)

  • STEP 7: Attach one end of the safety cable to the lamp and the opposite end of the safety cable to the enclosure. (Figure 2) STEP 8: Attach the Lamping Replacement Label which is provided with the retrofit lamp to the fixture so it shall be visible during relamping.

  • STEP 9: Close the wiring compartment. Watch to be sure the wires are not pinched, bound or crimped when closing the compartment.

  • STEP 10: Switch on the power.

Minimum Required Lamp Compartment Dimensions

For 54W LED Retrofit lamps

Note: It is the customer’s repsonsibility to verify that the lamp compartment meets the minimum required lamp compartment dimensions of 4.9” x 10.0” (125mm x 255mm).

For 115W LED Retrofit lamps
Note: It is the customer’s repsonsibility to verify that the lamp compartment meets the minimum required lamp compartment dimensions of 5.9” x 12.6” (150mm x 320mm).VENTURE-LIGHTING-AK0005-B-LED-Retrofit-Lamp-
fig-1

Wiring Diagrams

Replacing Self Ballasted CFL Lamp

VENTURE-LIGHTING-AK0005-B-LED-Retrofit-Lamp-fig-2

Replacing HPS/HID Lamp

VENTURE-LIGHTING-AK0005-B-LED-Retrofit-Lamp-fig-3

800-451-2606 6675 Parkland Blvd., Suite 100 Solon, Ohio 44139 USA E-mail: [email protected] VentureLighting.com

  • 2022 Venture Lighting International
  • Venture Lighting is a registered trademarks of Venture Lighting International.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

VENTURE LIGHTING User Manuals

Related Manuals