Before You Begin

Read These Instructions Completely and Carefully

Upgrade Instructions

STEP 1: Disconnect power from the luminaire and follow proper lockout/Tagout procedures before beginning installation or maintenance.
STEP 2: Remove the existing luminaire. Dispose of the lamp(s) and ballast(s) per local requirements.
STEP 3: Each fixture is supplied with a carabiner (1). Place the carabiner through the eyelet of the eyebolt (2) on top of the fixture.
STEP 4: Attach the carabiner to a secure structure.
STEP 5: Connect the fixture input leads to the supply wire leads.
STEP 6: Each fixture is supplied with 1-10V DC dimming leads.
– If dimming is not needed, nothing needs to be done.
NOTE: Do NOT connect the dimming leads together.
This will cause the fixture to not operate as desired.

– If dimming is desired:
a) Connect the “+” supply lead to the “+” connection lead on the fixture.
b) Connect the “-” supply lead to the “-” connection lead on the fixture.
NOTE: The polarity of the dimming leads is important.
Improper connection will cause the fixture to not operate as desired.

Wiring Diagram

VENTURE LIGHTING HB64152 300W White LED Highbay Light - Wiring Diagram
3

STEP 7: Loop the safety cable through the opening on the side of the fixture as shown.
Attach the opposite end of the safety cable to a secure structure. (3)
STEP 8: Power can now be restored to the fixture.

VENTURE LIGHTING HB64152 300W White LED Highbay Light - Wiring Diagram
2

Reflector Installation

  1. Remove 3 of the screws which hold down the lens (remove every other screw).
  2. Place the reflector onto the fixture and secure to the fixture with the 3 longer screws supplied with the reflector.

VENTURE LIGHTING HB64152 300W White LED Highbay Light - Wiring Diagram
3

Lens Installation

VENTURE LIGHTING HB64152 300W White LED Highbay Light -
Install

There is one arrow on the edge of the 50° and 90° lenses, and two locating columns on the back.
Match them with the arrow and two small holes on the PCB board.

Safety Cable Assembly

VENTURE LIGHTING HB64152 300W White LED Highbay Light -
Assembly.

WARNING

Risk of fire and electric shock

  • Disconnect power from the luminaire and follow proper lockout/Tagout procedures before beginning installation or maintenance.
    Contact a qualified electrician for installation.

  • Venture Lighting’s High Bay Fixture installation requires knowledge of luminaire electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.

  • To prevent wiring damage or abrasion, do not expose wiring to the edges of sheet metal or other sharp objects.

  • Do not make or alter any open holes in a wiring enclosure or electrical component during installation.

  • Do not dismantle the fixture without Venture Lighting’s approval.

  • If the external flexible cable of the luminaire is damaged, it should only be replaced by the supplier, a service agent, or a Venture Lighting-approved qualified person.

CAUTION

  • Suitable for use in wet locations only.
  • Venture Lighting’s High Bay Fixture must be operated within an ambient fixture temperature range of -30° to 40°C.

800-451-2606
7905 Cochran Rd., Suite 300
Glenwillow, Ohio 44139 USA
E-mail: Venture_Lighting@VentureLighting.com
VentureLighting.com

http://www.venturelighting.com/

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

VENTURE LIGHTING User Manuals

Related Manuals