TROX MFPCR Mini Pleat Filters Instruction Manual
- June 11, 2024
- TROX
Table of Contents
The art of handing air
Installation and maintenance manual
MFPCR
Mini Pleat filters
Important notes
Information on the installation manual
This manual enables operating or service personnel to correctly install the
product described below and to use it safely and efficiently.
It is essential that these individuals read and fully understand this manual
before starting any work.
The basic prerequisite for safe working is to comply with the safety notes and
all instructions in this manual.
The local regulations for health and safety at work and general safety
regulations also apply.
Safety
Correct use
Filter insert MFPCR is used as a prefilter or final filter in ventilation and
air conditioning systems to separate fine dusts from the air.
Airflow velocity and nominal volume flow rate
If the filter is used correctly and if the nominal volume flow rate is
maintained, the airflow velocity on the filter will usually not exceed the
maximum airflow velocity (see technical data), not even when the final
differential pressure is reached.
Use test and monitoring systems, e.g. differential pressure monitors or flow
meters, to ensure that the nominal volume flow rate is maintained.
Qualified staff
The work described in this manual has to be carried out by individuals with
the qualification, training, knowledge and experience described below:
Properly trained person
Properly trained persons are trained individuals who understand any potential
hazards related to the work under consideration, and who recognise and avoid
any risks involved. Training is provided by the HVAC contractor when the
system is handed over.
Properly trained persons are responsible for cleaning the unit, and for
carrying out functional tests, regular checks and smaller adjustments.
Personal protective equipment
Personal protective equipment is equipment that protects the user against
health or safety risks at work. Personal protective equipment must be worn for
various types of work; the protective equipment required is listed in this
manual together with the description of each type of work.
Supply package, transport and storage
Upon delivery, carefully remove the packaging and check the unit for transport
damage and completeness. Then put the product back into its packaging.
Supply package:
Filter MFPCR
Transport
Do not remove the protective wrapping until just before installation.
Storage
Please note:
-
Store the product only in its original packaging
-
Protect the product from the effects of weather
-
Protect the product from humidity, dust and
contamination -
Storage temperature: -10 °C to 50 °C.
-
Relative humidity: 95% max., no condensation
Technical data
Product description | Mini Pleat filter |
---|---|
Name | MFPCR |
Filter class according to ISO 16890/EN 1822 | see product sticker |
Nominal volume flow rate
Initial differential pressure|
Airflow velocity at nominal volume flow rate| Calculated from nominal volume
flow rate and cross-sectional area ::* example below
Max. rel. humidity| 90%
Ambient temperature range| PLA: -F51) to +60 °C GAL: +51) to +90 °C
Filter medium| Micro glass fibre paper
Filter frame material| STA = stainless steel
ALx = extruded aluminium
sections of various depths
- There is a risk of ice buildup on the filter with temperatures below +5 °C.
Be sure to prevent this, e.g. with a filter preheater.
Calculation example
qv – 905 m³/h
B – 915 mm (0.915 m)
H – 610 mm (0.61 m)
Result: V = 0.45 m/s
Filter change, inserting filters
Before installation
- Be sure to install the filter only in a place that is suitable.
- Unpack the filter outside of the hazardous area.
– Handle the filter with care to not damage the filter medium.
Hold the filter only by the edges.
– Check the filter for external damage and completeness, Ä Chapter 3 ‘Supply package, transport and storage’ on page 1. Do not install a damaged or incomplete filter.
Installation
Personnel:
-
Properly trained person
Protective equipment: -
Industrial safety helmet
-
Light respiratory protection
-
Protective gloves
Before you start changing filters, switch off the ventilation and air conditioning system.
- Remove the existing filter.
- Then clean the system as required.
- Insert the new filter and secure it.
Be sure to not damage the filter medium: Handle the filter with care and only touch the frame.
Maintenance
Maintenance applies mainly to the filter element.
Check the filter regularly and replace it, if necessary.
The service life of a filter depends mainly on how contaminated the air is.
Check the filter in intervals that are short enough so that you can anticipate
any defects or problems before they actually occur.
Replace the filter immediately if any of the following is true:
- the filter is defective
- there are hygiene problems (micro-organisms, fungal spores, odours, etc.)
- the maximum filter usage time has been reached (VDI 3803, part 4)
- the defined final differential pressure has been reached
For more recommendations regarding the maximum usage time see SWKI 2003-5, VDI 6022, VDI 3803 and EN 13053.
You may replace a filter even before the defined final differential pressure has been reached if this is more economic.
Disposal
ENVIRONMENT!
Risk of harm to the environment due to the incorrect handling of hazardous
materials and substances.
Filters and cleaning materials that have been contaminated with bacterial,
toxic or radioactive particles are considered hazardous waste and have to be
disposed of by an authorised business in compliance with local regulations.
Disposing of filter elements with household waste is allowed only in the
following cases:
- For unused filter elements
- For filter elements that have been exposed only to atmospheric outdoor air
Ordering replacement filters
To ensure permanent protection from particulate matter and other pollutants we
recommend using only original TROX filters.
Original TROX filters carry a sticker on the frame with information on how to
order replacements.
To avoid downtime of the ventilation and air conditioning system, we recommend you to always have the required filters in stock.
To order replacement filters: https://www.trox.de/onlineshop/filtergeraete- undfilterelemente-1df986693c21980d
TROX GmbH
Heinrich-Trox-Platz
47504 Neukirchen-Vluyn Germany
Phone: +49 (0) 2845 2020
Fax: +49 (0) 2845 202265
E-mail:trox-de@troxgroup.com
Internet:http://www.troxtechnik.com
References
Read User Manual Online (PDF format)