TROX Type AFG Floor Grilles Within Raised Access Floors Datasheet
- June 11, 2024
- TROX
Table of Contents
- TROX Type AFG Floor Grilles Within Raised Access Floors Datasheet
- Floor Grilles for Installation into Raised Access Floors
- Optional Equipment and Accessories
- Product Usage Instructions
- General information
- Technical data
- Basic information and nomenclature
- Quick sizing
- Order code
- Dimensions and weight
- Specification text
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
TROX Type AFG Floor Grilles Within Raised Access Floors Datasheet
Floor Grilles for Installation into Raised Access Floors
The Type AFG floor grilles are heavy and extra heavy-duty floor grilles made of aluminum with fixed horizontal blades. These single ventilation grilles are suitable for raised access floor systems with a nominal size of 600 x 600 and a volume flow rate range of 0 – 530 l/s or 0 – 1908 m3/h. The grille face is made of aluminum with a powder-coat finish and a front border of 6mm with 6mm wide blades. The grilles are suitable for floor tile depths between 25mm and 50mm.
Optional Equipment and Accessories
Attachments for volume flow rate balancing are available.
Product Usage Instructions
The AFG floor grilles can replace 600mm square floor tiles with depths from
25mm up to a maximum of 50mm. The F series floor grilles can be used in
commercial or industrial settings to provide mixed-flow ventilation for
comfort and overall room ventilation.
When using the floor grilles, please check the floor system and confirm the
stringer width to ensure proper installation. Attachments for volume flow rate
balancing are available as optional equipment.
General information
Application
- Floor grille of Type AFG as supply air for comfort zones and industrial zones
- For variable and constant volume flows
- For supply air to room air temperature differences from -12 to ÷4 K
For installation in raised access floors
Variants
-
AFG-A: Floor grille for pressurized floor void
-
AFG-AG: Floor grille with rear-mounted volume control damper)
Construction features -
6 mm wide mitred border
-
6mm wide blades for straight (0°) air discharge
Materials and surfaces -
Border and blades made of aluminum
-
P2: Border and blades powder-coated, RAL9006:30%
-
P4: Border and blades powder-coated, RAL9005:20%
-
N1: Border and blades powder-coated, with nylon reinforcing RAL9005
Parts and characteristics -
6mm wide welded mitered border sections
-
Fixed horizontal blades
-
Vertical lateral mullions
Nominal sizes -
600mm × 600mm
Attachments -
AG: For volume flow rate balancing
Special Characteristics -
Fixed blades
-
Welded front border sections
Installation and commissioning -
Installation preferably in raised access floor systems with a minimum depth of 25mm and a maximum depth of 50mm
Standards and guidelines -
The sound power level of the air-regenerated noise measured according to EN ISO 5135
-
Structural classification tested according to BS EN 13264:2001 (Heavy & Extra Heavy)
Maintenance -
Maintenance-free as construction and materials are not subject to wear
-
Inspection and cleaning to VDI 6022
Technical data
Nominal size | 600 mm x 600mm |
---|---|
Nominal frame depth | 25mm up to 50mm |
Total open area | 0.152m2 |
Free area | 42% |
Maximum volume flow rate, with L WA max. 50 dB(A) without attachments |
__530 l/s or 1908 m3/h
Basic information and nomenclature
Functional description
Type AFG Heavy / Extra Heavy duty floor grilles are air terminal devices for
the supply air of ventilation and air conditioning systems.
They direct the supply air into the room from low-level floor void supply
systems. The result is mixed flow ventilation in comfort zones and industrial
zones, with good overall room ventilation.
Designed for use within commercial or industrial applications where prolonged foot traffic or rolling loads may be expected such as offices, atrium areas or data centres. TROX AFG series floor grilles can replace 600mm square floor tiles with depths from 25mm up to a maximum of 50mm and exceeds the requirements of BS-EN 13264:2001 heavy & extra heavy structural classification.
Nomenclature
-
Lwa [dB(A)]
The sound power level of the air-regenerated noise -
V [m°/h] and [I/s]
Volume flow rate -
Ap, [Pa]
Floor void static pressure -
Ap, [Pa]
Total differential pressure
Quick sizing
Technical data
Volume flow rates apply to a nominal grille size of 600mm x 600mm, max. the
sound power level of their-regenerated noise of 50 dB(A) with an open damper
unit (unrestricted airflow) and maximum 30Pa pressure drop.
Thow length [Is] provided to a maximum time average air velocity [V J of
0.5m/s with supply air temperature differential of -10°K.
AFG-A .-AG Quick sizing – sound power level and total differential pressure
Nominal size
| ****
\I
| Damper blade position| Discharge height
---|---|---|---
100%| 50%
Ap t| L WA| Ap t| L WA| L S
l s| m3 h| Pa| dB(A)| Pa| dB(A)| m
600×600
| 100| 360| 1| <15| 1| <15| 0 7
125| 450| 1| <15| 2| <15| 0 8
150| 540| 2| <15| 3| <15| 0 9
175| 630| 3| <15| 4| 18| 1 0
200| 720| 4| 18| 5| 22| 1 2
225| 810| 5| 22| 6| 26| 1 3
250| 900| 6| 25| 8| 28| 1 5
275| 990| 8| 28| 10| 32| 1 7
300| 1080| 9| 31| 12| 35| 1 9
325| 1170| 11| 34| 14| 37| 2 1
350| 1260| 13| 36| 16| 40| 2 4
375| 1350| 14| 38| 18| 42| 2 6
400| 1440| 16| 41| 21| 44| 2 8
425| 1530| 18| 43| 23| 46| 3 1
450| 1620| 21| 44| 26| 48| 3 2
475| 1710| 23| 46| 29| 50| 3 7
500| 1800| 25| 48| 32| 52| 4 0
525| 1890| 28| 50| 35| 53| 4 3
Order code
-
Туре
AFG Floor grille -
Attachments
A Without (grille face only)
AG Damper unit, opposed action blades -
Nominal size
600 x 600 -
Frame depth
25 Standard
XX 26mm to 50mm (1mm increments) -
Frame Construction
2 Stringer width 0-40mm -
Exposed surface
P2 Powder-coated, RAL9006:30%
P4 Powder-coated, RAL9005:20%
N1 Powder-coated, with nylon reinforcing, RAL9005
Order example
AFG-AG/600×600/0/35/2/P2
- Attachments Damper unit, opposed action blades
- Nominal size 600 × 600
- Floor tile depth 35mm
- Stringer width 40mm
- Exposed surface Powdercoat, RAL9006:30% (silver grey)
Dimensions and weight
Front border and blade
Optional shim factory installed in each corner where total frame depth [‘X’1 >
25mm.
Frame depth [X] is the depth from the finished pedestal bearing surface to the
floor level and should be checked before order.
AFG-A …. AG
Optional ‘AG’ opposed blade volume control damper factory installed to rear of
AFG floor grille.
Damper operation is possible through face of grille.
NOTE: Type AFG suitable for a maximum pedestal head diameter of 90mm.
Type AFG suitable for maximum stringer width 40mm (..-2). Please check floor
system and confirm at the point of order.
Weight
Grille type
| ****
Weight
---|---
kg
AFG- A| 11 5
AFG- AG| 13 5
Specification text
Standard text
This specification text describes the general properties of the product Extra
heavy-duty construction floor grille for computer rooms for supply air. Edge
frames with welded mitered corners suitable for pedestal mounting (maximum
090mm and stringer widths 0–40mm. Height between pedestal face and face of
grille to be selected with permanent factory-fitted shims as necessary.
Options: opposed blade volume control damper assembly. The sound power level
of the air-regenerated noise was measured according to EN ISO 5135.
Parts and characteristics
- 6mm wide welded mitred border sections
- Fixed horizontal blades Vertical lateral mullions
Materials and surfaces
- Border and blades made of aluminium
- P2: Border and blades powder-coat RAL9006:30%
- P4: Border and blades powder-coat RAL9005:20%
- N1: Border and blades powder-coat RAL9005, with nylon reinforcing
Technical data
- Nominal size: 600 × 600
- Nominal frame depth: 25mm up to 50mm, (1mm increments)
- Total open area: 0.152m?
- Free area: 42%
- Maximum volume flow rate (supply air), at LWA max. 50 dB(A) without attachments: 530 l/s or 1908 m’/h
Order options
-
Туре
AFG Floor grille -
Attachments
A Without (grille face only)
AG Damper unit, opposed action blades -
Nominal size
600 x 600 -
Frame depth
25 Standard
XX 26mm to 50mm (1mm increments) -
Frame Construction
2 Stringer width 0-40mm -
Exposed surface
P2 Powder-coated, RAL9006:30%
P4 Powder-coated, RAL9005:20%
N1 Powder-coated, with nylon reinforcing, RAL9005
Read User Manual Online (PDF format)