TELE E3ZI20 Timers – Asymmetric Flasher
Timers – Asymmetric flasher
- series ENYA
- 2-time multifunction
- 7 time ranges
- Wide input voltage range
- 2 change-over contacts
- Width 35mm
- Installation design
Technical data
Functions
The function has to be set before connecting the relay to the supply voltage.
- Ip Asymmetric flasher pause first
- Ii Asymmetric flasher pulse first
- ER ON delay and OFF delay with control contact
- EWu ON delay single shot leading edge voltage controlled
- EWs ON delay single shot leading edge with control contact
- WsWa Single shot leading and single shot trailling edge with control contact
- Wt Pulse sequence monitoring
Time ranges
- Time range Adjustment range
- 1s 50ms 1s
- 10s 500ms 10s
- 1min 3s 1min
- 10min 30s 10min
- 1h 3min 1h
- 10h 30min 10h
- 100h 5h 100h
Indicators
- Green LED U/t ON: indication of supply voltage
- Green LED U/t slow flashing: indication of time period t1
- Green LED U/t fast flashing: indication of time period t2
- Yellow LED ON/OFF: indication of relay output
Mechanical design
Self-extinguishing plastic housing, IP rating IP40 Mouted on DIN-Rail TS 35 according to EN 60715 Mounting position: anyShockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20 Tightening torque: max. 1Nm Terminal capacity:
- 1 x 0.5 to 2.5mm² with/without multicore cable end
- 1 x 4mm² without multicore cable end
- 2 x 0.5 to 1.5mm² with/without multicore cable end
- 2 x 2.5mm² flexible without multicore cable end
Input circuit
- Supply voltage: 12 to 240V a.c./d.c.
- Terminals: A1(+)- A2
- Tolerance: -10% to +10%
- Rated frequency: 48 to 63Hz
- Rated consumption: 6VA (2W)
- Duration of operation: 100%
- Reset time: 100ms
- Residual ripple of d.c.: –
- Drop-out voltage : >30% of supply voltage
- Overvoltage category : III (in accordance with IEC 60664-1)
- Rated surge voltage: 4kV
Output circuit
2 potential free change over contacts
- Rated voltage: 250V a.c.
- Switching capacity: 2000VA (8A / 250V)
- Fusing: 8A fast acting
- Mechanical life: 20 x 106 operations
- Electrical life: 2 x 105 operations at 1000VA resistive load
- Switching frequency: max. 6/min at 1000VA resistive load (in accordance with IEC 60947-5-1)
- Overvoltage category: III (in accordance with IEC 60664-1)
- Rated surge voltage: 4kV
Control input
- Input not potential free: terminals A1-B1
- Loadable: yes
- Max. line length: 10m
- Trigger level (sensitivity): automatic adaption to supply voltage
- Max. control pulse length : d.c. 50ms / a.c. 100ms
Accuracy
- Base accuracy: ±1% of maximum scale value
- Adjusting accuracy: ≤5% of maximum scale value
- Repetition accuracy: <0.5% or ±5ms
- Voltage influence: –
- Temperature influence: ≤0.01% / °C
Ambient conditions
- Ambient temperature : -25 to +55°C
- Storage temperature: -25 to +70°C
- Transport temperature: -25 to +70°C
- Relative humidity: 15% to 85% (in accordance with IEC 60721-3-3 class 3K3)
- Pollution degree: 2 (in accordance with IEC 60664-1)
Weight
- Single packing: 106g
Functions
Asymmetric flasher pause first (lp)
When the supply voltage U is applied, the set interval t1 begins (green LED
U/t flashes slowly). After the interval t1 has expired, the output relay R
switches into on-position (yellow LED illuminated) and the set interval t2
begins (green LED U/t flashes fast). After the interval t2 has expired, the
output relay switches into off-position (yellow LED not illuminated). The
output relay is triggered at the ratio of t1:t2 until the supply voltage is
interrupted.
Asymmetric flasher pulse first (li)
When the supply voltage U is applied, the output relay R switches into on-
position (yellow LED illuminated) and the set interval t1 begins (green LED
U/t flashes slowly). After the interval t1 has expired, the output relay
switches into off-position (yellow LED not illuminated) and the set interval
t2 begins (green LED U/t flashes fast). After the interval t2 has expired, the
output relay switches into on-position (yellow LED illuminated). The output
relay is triggered at the ratio of t1:t2 until the supply voltage is
interrupted.
ON delay and OFF delay with control contact (ER)
The supply voltage U must be constantly applied to the device (green LED U/t
illuminated). When the control contact S is closed, the set interval t1 begins
(green LED U/t flashes slowly). After the interval t1 has expired, the output
relay R switches into on-position (yellow LED illuminated). If the control
contact is opened, the set interval t2 begins (green LED U/t flashes fast).
After the interval t2 has expired, the output relay Switches into off-position
(yellow LED not illuminated). If the control contact is opened before the
interval t1 has expired, the interval already expired is erased and is
restarted with the next cycle.
ON delay and single shot leading edge voltage controlled (EWu)
When the supply voltage U is applied, the set interval t1 begins (green LED
U/t flashes slowly). After the interval t1 has expired, the output relay R
switches into on-position (yellow LED illuminated) and the set interval t2
begins (green LED U/t flashes fast). After the interval t2 has expired, the
output relay switches into off-position (yellow LED not illuminated). If the
supply voltage is interrupted before the interval t1+t2 has expired, the
interval already expired is erased and is restarted when the supply voltage is
next applied.
ON delay and single shot leading edge with control contact (EWs)
The supply voltage U must be constantly applied to the device (green LED U/t
illuminated). When the control contact S is closed, the set interval t1 begins
(green LED U/t flashes slowly). After the interval t1 has expired, the output
relay R switches into on-position (yellow LED illuminated) and the set
interval t2 begins (green LED U/t flashes fast). After the interval t2 has
expired, the output relay switches into off-position (yellow LED not
illuminated). During the interval, the control contact can be operated any
number of times. A further cycle can only be started when the cycle run has
been completed.
Single shot leading and single shot trailing edge with control contact
(WsWa)
The supply voltage U must be constantly applied to the device (green LED U/t
illuminated). When the control contact S is closed, the output relay R
switches into on-position (yellow LED illuminated) and the set interval t1
begins (green LED U/t flashes slowly). After the interval t1 has expired, the
output relay R switches into off-position (yellow LED not illuminated). If the
control contact is opened, the output relay again switches into on-position
(yellow LED illuminated) and the set interval t2 begins (green LED U/t flashes
fast). After the interval t2 has expired the output relay switches into off-
position (yellow LED not illuminated). During the interval, the control
contact can be operated any number of times.
Pulse sequence monitoring (Wt)
When the supply voltage U is applied, the set interval t1 begins (green LED
U/t flashes slowly) and the output relay R switches into on-position (yellow
LED illuminated). After the interval t1 has expired, the set interval t2
begins (green LED U/t flashes fast). So that the output relay R remains in on-
position, the control contact S must be closed and opened again within the set
interval t2. If this does not happen, the output relay R switches into off-
position (yellow LED not illuminated) and all further pulses at the control
contact are ignored. To restart the function the supply voltage must be
interrupted and reapplied.
Connections
Dimensions
Ordering information
Type | Functions | Supply voltage | Part. No. (PQ 1) |
---|---|---|---|
E3ZI20 12-240V a.c./d.c. | lp, li, ER, EWu, WsWa, Wt | 12-240V a.c./d.c. | 111101 |
- RELEASE 2012/07