tele E1ZM Multi Function Timer User Guide
- June 4, 2024
- TELE
Table of Contents
tele E1ZM Multi Function Timer
ENYA series
Multifunction
Up to 7 functions 7 time ranges Wide input voltage range 1 change over contact
Width 17.5 mm Installation design
Technical data
Functions
The function has to be set before connecting the relay to the supply voltage.
E ON delay
R OFF delay
Ws Single shot leading edge with control input
Wa Single shot trailing edge with control input
Es ON delay with control input
Wu Single shot leading edge voltage controlled
Bp Flasher pause first
Function sets of the distinct types are according to table ordering information or printing on the unit.
Time ranges
Indicators
- Green LED U/t ON: indication of supply voltage
- Green LED U/t flashes: indication of time period
- Yellow LED R ON/OFF: indication of relay output
Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-rail TS 35 according to EN 60715
Mounting position: any
Shockproof terminal connection according to VBG 4 (PZ1 required),IP rating
IP20
Tightening torque: max. 1Nm
Terminal capacity:
- 1 x 0.5 to 2.5mm² with/without multicore cable end
- 1 x 4mm² without multicore cable end
- 2 x 0.5 to 1.5mm² with/without multicore cable end
- 2 x 2.5mm² flexible without multicore cable end
Input circuit
Supply voltage: terminals A1(+)-A2
- E1Z… 12-240VAC/DC: 12 to 240V a.c./d.c.
- Tolerance: 12V -10% to 240V +10%
- E1Z… 24-240VAC/DC: 24 to 240V a.c./d.c.
- Tolerance: 24V -15% to 240V +10%
- Rated consumption: 4VA (1.5W)
- Rated frequency: a.c. 48 to 63Hz
- Duty cycle: 100%
- Reset time: 100ms
- Residual ripple for d.c.: 10%
- Drop-out voltage: >30% of minimum rated supply voltage
- Overvoltage category: III (in accordance with IEC 60664-1)
- Rated surge voltage: 4kV
Output circuit
1 potential free change over contact
-
Contact material: AgNi
-
Rated voltage: 250V a.c.
-
Switching capacity: 2000VA (8A / 250V a.c.)
-
Fusing: 8A fast acting
-
Mechanical life: 20 x 106 operations
-
Electrical life: 2 x 105 operations at 1000VA resistive load
-
Switching frequency: max. 6/min at 1000VA resistive load
(in accordance with IEC 60947-5-1) -
Overvoltage category: III (in accordance with IEC 60664-1)
-
Rated surge voltage: 4kV
Control input
- Input not potential free: terminals A1-B1
- Loadable: yes
- Max. line length: 10m
- Trigger level (sensitivity): automatic adaption to supply voltage
- Min. control pulse length: d.c. 50ms / a.c. 100ms
General data
-
Degree of protection: Basic insulation
-
Insulation test voltage:
Supply circuit – Output circuit: 1680V -
Interference immunity: Class A
-
Prospective current value: 1000A / 8A
Accuracy
-
Base accuracy: ±1% of maximum scale value
-
Adjustment accuracy: <5% of maximum scale value
-
Repetition accuracy: <0.5% or ±5ms
Voltage influence: – -
Temperature influence: ≤0.01% / °C
Ambient conditions
- Ambient temperature: -25 to +55°C
- Storage temperature: -25 to +70°C
- Transport temperature: -25 to +70°C
- Relative humidity: 15% to 85% (in accordance with IEC 60721-3-3 class 3K3)
- Pollution degree: 2 (in accordance with IEC 60664-1)
Weight
- Single packing: 72g
- Package 10pcs: 670g per Package
Functions
ON delay (E)
When the supply voltage U is applied, the set interval t begins (green LED U/t
flashes). After the interval t has expired (green LED U/t illuminated) the
output relay R switches into on-position (yellow LED illuminated). This status
remains until the supply voltage is interrupted.
If the supply voltage is interrupted before the expiry of the interval t, the
interval already expired is erased and is restarted when the supply voltage is
next applied.
OFF delay (R)
The supply voltage U must be constantly applied to the device (green LED U/t
illuminated). When the control contact S is closed, the output relay R
switches into on-position (yellow LED illuminated). If the control contact is
opened, the set interval t begins (green LED flashes). After the interval t
has expired (green LED U/t illuminated) the output relay switches into off-
position (yellow LED not illuminated). If the control contact is closed again
before the interval t has expired, the interval already expired is erased and
is restarted.
Single shot leading edge with control input (Ws)
The supply voltage U must be constantly applied to the device (green LED U/t
illuminated). When the control contact S is closed, the output relay R
switches into on-position (green LED U/t illuminated) and the set interval t
begins (green LED U/t flashes). After the interval t has expired (green LED
U/t illuminated) the output relay switches into off-position (yellow LED not
illuminated). During the interval, the control contact can be operated any
number of times. A further cycle can only be started when the cycle run has
been completed.
Single shot trailling edge with control input (Wa)
The supply voltage U must be constantly applied to the device (green LED U/t
illuminated). Closing the control contact S has no influence on the condition
of the output R. When the control contact is opened, the output relay switches
into on-position (yellow LED illuminated) and the set interval t begins (green
LED U/t flashes). After the interval t has expired (green LED U/t
illuminated), the ouput relay switches into off-position (yellow LED not
illuminated). During the interval, the control contact can be operated any
number of times. A further cycle can only be started when the cycle run has
been completed.
ON delay with control input (Es)
The supply voltage U must be constantly applied to the device (green LED U/t
illuminated). When the control contact S is closed, the set interval t begins
(green LED U/t flashes). After the interval t has expired (green LED U/t
illuminated) the output relay R switches into on-position (yellow LED
illuminated). This status remains until the control contact is opened again.
If the control contact is opened before the interval t has expired , the
interval already expired is erased and is restarted with the next cycle.
Single shot leading edge voltage controlled (Wu)
When the supply voltage U is applied, the output relay R switches
into on-position (yellow LED illuminated) and the set interval t begins
(green LED U/t flashes). After the interval t has expired (green LED U/t
illuminated) the output relay switches into off-position (yellow LED not
illuminated). This status remains until the supply voltage is interrupted. If
the supply voltage is interrupted before the interval t has expired, the
output relay switches into off-position. The interval already is erased and is
restarted when the supply voltage is next applied.
Flasher pause first (Bp)
When the supply voltage U is applied, the set interval t begins (green LED U/t
flashes). After the interval t has expired, the output relay R switches into
on-position (yellow LED illuminated) and the set interval t begins again.
After the interval t has expired, the output relay switches into off-position
(yellow LED not illuminated).
The output relay is triggered at a ratio of 1:1 until the supply voltage is
interrupted.
Connections
with control input
without control input
Dimensions
Ordering information
Type| Functions| Supply voltage| Art. No. (PQ 1)| Art.
No. (PQ 10)
---|---|---|---|---
E1ZM10 12-240V AC/DC| E, R,Ws, Wa, Es, Wu, Bp| 12-240V a.c./d.c.| 110100|
110100A
E1ZM10 24-240V AC/DC| E, R,Ws, Wa, Es, Wu, Bp| 24-240V a.c./d.c.| 110200|
110200A
E1ZMQ10 24-240V AC/DC| E, R, Wu, Bp| 24-240V a.c./d.c.| 110202| 110202A
E1Z1E10 24-240V AC/DC| E| 24-240V a.c./d.c.| | 110204A
E1Z1R10 24-240V AC/DC| R| 24-240V a.c./d.c.| | 110205A
TELE Haase Steuergeräte Ges.m.b.H. Vorarlberger Allee 38
AT-1230 Vienna, AUSTRIA
RELEASE 2017/01
Subject to alterations and errors
www.tele-online.com