CBI CM-MI 125 Automatic Switch Control Unit User Manual
- June 9, 2024
- cbi
Table of Contents
Manual or Fully Automatic Transfer System
OPERATOR’S MANUAL
ATS-385
Automatic Transfer Switch Control Unit
CM-MI 125 Automatic Switch Control Unit
Frame| Circuit Breaker| Selectable Amps| System is frame &
size dependent, eg. the selection must be from the same frame size. Select any
MCCB combination 230 – 400V Network
---|---|---|---
CM-M1 125| G37D| 15 – 125 A
CM-MI 250| F37D| 150 – 250A
CM-MI 400| K5OD| 250 – 400 A
CM-MI 800| L65D| 500 – 800A
- MCCB styled electrical change over with manual option
- Easy to read mechanical status. Compatible with most ATS controllers
- Fully built and pre-wired to accept mains and controller interface
- Customer selected combinations
- Factory assembled and tested
- Factory fitted combined Busbars on load side
- Electrical locking system with factory fitted MCCB, Aux Circuit
- 3P System standard (4 Pole optional*)
Motor specifications
200 – 240 VAC (50 / 60Hz)
Uzi AC 750V
Ute 220V
- Please select breakers for assembly
**Complete System Assembly***
INTRODUCTION
Preliminary Comments and Safety Precautions
The manual covers installation, operation and maintenance of the ATS-385 Automatic Transfer Switch PLC Controller. This manual is for use by authorized and qualified personnel only.
WARNING
High voltage will cause severe injury or death
Overview
Transfer switches protect critical electrical loads against loss of power. A_ standby (emergency) generator backs up the normal grid power. The transfer switch connects Normal and Standby source supply to the load. When power is lost from Normal source, the transfer switch transfers the load to the standby source. After power is restored, the ATS will transfer the load back to Normal source.
Product Overview
The ATS-385 is a multifunction programmable logic automatic transfer switch controller. Suitable for 1 phase and 3 phase system, including all necessary monitoring and protections.
Controller’s features :
- Microprocessor based & Polycarbonate panel.
- Membrane switch button designed. *1
- Compact size with user-friendly LED display.
- Programmable for cycle-mode or fix-mode displays for 3-phase and 1-phase voltages and frequencies.
- All programming and operations can be configured on the front panel.
- Monitors Normal and Standby power for Over /Under voltage anomalies.
- Monitors Normal and Standby power for Over /Under frequency anomalies.
- Exercise with or without load.
- 1 week to 4 weeks automatic scheduled exercise / testing.
- Transfer failure output signal.
- Pre-alert warning signal output for transferring operation.
- Pre-alert warning signal output for scheduled automatic Exercise / testing.
- Compatible with most ATS switches on the market.
- Communication Port for Remote Monitoring and Control Options. (USB / RS485 / Ethernet / WI-FI modules SIM Card).
- Program on-site or from remote (mobile) device (PC, Smartphone).
- Auto-saved settings (memory preserved throughout all power disconnects and resets).
- Front panel display provides source status and fail alarm indications.
Functions / Features
The primary function of ATS-385 controller is to monitor Normal / Standby power and to provide seamless automatic transfer of load.
Operational Simplicity
From installation to programming and to usage, the ATS-385 controller is
designed with operational simplicity in mind. The user-friendly front panel
interface simplifies routine operation, programming and setting adjustments.
Standard Features
All logic settings for different ATS’s are preprogrammed and stored in_
its non-volatile random-access memory (NVRAM), this memory retains its
information when power is turned off. Some features and set points are user
adjustable.
Feature 1 : Time Delay Emergency to Normal (TDEN)
TDEN delays the transfer from the emergency source to the normal Source to
permit stabilization of the normal source before retransfer is made. Timing
begins when the normal source becomes available. (Refer to program table line
3)
Adjustable TDEN time range : 00 999 sec.
Feature 2 : Time Delay Normal to Emergency (TDNE)
TDNE delays the transfer from normal to emergency to permit stabilization
of the generator before the retransfer is made. Timing begins when the standby
source becomes available. (Refer to program table line 4)
Adjustable TDEN time range : 00 250 sec.
Feature 3 : Time Delay Engine Start (TDES)
The TDES Time (Delays Engine Start) this timer prevents nuisance start
because of momentary electrical glitches. If power normalizes before the
countdown ends, the controller skips the engine start and resets the timer.
(Refer to program table line 5)
Adjustable TDES time range : 00 30sec.
Feature 4 : Time Delay Engine Cool-down (TDEC)
TDEC permits the generator to run unloaded after the ATS retransfer back the
load to Normal source. Timing begins when the ATS connects back to Normal
source. (Refer to program table line 6)
Adjustable TDEC range : 00 250 sec.
Feature 5 : Time Delay Center OFF Position
This timer temporally stops the switch in the center OFF position (completely
cut off) before proceeding to Normal source. (Refer to program table line 7)
Adjustable time delay range : 00 99sec.
Feature 6 : Full Phase Over / Under Voltage and Loss of Phase Sensing
The controller monitors full phase output voltage from Normal and Standby
source. The user can program over & under voltage window. (Refer to program
table line 8, 9, 10, 14, 15 & 16)
O/V adjustment range : 390 490 Vac
O/V reset value : -10 Vac (Not adjustable)
U/V adjustment range : 300 410 Vac
U/V reset value : +10 Vac (Not adjustable)
Feature 7 : Under / Over Frequency Sensing
The controller monitors Normal and Standby source frequency. The client can
set the over & under frequency range. (Refer to program table line 11, 12,
13,17, 18 & 19)
O/F adjustable range : 51 75 Hz
O/F reset value : -1 Hz (Not adjustable)
U/F adjustable range : 40 59Hz
U/F reset value : -1 Hz (Not adjustable)
Feature 8 : Programmable exerciser
It can be set to exercise one time per week to one time every 4 weeks on
any day and time, with or without load. The length of the exercise is also
set. (Refer to program table line 23, 24, 25, 26 & 27)
Feature 9 : Failure Warning Output
The controller also has one dry contact that can be set to react to one of
four warning. (Refer to program table line 30)
- Transfer failure warning
- Pre-transfer warning
- Pre-test / exercise warning
- When ATS is in emergency position warming
NOTICE
ATS-385 provides one auxiliary contact for external output signal for Transfer
Failure, Pre-transfer or Pre-exerciser alarm output.
Feature 10 : Controller Panel Lighting Test
This checks the LED lights. Press the OFF button twice, all panel LEDs must
light up.
OPERATOR PANEL
General
Get acquainted with the ATS-385 :
- Front Display Window
- Function Buttons
- Panel LEDs Display
Display Window
The ATS-385 controller has a four-digit, seven-segment displayer to monitor all parameters, setting and messages.
The screen display’s :
- Full phase voltage / frequency display
- Current Time HH : MM (In OFF only)
- Time delay countdown display
- Program setting parameter display
Function Buttons
The front panel employs five membrane switch buttons.
Increase (▲) Button
In AUTO Mode, each press of the up ( ▲ ) button changes the display to
the next phase voltage reading.
However, when programming every press of the up ( ▲ ) button increases the
displayed parameter by a single unit. If held, the up ( ▲ ) button
continues to scroll.
Decrease (▼) Button
In AUTO Mode, each press of the down ( ▼ ) button changes the display
between voltage, duty time and frequency.
However, when programming every press of the down ( ▼ ) button decreases
the displayed parameter by a single unit. If held, the down ( ▼ ) button
continues to scroll.
AUTO Button
When selecting the AUTO button, the ATS-385 runs in automatic mode (AUTO)
lighting the corresponding LED to indicate the selection. The controller
automatically starts the generator, transfer and retransfers from Normal to
Standby source as commanded by the features supplied and the preprogrammed
setting.
TEST Button
Pressing the TEST button simulates a power failure In TEST the generator
starts and begins a preprogrammed execution and testing sequence made with or
without loading the generator. (Refer to program line 28)
OFF Button
Pressing the OFF again, turns the ATS-385 OFF engaging a flashing red LED
instantly disabling all functions and the screen shows the current time.
Panel LED Outputs
Eight individual red and blue LEDs light bars perform or indicating each function.
OPERATION
General
The five functions of the ATS-385 :
- AUTO Mode
- OFF Mode
- Manual Test Mode (TEST)
- Programming Instruction
- Remote Communication Instruction
The practical use of each operation under each category will be explained in this section. It is assumed that prior sections are understood, and the operator has a basic understanding of the hardware.
AUTO Mode
The AUTO mode provides automatic engine start, stop, and power transfer and
retransfers from source to source as_ dictated by the values previously
programmed.
The ATS-385 constantly monitors the condition of both Normal and Standby
source.
OFF Mode
In OFF mode, the ATS-385 disables all the transfers and protection functions
with all LED indicators off leaving the display screen only showing the time.
User can test the LEDs by pressing the OFF button twice. Check and reset the
clock every year. The wrong time can affect the schedule exerciser. Without
power, the controller can maintain the clock working for up to a week.
However, when programming, the OFF button allows you to move to the next
program line and then change the values for that line using down (▼ ) and up
(▲) buttons. 3.4 Manual Test Mode (TEST)
Pressing TEST simulate a loss of Normal power source.
Permitting the controller to start the engine and carry out a power transfer.
TEST can be with load or without load.
To end, press the AUTO button. If Normal power is available, the controller
transfer back to Normal and the engine follow the program shutdown procedure
to stop the generator. However, by pressing the OFF button, the transfer
switch remains in its current position stopping the engine, and bypassing all
time delays.
Programming Instruction
Program the controller from the front faceplate.
To start, set the controller to OFF and press & hold the OFF button for 4
seconds. The word “Vr” appears on the display for 2 seconds, showing the
software version.
You are now ready to. start the line-by-line programming sequence. Always
press the OFF button to move to the next line. To change the parameter, on
each line use the up (▲) and down (▼) arrows. Repeatedly pressing the up (▲)
or down (▼) button, changes the displayed by one. To change faster, hold the
buttons down.
Remember to always press the “OFF” button to move to the next line or until
the “End” appears on the screen.
Note : To end and exit at any time, hold the “OFF” button down for 4
seconds.
If you make an error or need to return to factory settings, stay or reenter
programming and then hold the AUTO button down for 4 seconds, until the word
“Apo” appears on the screen verifying that all programming lines are factory
reset back like in the manual. (See line-by-line programming table for ATS-385
factory settings).
Remote Communication Instruction
You can monitor and control two gen-sets on a remote PC/Smartphone using the remote communication modules. Contact CBI for availability.
Model | Communication interface |
---|---|
KCU-01 | USB |
KCU-02 | RS-485 |
KCU-30 | Ethernet (Dynamic IP) |
KCU-40 | WI-FI |
KCU-50 | 3G SIM Card |
WARNING
A remote start signal can start an engine via ATS-385 without warning.
Place a “Danger” sign next to the generator stating it can start anytime! A
warning buzzer / _ taillight’ installed’ is recommended. Unexpected engine
starts can result in serious’ injury or death. When performing service or
maintenance, always disconnect the remote start signal input.
When KCU-30, KCU-40, KCU-50 module is installed on ATS-385, it allows you to
remote monitor or operate ATS and generator via iPhone or Android Mobil
phones. Free App software currently available for Apple iOS5.‘ system or above
and android operating system.
Download “Remote Communication’ free software by searching “Kutak” in Apple
Store or Google Play.
The corresponding program settings for ATS-385 installed with KCU-XX module
includes item (32), (33), (34) Programming item (32) is a must. When Item (32)
is set to “00° Disable, then the remote monitoring software is restricted to
read information only whereas remote command is strictly forbidden.
When KCU-02 — RS-485 communication module is installed, additional program
setting on lines (33) and (34) are required.
Refer to KCU-XX hardware and software manual for detail information
WARNING
ATS-385 with KCU-02 module constitutes a closed LAN network. Each
controller address can be setup range from 1 to 99 and not to be repeated. The
transmission rate must be the same!
The installation for the KCU-XX communication module on the ATS-385 controller
is fairly simple.
Step 1: Remove the slot cover from the back of controller.
Step 2 : Insert KCU-XX module into the slot and tighten the screw.
KCU Remote Connection Passwords Recovery
Step 1 : Make sure the KCU module is installed on the controller before
carrying out remote connection passwords recovery.
Step 2 : Enter Program mode and set the program item (36) to (01) and
press OFF button. 4-digit numbers “0000” and “9999” will appear on the display
window about two seconds. Then “End” appears which means passwords have been
restored successfully.
NOTICE
Program Line 36 is only available when KCU Module is installed on the
ATS-385 controller.
Voltage Adjustment
The ATS-385 voltage readings are factory set and calibrated. However, if you
need to modify any voltage reading, follow these steps.
Step 1 : Ensure supply is connected to both the normal and standby line
sides before undertaking Voltage calibration, and then manually start standby
generator to generate power.
Step 2 : Enter Program mode and set the program item (35) to (01). “VAdJ”
will appear on the display window.
Step 3 : Select the phase you wish to re-calibrate by pressing the OFF
button.
Step 4 : Use a good quality voltmeter as a reference to
calibrate the ATS-385 voltage reading to the desired phase.
Step 5 : With the up (▲) and down (▼) buttons reset the voltage reading
on the ATS-385.
Step 6 : Press the “OFF” button to move to the next phase or until the
word “End” appears on the screen. To exit hold the “OFF” button at any time
for 4 sec.
Step 7 : If you get “FAIL”, the calibration is null. Press the OFF button
to reset and repeat Step 1.
SECURITY NOTICE AND LIABILITY DISCLAIMER
You are responsible for keeping your KCU Remote Connection Passwords
(Administrator/Viewer) safe and_ confidential because they are the key to
access your equipment’s.
There will be potentially serious security issues if your passwords are
compromised. Some of the risks of compromised security include the equipment
being remotely controlled by third parties, who may have criminal intent and
malicious damage to your equipment’s.
We are entitled to rely on any use of our connection services using that
password as being use by you and authorized by you. If you know or believe
that there is any unauthorized, fraudulent or unlawful use of your password,
you must reset it in the controller. (Refer to controllers user manual for
connection password reset)
Line By Line Programming Table
Line | Description | Value | Factory Setting |
---|---|---|---|
1 | Is this ATS operating in 1 Phase or 3 Phase? | 00 → 1 Phase 01 → 3 Phase | 01 |
2 | Select Switch ATS type | ||
See drawing on the back of this manual for guide on different ATS types | 00) |
MCCB BTS type ATS (Single motor)
1)Mot type (MCCB with separate motor)
2)Air circuit breaker type (ACB)
3)Double throw type (Without OFF position)
4)Double throw type (With OFF position)
5)Kutak TS-XXX type ATS
6)Magnetic contactor type ATS (MC)| 00
3| TDEN Time Delay Emergency to Normal| 00 999 sec.| 10 sec.
4| TDNE Time Delay Normal to Emergency| 00 250 sec.| 10 sec.
5| TDES Time Delay Engine Start| 00 30 sec.| 5 sec.
6| TDEC Time Delay Engine Cool-down| 00 250 sec.| 30 sec.
7| Time Delay in the OFF Position| 00 99 sec.| 5 sec.
8| Normal over voltage protection setting| 39 49 ( 390 490V)| 44 (440V)
9| Normal under voltage protection setting| 30 41 ( 300 410V)| 36 (360V)
10| Time delay if there is a problem with the Normal voltage| 00 99 sec.
( 0 = Disable voltage monitoring )| 10 sec.
11| Normal over frequency protection setting| 51 75 Hz| 55 Hz
12| Normal under frequency protection setting| 40 59 Hz| 45 Hz
13| Time delay if there is a problem with the Normal frequency| 00 99 sec.
( 0 = Disabled Hz monitoring )| 10 sec.
14| Generator over voltage protection setting| 39 49 ( 390 490V)| 44 (440V)
15| Generator under voltage protection setting| 30 41 ( 300 410V)| 36 (360V)
16| Time delay if there is a problem with
emergency voltage output| 00 99 sec.
(0 = Function disabled)| 10 sec.
17| Generator over frequency setting| 51 75 Hz| 55 Hz
18| Generator under frequency setting| 40 59 Hz| 45 Hz
19| Time delay if there is a problem with the
Generator frequency| 00 99 sec.
(0 = Function disabled)| 10 sec.
20| Set today’s day of the week— Day| 1 7 ( Monday to Sunday )| current
21| Set today’s hour — hour| 23| Current
22| Set today’s minutes| 59| current
23| Set day of week to do the engine exercise| 1 7 ( Monday to Sunday )| 6
24| Set the time to start the exercise| 00 23 ( 24 Hr Mode )| 12
25| Set generator automatic exercise cycle| 1)1 week 03) 3 weeks
2)2 weeks 04) 4 weeks| 1
26| Exercising duration| 00 99 minutes ( 0 = Do not exercise )| 0
27| Exercise with load or without load| 00) Without load 01) With load| 0
28| Test with load or without load| 00) Without load 01) With load| 1
29| Display setting| 00) Cyclic Mode 01) Fix Mode| 0
30| Program the auxiliary contact output| 00) Transfer failure
1)Pre-transfer
2)Pre-exerciser
3)When the ATS is in emergency position| 1
31| Pre-transfer / Pre-exercising time delay
before transfer load from one source to another source| 00 99 sec.| 10
32| Remote control by KCU-XX module| 00 → Disable 01 → Enable| 0
33| KCU-02 module address| 00 → KCU-02 module restricted 01 99| 0
34| KCU-02 module transmission rate| 01 → 115200 04 → 19200 07 → 4800
02 → 57600 05 → 14400 08 → 2400
03 → 38400 06 → 9600 09 → 1200| 3
35| Enter AC voltage correction| 00 → No 01 → Yes| 0
36| Restore KCU Remote Connection Passwords to original factory default
settings.
(Administrator : 0000, Viewer : 9999)| 00 → No 01 → Yes| 0
Specification Summary
Description | Specification |
---|---|
AC Voltage Input Range | 300 490 Vac 50/60 Hz |
AC Voltage Display Range | 300 490 Vac 50/60 Hz |
Frequency Measurement Range | 40 75 Hz |
Remote Start Contact | 7A @ 250 Vac Max |
Normal ON Contact | 5A @ 250 Vac Max |
Emergency ON Contact | 5A @ 250 Vac Max |
Auxiliary Contact Output | 7A @ 250 Vac Max |
Operating Temperature | -20 to +70 C |
Storage Temperature | -30 to +80 C |
Relative Humidity | Max. 90% |
Panel Cut-Out | 113.0 (L) x 168.0 (W) 4- 0.5 mm |
Dimensions | 125.0 (L) x 180.0 (W) x 51.0 (H) mm |
Weight | 890 g +/- 2% |
NOTICE
The control unit has no built-in protection fuses. Protection fuses should be
installed when connection.
It is recommended to use the original factory equipment BUSSMANN S505H, 5Amps.
Failure to add a protective fuse or change to another brand or current value
may result in damage to the control unit.
INSTALLATION INSTRUCTIONS
General
The ATS-385 is made for front panel mounting.
Figure / Size / Installation Reference ( All Dimensions in mm. )
CBI-Electric MCCB Type Transfer Switch wiring diagram
PIN NO. | DESCRIPTION |
---|---|
CN1-1 | Normal power L1 voltage output |
CN1-2 | Normal power L3 voltage output |
CN1-3 | Normal Power L2 voltage output |
CN1-4 | Emergency ON motor AC power input |
CN1-5 | Normal ON signal output |
CN1-6 | Normal ON motor AC power input |
CN1-7 | Normal ON motor AC power input |
CN1-8 | Emergency ON signal output |
CN1-9 | Emergency ON motor AC power input |
CN-10 | Emergency power L2 voltage output |
CN1-11 | Emergency power L3 voltage output |
CN1-12 | Emergency power L1 voltage output |
NLS»Norrnal Auxiliary Switch
ELS»Emergency Auxiliary Switch
12P AMP Housing
(Neutral Phase may be optional)
TYPICAL WIRING
Single motor MCCB Type ATS Wiring Diagram (3P/4P) — Called BTS Switch
MITSUBISHI MD Type ATS Wiring Diagram (3P/4P) — MCCB With Separate Motor
KUTAI TS-XXX Type ATS Wiring Diagram (3P)
Magnetic Contactor Type ATS Wiring Diagram (3P/4P)
APPENDIX : KCU Modules Connection Illustration
CBI-electric: low voltage
Trips itch Drive Elandsfontein
Gauteng South Africa
Tel: +27 I 1928 2000
Fax: + 27 I 1392 2354
Email: cbi@cbi-electric.com
Website: www.cbi-lowvoltage.co.za