AKO-55326 Trapped Person Push Button Instruction Manual
- June 9, 2024
- AKO
Table of Contents
AKO-55326 Trapped Person Push Button
02 AKO-55326 AKO-5761x
Installation of detectors and buttons
- For installation inside refrigeration chambers, always use UNIVERSAL (AKO-57614) type detectors. 2 -Use type V3V3-fr cables with three 0.5 mm conductors. Insulation voltage must be 300/500 V.
- Do not install the detector or button near areas where ice or condensation could form (evaporators, doors, etc.).
AKO-5761x
Refrigerant gas detector

- 
Make a 16 mm hole and fit the gland. 
- 
Mark the fastening holes on the wall using the 
 template provided and drill, attach the detector /
 transmitter using the supplied screws and wall plugs. If
 attaching to the wall of a cold room, do not use the
 wall plugs.
- 
The detector must be located at a height of 1 m 
 from the floor and must have at least 50 cm of free
 space around it.
AKO-5761x
Refrigerant gas detector

- 
Insert the cable through the gland and tighten it. 
- 
Strip and cut the cable sheath so that the wires arrive 
 at the connector strip without tension.
- 
Install the connector tips on the ends of the three 
 wires.
- 
Connect the wires according to the installation 
 diagram.
AKO-5761x
Refrigerant gas detector

IMPORTANT
- Do not use silicone or other sealants to
 close openings.
AKO-55326
Trapped person alarm button

- 
Drill a 16 mm hole in the lower area for cable 
 entry and attach the supplied cable gland.
- 
Use the template provided to mark the fastening holes 
 on the wall, drill them and then attach the pushbutton
 using the screws and wall plugs supplied. If attaching
 to the wall of a cold room, do not use the wall plugs.
- 
The pushbutton must be located no more than 
 1.25 m from the ground, positioned horizontally,
 and must be in a visible location inside the cold room.
AKO-55326
Trapped person alarm button
- 
Insert the cable through the gland and tighten it 
 to make sure it is water-tight.
- 
Strip and cut the cable sheath so that the wires arrive 
 at the connector strip without tension.
- 
Install the connector tips on the ends of the three 
 wires, then connect the wires according to the
 installation diagram.
AKO-55326
Trapped person alarm button

IMPORTANT
- Do not use silicone or other sealants to
 close openings.
AKO ELECTROMECÁNICA , S.A.L.
Avda. Roquetes, 30-38
08812 • Sant Pere de Ribes.
Barcelona • Spain.
www.ako.com
We reserve the right to supply materials that might vary slightly to those described in our Technical Sheets. Updated information is available on our website.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>
