AKO-55326 Trapped Person Push Button Instruction Manual
- June 9, 2024
- AKO
Table of Contents
AKO-55326 Trapped Person Push Button
02 AKO-55326 AKO-5761x
Installation of detectors and buttons
- For installation inside refrigeration chambers, always use UNIVERSAL (AKO-57614) type detectors. 2 -Use type V3V3-fr cables with three 0.5 mm conductors. Insulation voltage must be 300/500 V.
- Do not install the detector or button near areas where ice or condensation could form (evaporators, doors, etc.).
AKO-5761x
Refrigerant gas detector
-
Make a 16 mm hole and fit the gland.
-
Mark the fastening holes on the wall using the
template provided and drill, attach the detector /
transmitter using the supplied screws and wall plugs. If
attaching to the wall of a cold room, do not use the
wall plugs. -
The detector must be located at a height of 1 m
from the floor and must have at least 50 cm of free
space around it.
AKO-5761x
Refrigerant gas detector
-
Insert the cable through the gland and tighten it.
-
Strip and cut the cable sheath so that the wires arrive
at the connector strip without tension. -
Install the connector tips on the ends of the three
wires. -
Connect the wires according to the installation
diagram.
AKO-5761x
Refrigerant gas detector
IMPORTANT
- Do not use silicone or other sealants to
close openings.
AKO-55326
Trapped person alarm button
-
Drill a 16 mm hole in the lower area for cable
entry and attach the supplied cable gland. -
Use the template provided to mark the fastening holes
on the wall, drill them and then attach the pushbutton
using the screws and wall plugs supplied. If attaching
to the wall of a cold room, do not use the wall plugs. -
The pushbutton must be located no more than
1.25 m from the ground, positioned horizontally,
and must be in a visible location inside the cold room.
AKO-55326
Trapped person alarm button
-
Insert the cable through the gland and tighten it
to make sure it is water-tight. -
Strip and cut the cable sheath so that the wires arrive
at the connector strip without tension. -
Install the connector tips on the ends of the three
wires, then connect the wires according to the
installation diagram.
AKO-55326
Trapped person alarm button
IMPORTANT
- Do not use silicone or other sealants to
close openings.