INSTEK GPP-3060 3 Channel Programmable DC Power Supply User Manual
- June 9, 2024
- INSTEK
Table of Contents
- INSTEK GPP-3060 3 Channel Programmable DC Power Supply
- Product Information
- Product Usage Instructions
- SAFETY INSTRUCTIONS
- Power cord for the United Kingdom
- OVERVIEW
- Introduction
- Key Features
- Constant Voltage/Constant Current Crossover CharacteristicsGETTING
- GETTING STARTED
- Load Connection
- BASIC OPERATIONLoad Function
- Set Group Parameter
- SYSTEM SETTINGSREMOTE CONTROL
- Remote control setting
- REMOTE CONTROL
- Command List
- Command Function Description
- Function Example
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
INSTEK GPP-3060 3 Channel Programmable DC Power Supply
Product Information
The Programmable DC Power Supply GPP-3060/GPP-6030 is a product manufactured by Good Will Instrument Co., Ltd. It is a certified ISO-9001 product that has proprietary information protected by copyright. The product can operate in Independent Output Mode, Tracking Series, Tracking Parallel Modes, Load Function, Sequence Function, Delay Function, Monitor Function and Recorder Function. It also has an External I/O Control feature. The product comes with a user manual.
Product Usage Instructions
Getting Started:
- Connect the power cord to the power supply and plug it into a power outlet.
- Connect the load to the output terminals of the power supply.
- Select the front/rear panel output.
- Turn on the output using the On/Off button.
Basic Operation:
- To change the display, press the Display Change button.
- To change the source function, press the Source Functionbutton.
Independent Output Mode:
- Press the Independent Output Mode button.
- Select the output voltage and current values using the keypad.
- Press the Set button to confirm the values.
Tracking Series and Tracking Parallel Modes:
- Press the Tracking Series or Tracking Parallel Mode button.
- Select the output voltage and current values using the keypad.
- Press the Set button to confirm the values.
Load Function:
- Press the Load Function button.
- Select the load mode and set the load current value using the keypad.
- Press the Set button to confirm the values.
Sequence Function:
- Press the Sequence Function button.
- Select the sequence output and set the sequence values using the keypad.
- Press the Set button to confirm the values.
Delay Function:
- Press the Delay Function button.
- Select the delay output and set the delay values using the keypad.
- Press the Set button to confirm the values.
Monitor Function:
- Press the Monitor Function button.
- Select the monitor mode and set the monitor values using the keypad.
- Press the Set button to confirm the values.
Recorder Function:
- Press the Recorder Function button.
- Select the recorder mode and set the recorder values using the keypad.
- Press the Set button to confirm the values.
External I/O Control:
- Connect the external I/O control device to the power supply.
- Follow the external I/O control instructions to operate the power supply.
5 Commonwealth Ave Woburn, MA 01801 Phone
781-665-1400 Toll Free
1-800-517-8431 Visit us at
www.TestEquipmentDepot.com
Programmable DC Power Supply
GPP-3060/GPP-6030
User Manual
ISO-9001 CERTIFIED MANUFACTURER
Copyright Statement
This manual contains proprietary information, which is protected by copyright.
All rights are reserved. No part of this manual may be photocopied, reproduced
or translated to another language without prior written consent of Good Will
company. The information in this manual was correct at the time of printing.
However, Good Will continues to improve products and reserves the rights to
change specification, equipment, and maintenance procedures at any time
without notice.
Good Will Instrument Co., Ltd. No. 7-1, Jhongsing Rd., Tucheng Dist., New
Taipei City 236, Taiwan.
SAFETY INSTRUCTIONS
This chapter contains important safety instructions that you must follow
during operation and storage. Read the following before any operation to
insure your safety and to keep the instrument in the best possible condition.
Safety Symbols
These symbols may appear in the manual or on the instrument.
WARNING CAUTION
Warning: Identifies conditions or practices that could result in injury or
loss of life.
Caution: Identifies conditions or practices that could result in damage to the
GPP or to other properties.
DANGER High Voltage
Attention Refer to the Manual
Protective Conductor Terminal
Earth (ground) Terminal
Do not dispose electronic equipment as unsorted municipal waste. Please use a
separate collection facility or contact the supplier from which this
instrument was purchased.
7
GPP-3060/6030 User Manual
Safety Guidelines
General Guideline
CAUTION
Do not place any heavy object on the unit.
Avoid severe impact or rough handling that leads to damaging the unit.
Do not discharge static electricity to the unit.
Do not block the cooling fan opening.
Do not perform measurements on circuits that are directly connected to mains
power.
Do not disassemble the GPP unless you are qualified.
(Measurement categories) EN 61010-1:2010 specifies the measurement categories
and their requirements as follows. The GPP Series falls under category I .
Measurement category IV is for measurement performed at the source of low-
voltage installation .
Measurement category III is for measurement performed in the building
installation.
Measurement category II is for measurement performed on the circuits directly
connected to the low voltage installation.
Measurement category I is for measurements performed on circuits not directly
connected to Mains.
8
SAFETY INSTRUCTIONS
(Pollution Degree) EN 61010-1:2010 specifies pollution degrees and their requirements as follows.Pollution refers to “addition of foreign matter, solid, liquid, or gaseous (ionized gases), that may produce a reduction of dielectric strength or surface resistivity”. The GPP Series falls under degree 2.
Pollution degree 1: No pollution or only dry, nonconductive pollution occurs. The pollution has no influence.
Pollution degree 2: Normally only non-conductive pollution occurs.
Occasionally, however, a temporary conductivity caused by condensation must be
expected.
Pollution degree 3: Conductive pollution occurs, or dry, non-conductive
pollution occurs which becomes conductive due to condensation which is
expected. In such conditions, equipment is normally protected against exposure
to direct sunlight, precipitation, and full wind pressure, but neither
temperature nor humidity is controlled.
Power Supply WARNING
AC Input voltage range: 100V/120V/220V/230V ±10%
Frequency: 50Hz/60Hz
To avoid electrical shock connect the protective grounding conductor of the AC power cord to an earth ground.
Fuse
Fuse type: 100V/120VT12A/250V
WARNING
220V/230VT5A/250V
To prevent fire, replace the fuse only with the specified type and rating.
Disconnect the power cord before replacing the fuse.
Make sure the cause of fuse blowout is fixed before replacing the fuse.
9
Cleaning the power supply
Operation Environment
Storage environment
GPP-3060/6030 User Manual
Disconnect the power cord before cleaningit . Use a soft cloth dampened in a
solution of mild
detergent and water. Do not spray any liquid into it. Do not use chemicals
containing harsh products such as benzene, toluene, xylene, and acetone.
Location: Indoor, no direct sunlight, dust free, almost non-conductive
pollution (Note below) Relative Humidity: < 80% Altitude: < 2000m Temperature:
0°C to 40°C Location: Indoor Relative Humidity: < 70% Temperature: -10°C to
70°C
Power cord for the United Kingdom
When using the power supply in the United Kingdom, make sure the power cord
meets the following safety instructions.
NOTE: This lead/appliance must only be wired by competent persons
WARNING: THIS APPLIANCE MUST BE EARTHED
IMPORTANT: The wires in this lead are coloured in accordance with the
following code:
Green/ Yellow: Earth
Blue:
Neutral
Brown:
Live (Phase)
As the colours of the wires in main leads may not correspond with the coloured marking identified in your plug/appliance, proceed as follows:
The wire which is coloured Green & Yellow must be connected to the Earth
terminal marked with either the letter E, the earth symbol
or coloured Green/Green & Yellow.
The wire which is coloured Blue must be connected to the terminal which is marked with the letter N or coloured Blue or Black.
The wire which is coloured Brown must be connected to the terminal marked with the letter L or P or coloured Brown or Red.
If in doubt, consult the instructions provided with the equipment or contact the supplier.
This cable/appliance should be protected by a suitably rated and approved HBC mains fuse: refer to the rating information on the equipment and/or user instructions for details. As a guide, a cable of 0.75mm2 should be protected by a 3A or 5A fuse. Larger conductors would normally require 13A types, depending on the connection method used.
Any exposed wiring from a cable, plug or connection that is engaged in a live socket is extremely hazardous. If a cable or plug is deemed hazardous, turn off the mains power and remove the cable, any fuses and fuse assemblies. All hazardous wiring must be immediately destroyed and replaced in accordance to the above standard.
OVERVIEW
This chapter contains a brief introduction to GPP3060/GPP-6030 including the main features and an overview of the front and rear panel. Use the Getting Started chapter on page 27 to start up instructions and how to setup the appropriate operation environment.
Introduction
Overview
Independent / Tracking Series / Tracking Parallel
The GPP-3060/GPP-6030 regulated DC power supply series are adjustable,
multifunctional work stations. It has three independent outputs: two with
adjustable voltage levels and one with fixed level selectable from 1.8V, 2.5V,
3.3V and 5V.
It can be used for logic circuits where various output voltage or current are
needed, and for tracking mode definition systems where plus and minus voltages
with insignificant error are required.
The three output modes of it, independent, tracking series, and tracking
parallel, can be selected through pressing the TRACKING key on the front
panel. In the independent mode, the output voltage and current of each channel
are controlled separately. The isolation degree, from output terminal to
chassis or from output terminal to output terminal, is DC500V.
In the tracking modes, both the CH1 and CH2 outputs are automatically
connected in series or parallel; no need to connect output leads. In the
series mode, the output voltage is doubled; in the parallel mode, the output
current is doubled.
13
GPP-3060/6030 User Manual
Load Mode
It has additional Load function on both CH1 & CH2 with 3 modes: CV (Constanct Voltage), CC (Constant Current) and CR (Constant Resistance), all of which can be selected through the function keys on the front panel. Voltage, current and resistance can be well regulated in each mode, respectively.
Constant Voltage/ Constant Current
Each output channel is completely transistorized and well-regulated, and works in constant voltage (CV) or constant current (CC) mode. Even at the maximum output current, a fully rated, continuously adjustable output voltage is provided. For a big load, the power supply can be used as a CV source; while for a small load, a CC source. When in the CV mode (independent or tracking mode), output current (overload or short circuit) can be controlled via the front panel. When in the CC mode (independent mode only), the maximum (ceiling) output voltage can be controlled via the front panel. The power supply will automatically cross over from CV to CC operation when the output current reaches the target value. The power supply will automatically cross over from CC to CV when the output voltage reaches the target value. For more details about CV/CC mode operation, see page 26.
Automatic tracking mode
The front panel display (CH1, CH2) shows the output voltage or current. When operating in the tracking mode, the power supply will automatically connect to the auto- tracking mode.
14
OVERVIEW
Display Change Function
It provides up to 6 display types, each of which can be well selected via setting. For details, see page 33.
Output Waveform Function
Under Source mode, user can customize a certain V/I sequential waveform output. Under Load mode, it is programmable for dynamic load (below 1Hz). For details, see page 54.
Front and rear output function
For the convenience of customers, GPP can be operated by the panel menu or remote command, so that it can be output on the front and rear panels, please refer to page 31.
Remote Control
To meet the various needs of customers, the GPP is designed for USB, GPIB ,LAN and RS232 remote control. For details, see page 101.
Additional Function
Control signal of external switch is reserved for user. For details, see page 85.
15
GPP-3060/6030 User Manual
Key Features
Features Operation
Multiple Outputs:
Constant voltage and constant current operation (CV/CC).
Low noise, thermostatically controlled fan.
Compact, lightweight, standard rack mount comformity 3U, half Rack.
4.3 inch TFT display.
Digital panel control.
Output on/off control (ON/OFF), and each channel can be controlled separately.
Digital voltage and current settings. (Key & Encode)
10 groups of save/recall settings and 2 groups of power-on settings. 10 groups
of save/recall Sequence. 10 groups of save/recall Delay. 10 groups of
save/recall Record.
CH1/CH2 workable in Load Mode
6 types display modes available with 4 contents and 2 waveforms respectively
Input/Output terminal (Control I/O)
Alarm buzzer (Beeper).
Key lock function (LOCK).
Front and rear output function
Multiple remote control interfaces (standard: RS-232, USB; optional: GPIB,
LAN)
16
Protection Features
Interface
OVERVIEW
Overvoltage and overcurrent protection (OVP/ OCP)
Overtemperature protection (OTP). Polarity Reverse Protection Overload
Protection (OPP in Load mode) Remote Control RS-232 (standard) USB remote
control. (standard) Control I/O (standard) LAN remote control (optional) GPIB
& LAN remote control (optional)
17
Front Panel
LCD
GPP-3060/6030 User Manual
Number Scroll wheel Pad Arrow keys
Power button
Front output terminals Funtion keys USB host
Display
Display Interface
(Take GPP-3060 model as example) 18
OVERVIEW
Channel distribution
Single channel display
Channel no.
Channel status
Channel number and distribution vary by models with different colors identifications: CH1: Yellow CH2: Blue CH3: Pink CH1 is master and CH2 becomes yellow under tracking series and tracking parallel modes.
Channel/ Status
Power display
V/I setting
Voltage display
Current display
OVP/OCP setting area
Color of channel remains the origanl when not in the state of setting.
Color of channel blinks between the original and
orange
when being set.
Display active channel state
Power supply: CH1/CH2: green or red
Voltmeter Indicators
Load Mode: CH1/CH2: orange
Displays the output voltage with up to 6 digits of resolution. The default
units are Volts (V).
Ammeter Indicator
CH1
CH2 CH3
Displays the output current with up to 5 digits of resolution. The default
units are ampere (A).
19
GPP-3060/6030 User Manual
Setting Display
CH1:
CH2 CH3None
Displays the voltage and current settings.
CH1/CH2: CH3: displays setting of voltage only
Status Indicator
Display OVP/OCP settings
CH1/CH2:
, The CH3 OVP is a
fixed value (approx. 5.5V), non-configurable and
with only on or off switch available for user.
OCP is available only for USB output port
(approx. 3.1A)
Display the set function/remote control interface
: The active channel under setting status : The status of OTP protection mode
: The status of USB flash drive connected : USB remotely disconnected : USB
remotely connected
: The status of control I/O connected Others: when operating in the
series/parallel tracking mode, the corresponding SER/PAR icons appear on the
display. when Sequence/Delay/Monitor/Recorder is activated, the corresponding
SEQ/DLY/MON/ REC icons appear on the display.
Function Keys 20
Power Button Channel select buttons Output buttons Individual
output
Output all Number pad
OVERVIEW
Turns the power on or off. On: Off:
Each channel has its own button and promptly switchable among CH1-CH3 setting.
The ON/OFF button is operational individually by each channel. The Output key
will light up when the output is on.
ON:
All ON:
For parameter value setting
Scroll wheel & Arrow keys
Scroll wheel is used to set each parameter value, whilst arrow keys are used
for parameter, menu selection and voltage/current fine adjustment. It is used
to switch or operate the displayed waveforms under diagram display mode.
21
Function keys System key
Advance key Memory key
Lock key
Unlock
Terminals CH1 terminal
CH2 terminal
GPP-3060/6030 User Manual
The 6 function keys (F1-F6) display varied functions per different
opertations.
It is used to set functions including Interface, Beeper, Backlight, etc. For
details, refer to page 96.
It is used for certain advanced functions like Sequence, Delay, Monitor,
Recorder, etc.
It is used to operate several functions including save and recall, etc., for
set parameters. For details, refer to page 89.
It is used to disable all the panel keys except for the Output key.
Press the F6 button to unlock, which can disable remote control and return to
panel operation.
Power output terminal or load input terminal
Power output terminal or load input terminal
22
CH3 terminal
OVERVIEW Power output terminal
Power output terminal
Warning: The output current from the 2 terminals should Not exceed 5A.
GND terminal
Ground terminal
23
Rear Panel
GPP-3060/6030 User Manual
Terminals Alternate input switch
AC input socket and line fuse
Rear output terminal
24
AC voltage selection:
100V/120V/220V/230V ±10%, frequency 50/60Hz
The AC input accepts 100V/120V/220V/230V AC. The frequency is 50Hz/60Hz. Fuse:
100V/120V: T12A/250V 220V/230V :T5A/250V slow-blow type, See page 213 for
details.
Operation and connection mode, see page29 and page43.
USB port GPIB port
LAN port
RS-232 port Heat sink fan
Control I/O port
OVERVIEW
USB device port for remote control. See page 101 for details.
GPIB slave port for remote control. Abides to IEEE488.2 (SCPI) protocol. See
page 108 for details.
LAN port for remote control. See page 110 for LAN setting and operation
details.
RS-232 port for remote control. See page 104 for details.
It is used to discharge the heat inside the equipment through air flow.
5 ports in all for input/output control. See page 85 for details of
configuration.
25
GPP-3060/6030 User Manual
Constant Voltage/Constant Current Crossover CharacteristicsGETTING
STARTED
Background CV mode
Constant Current Mode
The unit will switch automatically between constant voltage and constant
current according to changes in the load.
When the load current is less than the current setting, the unit operates in
constant voltage mode, changing the current level according to the load but
maintaining the set voltage level until the current reaches the set current
level. The status indicator will show CV on the LCD when in CV mode.
When the output current reaches the set current level, the unit switches
operation to constant current mode. The status indicator will show CC on the
LCD display. In CC mode, the current level is maintained and the voltage level
is limited to less than the set voltage level to limit the output power from
an overload. When the current drops below the set current level, the unit will
revert back to CV mode.
Diagram
Vout
Vmax
Constant Voltage
Constant Current
Imax Iout
26
GETTING STARTED
This chapter describes the start up procedures and the preparation that is necessary before operating the power supply.
GPP-3060/6030 User Manual
Start Up
Checking the AC Voltage
Connecting the AC power cord
Turning the power on
Before the power is turned on, confirm that the input power supply meets the
following conditions: 100V/120V/220V/230V ±10% 50/60Hz
The fuse is a slow-blow fuse. 5A(220V/230V),12A(100V/120V Confirm that the
fuse is of the correct type and rating before connecting the power cord.
Press the power button.
Turning the power off
To turn the power off, press the power button again.
28
GETTING STARTED
Load Connection
Recommen ded Cables
Model GTL-104A
Specification 10A
Front panel wiring
Use the GTL-104A cables for the front panel source connections.
USB Type A only (Greater than 4A)
Usage
Front panel terminal
Rear panel wiring
Self distribution wire: + / – need to be equipped with awg12 or above S + / S – can be equipped with awg20, preferably twisted into twisted pair. When in LOAD mode, there is no need to connect sense.
Caution
For safety considerations, please keep in mind that the wiring must be equivalent to the wiring on the front terminals.
Wire Gauge
Load wires must have enough current capacity to minimize cable loss and load line impedance. Voltage drop across a wire should not excess 0.5V. The following list is the wire current rating at 450A/cm2.
Wire Size(AWG)
Maximum Current (A)
20
2.5
29
GPP-3060/6030 User Manual
18
4
16
6
14
10
12
16
30
GETTING STARTED
Select front/rear panel output
Panel
1. Double click the system button
Operation
2. Press F1 (front) key to select front panel output, or press F2 (rear) key to select rear panel output.
F1
F2
3. You can see the switching output panel results from the corresponding display interface.
Note
Command Set
The three channels will be switched at the same time for front or rear output.
Refer to page 120 for more details on remote commands chapter.
31
GPP-3060/6030 User Manual
Turning the Output On/Off
Panel Operation
Press the Output key of each channel individually to turn the output on. The Output key will light-up when the output is on.
When the output is turned on, pressing the Output key again will turn the output off.
Press ALL ON/OFF key when it needs to output or turn off all channels simultaneously.
Command Set
Refer to page 120 for more details on remote commands chapter.
Automatic Output Shut Down
Any of the following actions will cause the output to be automatically shut
down:
Toggle between power output and load mode Independent/Tracking Series/Tracking
Parallel
operation Recall the saved setting OVP/ OCP/OPP/OTP protection is tripped.
When Sequence/Delay/Monitor/Control IO
fits the set conditions.
32
BASIC OPERATIONLoad Function
Display Change
GPP-3060/6030 User Manual
Display Area Channel/status Read back area Work status area
Parameter Setting area
Function keys area
Warning :
1. Under the Source interface:
Each channel has its own setting area (V/I/OVP/OCP) and read back status area
(V/I/W).
2. Under the Load interface:
It is basically equivalent to Sourece interface with additional Load and OPP status displays.
Diverse display screens
In order to offer diverse information display of each channel to meet requirements from different users, the GPP provide several selections of different display screens as follows:
34
Type Nomarl Type1
Type2
Type4 Type5 Wave- Type6 form
Type7
BASIC OPERATION Display screens
Only Type 1, Type 4 and Type 7 have setting value display Type’s selection: Advance key ->F1(Display) key->F1(Normal) key or F2(Waveform) key. * Default factory display screen: Type1
35
The introduction to Type 6 display
GPP-3060/6030 User Manual
a b
c
d e
f
g
a represents the currently edited channel, which can be toggled through the
channel button on the panel.
b indicates the adjustable items of reference point for
voltage/current/power respectively in the active channel. The one with
a red triangular arrow is the active item to adjust, which can be toggled
through the directional button on the panel. c stands for the vertical
sensitivity for voltage/current/power
respectively in the active channel. d stands for the horizontal sensitivity
for time. e represents the output state of active channel and the open state
of
OVP/OCP. f indicates the output curve for voltage/current/power respectively
in
the active channel. The three curves have the identical color in
common with slight difference in brightness, which corresponds to the
brightness of b. g stands for the output reference point for
voltage/current/power
respectively in the active channel, which is adjustable ups and downs
via scroll wheel.
36
Source Function
BASIC OPERATION
Description
Parameter description
Each channel is equipped with basic power functions and able to display both settings and read back value of V/I as well as output status
Vset
Set output voltage of active channel.
The range is as the following:
CH1/CH2:
0.000V-32.000V (GPP-3060)
0.000V-62.000V (GPP-6030)
CH3: 1.8V/2.5V/3.3V/5.5V
Iset
Set limited current of active channel.
The range is as the following:
CH1/CH2:
0.0000A-6.2000A (GPP-3060)
0.0000A-3.2000A (GPP-6030)
OVP
Set OVP. The range is as the
following:
CH1/CH2:
0.5V-35.0V (GPP-3060)
0.5V-65.0V (GPP-6030)
OCP
Set OCP. The range is as the
following:
CH1/CH2:
37
Parameter Setting (CH1 for example)
GPP-3060/6030 User Manual
0.05A-6.50A (GPP-3060) 0.05A-3.50A (GPP-6030)
Voltage
Press the F1 key corresponding to Voltage to activatate voltage setting area on LCD (red font color with the underline indicator).
(a) Input digit with number pad (09,.) and press unit key F1(V) or F2(mV) to confirm:
Input 6.543V:
(b) Step input: Press the left or right arrow buttons to select high and low level that require fine-tune (underline below the corresponding number value), and scroll the scroll wheel to increase or decrease setting value.
Current
Press the F2 key corresponding to Current to activatate current setting area on LCD (red font color with the underline indicator).
38
BASIC OPERATION
(a) Input digit with number pad (09,.) and press unit key F1(A) or F2(mA) to
confirm:
Input 1.543V:
(b) Step input: Press the left or right arrow buttons to select high and low level that require fine tune (underline below the corresponding number value), and scroll the scroll wheel to increase or decrease setting value.
OVP
Press F3 key to enter the
Protect menu.
Press F3 key to open OVP function. OVP display will change from gray to white
font.
Press the F1 key to enter OVP setting area on LCD, which will be thus
activated (red font color with the underline indicator).
(a) Input digit with number pad (09,.) and press unit key F1(V) or
39
GPP-3060/6030 User Manual F2(mV) to confirm:
Input 6.5V:
(b) Step input: Press the left or right arrow buttons to select high and low level that require fine tune (underline below the corresponding number value), and scroll the scroll wheel to increase or decrease setting value.
OCP
Press F3 key to enter
the Protect menu.
Press F3 key to open OCP function. OCP display will change from gray to white
font.
Press the F2 key to enter OCP setting area on LCD, which will be thus
activated (red font color with the underline indicator).
(a) Input digit with number pad (0-
40
BASIC OPERATION 9,.) and press unit key F1(A) or F2(mA) to confirm:
Input 2.5A:
Operation
State description
CAUTION:
There’s no proper sequence between turning on OVP/OCP functions and setting OVP/OCP value.
Either step input or number pad input is applicable for setting parameter value.
ON/OFF
Output ON/OFF control. Output is open when output lights up; whilst output is off when output lights out.
All ON/OFF
1. When the output state of all channels is identical, press All ON/OFF to perform the opposite operation. 2. When the output of all channels is inconsistent, press All ON/OFF will close the open channel of the output.
CV/CC
Constant voltage displays in green CV, while constant current displays in red CC.
OVP/OCP
OVP/OCP displays in white when OVP is not in activation.
41
GPP-3060/6030 User Manual OVP/OCP displays in red and output is off when OVP
is activated. OVP/OCP displays in gray when OVP/OCP functions are off.
42
BASIC OPERATION
Independent Output Mode
Description
Each channel within the models is apart from one another and capable of operations including independent setting and individual output, etc.
Front panel connection
Rear panel with sense connection
+ –
+ – +-
CH1 Load
CH2
CH3
Load
Load
CH3 CH2 CH1 Load Load Load
43
GPP-3060/6030 User Manual
Voltage/Cur rent Rating
CH1/CH2: 30V/6A x 2 (GPP-3060) 60V/3A x 2 (GPP-6030)
CH3: 1.8V/2.5V/3.3V/5V/5A x 1 USB Port Output:3A
Setting
1. Press F4 or F5 button for operating the corresponding Independent to enter the Independent function.
2. For setting opertation of parameter, refer to page 38.
Output
The independent button ON/OFF of each channel is available, while All ON/OFF button is available for all channels.
44
BASIC OPERATION
Tracking Series and Tracking Parallel Modes
Description
Tracking series operation doubles the Voltage capacity of the GPP by internally connecting CH1 (Master) and CH2 (Slave) in series and combining the output to a single channel. CH1 (Master) controls the combined Voltage output level.
Tracking series without common terminal
Front panel connection
Rear panel with sense connection
–
Load
Load 45
Output rating Setting
Output
GPP-3060/6030 User Manual
0 – 60V/0 – 6A (GPP-3060) 0 – 120V/0 – 3A (GPP-3060)
1. Press F4 or F5 button for operating the corresponding Series to enter the
tracking series function. Yellow SER will be shown on the status area.
2. Press CH1 button to proceed to CH1/CH2 voltage setting and CH1 limit
current setting.
3. Press CH2 button to proceed to CH2 limit current setting.
4. For setting operation of parameter, refer to page 38.
The button ON/OFF of CH1/CH2 is individually available, while All ON/OFF
button is available for all channels.
46
Tracking series with common terminal
Front panel connection
BASIC OPERATION
Rear panel with sense connection
+ com Load
Output rating
Load
0-30V/0-6A for CH1+ 0-30V/0-6A for CH20-60V/0-3A for CH1+ 0-60V/0-3A for CH2-
– COM (GPP-3060) – COM (GPP-3060) – COM (GPP-6030) – COM (GPP-6030)
47
GPP-3060/6030 User Manual
Operation
1. Press F4 or F5 button for operating the corresponding Series to enter the tracking series function. Yellow SER will be shown on the status area.
2. Press CH1 button to proceed to CH1/CH2 voltage setting and CH1 limit current setting.
3. Press CH2 button to proceed to CH2 limit current setting.
4. For setting operation of parameter, refer to page 38.
Output
The button ON/OFF of CH1/CH2 is individually available, while All ON/OFF button is available for all channels.
CAUTION: under Tracking series mode, CH1 is master, CH2 is slave. Thus, output voltage setting is not available for CH2.
CH1/CH2 Tracking Parallel Mode
Front panel connection
+ Load
48
Rear panel with sense connection
BASIC OPERATION
Load
Output raing Operation
Output
0-30V/0 -12A(GPP-3060) 0 -60V/0 -6A (GPP-6030)
1. Press F4 or F5 button for operating the corresponding Parallel to enter
the tracking parallel function. Yellow PAR will be shown on the status area.
2. Press CH1 button to proceed to CH1/CH2 voltage/current setting.
4. For setting operation of parameter, refer to page 38.
The button ON/OFF of CH1/CH2 is individually available, while All ON/OFF
button is available for all channels.
CAUTION: under tracking parallel mode, CH1 is master, whilst CH2 is slave. Thus, output voltage/current setting is not available for CH2.
49
GPP-3060/6030 User Manual
Load Function
Description
CH1/CH2 can be set to the Load Mode function, under which both tracking series and tracking parallel function are Not available.
Note
The voltage (1V) or –.–(<1V) pertaining to port appears when Output is Off.
In LOAD mode, the rear panel does not need to be connected with sense.
Parameter Load Description
Vset
Iset
50
Under PWR. mode, press F6 (Load
Mode) to enter the Load mode. LCD
will display the status
.
Set rating range of voltage value under Load mode of active channel: 1.50V-32.00V(GPP-3060) 1.50V-62.00V(GPP-6030)
Set rating range of current value under Load mode of active channel 0.000A-6.200A(GPP-3060) 0.000A-3.200A(GPP-6030)
Rset
Others
Parameter Vset setting
BASIC OPERATION
Set rating range of resistance value under Load mode of active channel 1-1000
OPP Fixed 50W of single channel, non-revisable OVP/OCP indentical to Source
Press F4 or F5 button for operating the corresponding (CV) mode followed by F1
button (Vset). The voltage setting area on LCD will be activated and appears
(red font color with the underline indicator).
(a) number pad (0-9,.) input; press unit button F1 (V) or F2 (mV) button to
confirm:
Input 6.54V:
(b) Step input: Press the left or right arrow buttons to select high and low level that require fine tune (underline below the corresponding number value), and scroll the scroll wheel to increase or decrease setting value.
Iset
Press F4 or F5 button for operating
the corresponding (CC) mode
51
GPP-3060/6030 User Manual
followed by F1 button (Iset). The
current setting area on LCD will be
activated and appears
(red
font color with the underline
indicator).
(a) number pad (0-9,.) input; press unit button F1 (A) or F2 (mA) button to confirm:
Input 1.543A:
(b) Step input: Press the left or right arrow buttons to select high and low level that require fine tune (underline below the corresponding number value), and scroll the scroll wheel to increase or decrease setting value.
Rset
Press F4 or F5 button for operating
the corresponding (CR) mode
followed by F1 button (Rset). The
current setting area on LCD will be
activated and appears
(red font color with the underline
indicator).
(a) number pad (0-9,.) input; press unit button F1 (OHM) to confirm:
Input 52:
52
BASIC OPERATION
(b) Step input: Press the left or right arrow buttons to select high and low level that require fine tune (underline below the corresponding number value), and scroll the scroll wheel to increase or decrease setting value.
OVP
The setting method is identical to
OCP
Source.
Operation ON/OFF
The button ON/OFF of CH1/CH2 is individually available, while All ON/OFF button is available for all channels.
Mode
CV CC CR
Font color appears in orange under Load mode.
Note
In CR mode, the external power supply must provide the current required for I = V / R, otherwise the output ports V and I will fluctuate.
53
GPP-3060/6030 User Manual
Sequence Function
Description
This function can be used for practical applications when different voltage
waveforms are required to be output. Users can edit the output waveform
according to their needs. The amplitude range of the output waveform is the
output voltage range of power supply. The setting range for output waveform
duration is 1s (duration calculation: Time x Groups x Cycles) and the
resolution is 1s.
Caution: This feature is applicable to both CH1 and CH2.
Set Sequence Output
Parameter Cycles Description
Start
Cycle number, 1 represents a cycle of single period, whilst 2 indicate a cycle
with 2 periods, and so on. The range is from 1 to 9999 or Infinite.
The number to execute, 0 indicates the execution starts from the group 0,
while 1 indicates it begins from the group 1, and so on. The range is from 0
to 2047.
54
Groups End State Parameter Cycles Setting
Start
Groups
BASIC OPERATION
The number to be executed. It can NOT exceed 2048 for Start+Groups.
There’re 2 statuses after the necessary Group and Cycle are executed: output
termination or being hold with the last step.
Press the Advance key on control
panel. Select F2 (Sequence) function.
Press F1 (Set) button followed by
selecting F1 (Cycles). The setting on
LCD is activated and appears in red
font color
. Use number
pad to set the parameters directly
and then press the F1 (Done) button
to confirm; or use arrow keys along
with scroll wheel to complete the
setting. Press and hold the F5
(Infinite) button if Infinite execution
is in need.
Under the Sequence function, press F1 (Set) button followed by selecting F2 (Start). The setting on LCD is activated and appears in red font
color
. Use number pad to
set the parameters directly and then
press the F1 (Done) button to
confirm; or use arrow keys along
with scroll wheel to complete the
setting.
Under the Sequence function, press F1 (Set) button followed by selecting F3 (Groups). The setting on LCD is activated and appears in red font
color
. Use number pad
55
End State Operation ON/OFF
CAUTION
GPP-3060/6030 User Manual
to set the parameters directly and then press the F1 (Done) button to confirm;
or use arrow keys along with scroll wheel to complete the setting.
Under the Sequence function, press F1 (Set) button followed by selecting
F4 (End State), and 2 statuses Last/Output off will appear in turn
on LCD
. The one
displaying is what’s called the
current status.
Press the F5 (SEQ.On) button. When the output is on, the Output key will light up. When the output is off, the Output key will not be lit. SEQ will appear in the status area (yellow for CH1 only, blue for CH2 only, while white for both on).
In Sequence ON, the F1 (Restart) button appears, it means that start from the first; in CH1/CH2 running sequence, the F2 (Sync) button appears, it means that two channels start from the first at the same time.
If the channel has been in Output ON before Sequence function, the status remains unchanged until SEQ.On so that Sequence starts to output.
56
BASIC OPERATION
Set Group Parameter
Description
Each Group consists of Voltage, Current and Time. Therefore, properly confirm parameter of each group is correct before setting Sequence output.
Parameter Description
No. Voltage Current Time
Group number. Maximum 2047 Voltage setting of each group. Current setting of each group. Execution duration of each group. Range: 1S 300S
Parameter No. Setting
Under the Sequence function, press
F2 (Edit) button followed by
selecting F1 (No.). The setting on
LCD is activated and appears in red
font color
. Use number
pad to set the parameters directly
and then press the F1 (Done) button
to confirm; or use arrow keys along
with scroll wheel to complete the
setting. The F4 (Page Up)key and F5
(Page Down) key can jump directly
to the previous or next page,each 8
groups is a Page.
Voltage
Under the Sequence function, press F2 (Edit) button followed by selecting F3 (Voltage). The setting on LCD is activated and appears in red
font color
. Use
number pad to set the parameters
directly and then press the F1 (V) or
F2 (mV) button to confirm; or use
arrow keys along with scroll wheel
to complete the setting.
57
Current Time
GPP-3060/6030 User Manual
Under the Sequence function, press F2 (Edit) button followed by selecting F4 (Current). The setting on LCD is activated and appears in red
font color
. Use
number pad to set the parameters
directly and then press the F1 (A) or
F2 (mA) button to confirm; or use
arrow keys along with scroll wheel
to complete the setting.
Under the Sequence function, press
F2 (Edit) button followed by
selecting F2 (Time). The setting on
LCD is activated and appears in red
font color
. Use
number pad to set the parameters
directly and then press the F1
(Second) button to confirm; or use
arrow keys along with scroll wheel
to complete the setting.
Construct Templet
Description
This function can be used for practical applications when different voltage waveforms are required to be output. Users can edit the output waveform according to their needs. The built-in Sine, Pulse, Ramp, Stair Up, Stair Dn, Stair UpDn, Exp Rise, Exp Fall waveforms are practical per usage.
Parameter Description
Object Type
To edit Voltage or Current
Select the buit-in waveforms including Sine, Pulse, Ramp, Stair Up, Stair Dn,
Stair UpDn, Exp Rise,
58
Max Value Min Value Start
Points
Inverted Parameter Object Setting
Type
Max Value
Exp Fall.
BASIC OPERATION
Set the max. value of waveform voltage/current
Set the min. value of waveform voltage/current
Set the initial group number of waveform. Maximum: 2037
Select the required points. Range: 102047
Invert the selected waveform
Press the F1 (Object) button to select
Voltage
/Current
in turn. Simply stop at the
parameter which is in need of
setting.
After pressing the F2 (Type) button, select the button corresponding to the applicable waveform. Up to 8 default waveforms are available for selection.
Press the F3 (Max Value) button. The setting on LCD will be activated and
appears in red front color
. Use number pad to set the parameters directly and then press the F1 (V/A) or
the F2 (mV/mA) button to confirm; or use arrow keys along with scroll wheel to
complete the setting.
59
GPP-3060/6030 User Manual
Min Value
Start
Points
Interval
Press the F4 (Min Value) button. The setting on LCD will be activated and appears in red front color. Use number pad to set the parameters directly and then press the F1 (V/A) or the F2 (mV/mA) button to confirm; or use arrow keys along with scroll wheel to complete the setting.
Press the F5 (More) button and then
press the F1 (Start) button. The
setting on LCD will be activated and
appears in red front color
.
Use number pad to set the
parameters directly and then press
the F1 (Done) to confirm; or use
arrow keys along with scroll wheel
to complete the setting.
Press the F2 (Points) button. The setting on LCD will be activated and appears
in red front color
. Use number pad to set the parameters directly and then press the F1 (Done)
to confirm; or use arrow keys along with scroll wheel to complete the setting.
Setting the time interval of each point of the current selected template (i.e.
the duration of output of each set of timing parameters) ,it can be set from
1s to 300s. Press the F3 (Interval) button. The setting on LCD will be
activated and appears in red front color
. Use number pad to set
60
Inverted Construct Construct
BASIC OPERATION
the parameters directly and then press the F1 (Done) to confirm; or use arrow
keys along with scroll wheel to complete the setting.
Press the F4 (Inverted) button. On
(inverted)
and Off (non-
inverted)
appear on LCD
in turn. Simply stop at the status
which is required.
Press the F5 (Construct) to complte construction.
Menu Tree
Description
User is able to well understand the overall functions of Sequence via menu
tree, which is put in proper order by tiers. The Return key is used for back
to the parent menu. See the construction below:
Level1———— Advance
Level2———— Sequence
Level3—— Set
Edit ……
Cycles
Level4—- Done Level5——-
Return
Level6———(…)
No. ……
61
GPP-3060/6030 User Manual
Advance Sequence
Set
Edit Templet Memory SEQ.On Return
Cycles Done Return Start Done Return
Groups Done Return
Endstate
Infinite Return
No.
Object
Type Restart
Done
Type
*.CSV Sync
PageUp
PageDown Return Time
Sine
Pulse Ramp StairUp
*.SEQ NewFile SEQ.Off
Second Last Next Return
More (Stair Dn)
(Stair UpDn) (Exp Rise) (Exp Fall) (Return)
Return
Save Recall Select
Return
Voltage MaxValue Return
V
V/A
mV mV/mA
Last
Return
Next MinValue
Return
Current A
mA Last Next Return
V/A mV/mA Return
More
Start (Done, Return) Points (Done, Return) Interval (Done, Return) Inverted
Construct
Save
Return
Return Return
Note: In the Memory menu, Type/.CSV/.SEQ/New File/Select appear only when
flash drive is plugged in.
62
BASIC OPERATION
Save and Recall
Description
GPP models can save and recall the Sequence data from internal 10 groups or flash drive.
Parameter Description
Type New File
Avaialble for .CSV or .SEQ file type
Avaialble for creating new .CSV or .SEQ file type
Save
Save the Sequence data to the
specified file.
Recall
Recall the data saved in the specified file.
Select
Select the file folder in need.
Operation
Internal storage
1. In the Sequence menu, press F4 (Memory) button to enter the page as figure show below.
2. Press right arrow button to enter the list of 10 groups.
63
GPP-3060/6030 User Manual
Flash drive storage
3. Rotate the scroll wheel (Encode) to select target file.
4. Press F3 (Save) button to save the settings of Sequence into the
corresponding file.
5.Press the F4 (Recall) button to recall the Sequence file of list to the
current sequence settings when necessary.
1. Plug flash drive in before rotating the scroll wheel (Encode) to select
flash drive.
2. Press right arrow button to enter the root directory of flash drive.
3. Press F1 (Type) button to select required file type .CSV or .SEQ.
4. Rotate the scroll wheel (Encode) to select target file.
64
BASIC OPERATION
5. Press F3 (Save) button to save the settings of Sequence into the
corresponding file. 6. Press the F4 (Recall) button to recall the Sequence
file of list to the current sequence settings when necessary.
65
GPP-3060/6030 User Manual
Delay Function
Description
It is necessary to output a series of pulse in real applications. This
function is available when voltage is constant. Output waveform can be edited
per user’s preference. The amplitude range of the output waveform is the
output voltage range of power supply. The setting range for output waveform
duration is 1s ~ Infinite (duration calculation: Time x Groups x Cycles) and
the resolution is 1s.
Note: This feature is applicable to both CH1 & CH2.
Set Delay Output
Parameter Cycles Description
Start
66
Cycle number, 1 represents a cycle of single period. 2 represents a cycle with
2 periods, and so on. The range is from 1 to 9999 or Infinite.
The number (No.) to start execute. 0 indicates the execution starts from the
group 0, while 1 indicates it begins from the group 1, and so on. The range is
from 0 to 2047.
BASIC OPERATION
Groups End State
Stop Condition Parameter Cycles Setting
Start
The number to be executed. It can NOT exceed 2048 for Start+Groups.
There’re 3 statuses after the necessary Group and Cycle are executed: output termination or output on or being hold with the last step.
Halt the current operation based on the set condition of Voltage/Current/Power.
Press the Advance key on control
panel. Select the F3 (Delay) function.
Press the F1 (Set) button followed by
selecting F1 (Cycles). The setting on
LCD is activated and appears in red
font color
. Use number
pad to set the parameters directly
and then press the F1 (Done) button
to confirm; or use arrow keys along
with scroll wheel to complete the
setting. Press and hold the F5
(Infinite) button if Infinite execution
is in need.
Under the Delay function, press the
F1 (Set) button followed by selecting
the F2 (Start). The setting on LCD is
activated and appears in red font
color
. Use number pad to
set the parameters directly and then
press the F1 (Done) button to
confirm; or use arrow keys along
with scroll wheel to complete the
setting.
67
GPP-3060/6030 User Manual
Groups
Under the Delay function, press the F1 (Set) button followed by selecting the F3 (Groups), the setting on LDC will be activated and appears in red
font
. Use number pad
for direct setting followed by
pressing F1 (Done) key to confirm; or
use arrow keys along with scroll
wheel to complete setting.
End State
Stop Condition
Under the Delay function, press the F1 (Set) button followed by selecting the
F3 (Groups), and 3 statuses Last/Output on/ Output off will appear in turn on
LCD
. The one displaying is what’s called the current status.
Under the Delay function, a condition of stopping operation can be set. When
the instrument monitors the condition, the execution of delay function can be
terminated. press the F3 (Stop) button and halt the operation by setting
voltage F2 (Voltage), current F3 (Current) and power F4 (Power), or Stop
infinitely by F1 (None). The output state of the instrument after stopping is
determined by the setting of “End State”.
Operation ON/OFF 68
Press the F5 (Delay On) button. Output is open when output lights up; whilst output is off when output lights out. DLY appears on the status bar (yellow for CH1, blue for CH2, and white for both CH1 & CH2 on). At this time, the F5 button will become “Delay OFF”, which can
Warning
BASIC OPERATION
perform the function of closing Delay . In Delay ON, the F1 (Restart) button
appears, it means that start from the first; in CH1/CH2 running delay, the F2
(Sync) button appears, it means that two channels start from the first at the
same time.
If the channel has been in Output ON before Delay function, the status remains
unchanged until Delay.On so that the corresponding waveform starts to output.
Set Group Parameter
Description
Each Group consists of Vltage, Current and Time. Therefore, properly confirm parameter of each group is correct before setting Delay output.
Parameter No. Descriptiom
State
Group number. Maximum 2047
Output status of each group: On, Off
Time
Execution duration of each group. Range: 1s 300s
Patterm
Set the initial status of initial group. 01 Patt: start from Off; 10Patt: start from On
Time set
It is used to generally set the pattern of time change. Model is for the changes covering fix (FixTime), increase (Increase) and decline
69
Parameter No. Setting
State Time
70
GPP-3060/6030 User Manual
(Decline). Base Time is for setting time of initial Group. Step is for setting
time interval of neighboring Group.
Under the Delay function, press the
F2 (Edit) button followed by
selecting the F1 (No.). The setting on
LCD is activated and appears in red
font color
. Use number
pad to set the parameters directly
and then press the F1 (Done) button
to confirm; or use arrow keys along
with scroll wheel to complete the
setting. The F4 (Page Up)key and F5
(Page Down) key can jump directly
to the previous or next page,each 8
groups is a Page.
Under the Delay function, press the F2 (Edit) button, and then the F2 (State) button followed by selecting F1 (On), F2 (Off) or F3 (Inverted) to set output On/Off status of each group. Press the F4 (Last) key for the previous one and the F5 (Next) key for the next one
Under the Delay function, press the F2 (Edit) button followed by selecting the F3 (Time). The setting on LCD is activated. Use number pad to set the parameters directly and then press the F1 (Second) button to confirm; or use arrow keys along with scroll wheel to complete the setting. Press the F4 (Last) key for the previous one and the F5 (Next) key for the next one.
BASIC OPERATION
Patterm
Time Set
On Delay Off Delay Base Time Step
Under the Delay function, press the F2 (Edit) button followed by selecting F4
(Pattern), and then set up via F1 (01Patt) and F2 (10Patt). The live setting
result appears on the LCD.
Under the Delay function, press the F2 (Edit) button followed by selecting the
F5 (Time Set), and then set time change patterns of each group, There are 3
types”Time Gen” options:fix (FixTime), increase (Increase) and decline
(Decline) of which are available) via F1 (Model). The live setting result
appears on the LCD.
When fix (FixTime) is set in Time Set, it’s available to set the time value of
both F2 (On Delay) and F3 (Off Delay)at the same time.
When increase (Increase) or decline (Decline) is set in Time Set, it’s
available to set the time value of F2 (Base Time) start time and F3
(Step)group change at the same time.
71
GPP-3060/6030 User Manual
Menu Tree
Description
User is able to well understand the overall functions of Delay via menu tree, which is put in proper order by layer. The Return key is used for back to the parent menu. See the construction below:
Level1———— Advance Level2———— Delay
Level3—— Set
Edit ……
Level4—- Cycle No. ……
Done Level5——-
Return
72
BASIC OPERATION
Advance Delay
Set
Edit
Stop
Cycles
No.
None
Done Done Voltage
Return
PageUp Define
PageDown V Return mV
Start
State Return
Done Return
On Off Inverted Last Next Return
Current
Define A mA
Return
Groups Time Power
Done Return
Endstate
Second Last Next Return Patterm
Define W mW
Return Return
Infinite
01 Patt 10 Patt Return Time Set
Return Model
On Delay Off Delay
Return
Memory Delay On Return
Type
.CSV .DLY
Restart Sync
Delay.Off
NewFile Return
Save
Recall Select
Return
Note: In the Memory menu, Type/.CSV/. DLY/New File/Select appear only when flash drive is plugged in.
73
GPP-3060/6030 User Manual
Save and Recall
Description GPP models can save and recall the Delay data from internal 10 groups or flash drive.
Parameter Type Description
New File
Avaialble for .CSV or .DLY file type
Avaialble for creating new .CSV or .DLY file type
Save
Save the delay data to the specified
file.
Recall
Recall the data saved in the specified file.
Select
Select the file folder in need.
Operation Internal Storage
1. In the Delay menu, press F4 (Memory) button to enter the page as figure show below.
2. Press right arrow button to enter the file list of 10 groups.
74
BASIC OPERATION
Flash drive storage
3. Rotate the scroll wheel (Encode) to select target file.
4. Press F3 (Save) button to save the settings of Delay into the
corresponding file.
5. Press the F4 (Recall) button to recall the Delay file of list to the
current sequence settings when necessary.
1. Plug in flash drive before rotating the scroll wheel (Encode) to select
flash drive.
2. Press right arrow button to enter the root directory of flash drive.
3. Press F1 (Type) button to select required file type .CSV or .DLY.
4. Rotate the scroll wheel (Encode) to select target file.
75
GPP-3060/6030 User Manual
5. Press F3 (Save) button to save the settings of Delay into the
corresponding file. 6. Press the F4 (Recall) button to recall the Delay file
of list to the current sequence settings when necessary.
76
BASIC OPERATION
Monitor Function
Description
In order to have well understanding of the channel under long-term output, the
GPP series has the additional live monitor function, which helps guarantee
load status of client via halting operation based on certain preset
conditions.
Warning: this feature is Not applicable to CH3.
Set Monitor
Parameter Description
Voltage Current
Power
Stop Type
Select
Set condition of monitor of voltage.
Set condition of monitor of current.
Set condition of monitor of power.
Set status after halt. 3 types are available, output disable, content notice
and audible alarm.
To confirm if voltage/current/power is selected as monitor object. White font
stands for selected, while gray font represents
77
Parameter Setting
Voltage
Current 78
GPP-3060/6030 User Manual
not selected.
Press the Advance key on control panel. Select the F4 (Monitor) function
followed by pressing the F1 (Voltage) button to enter the voltage setting.
1. Press the F1 (Set) button. The setting on LCD is activated and appears in
red font color. Use number pad to set the parameters directly; or use arrow
keys along with scroll wheel to complete the setting.
2. Press the F4 (Define) button to define terminated condition.
3. Press the F5 (Logic) button to define logical pattern of other conditions.
Press the Advance key on control panel. Select the F4 (Monitor) function
followed by pressing the F2 (Current) button to enter the current setting.
1. Press the F1 (Set) button. The setting on LCD is activated and appears in
red font color. Use number pad to set the parameters directly; or use arrow
keys along with scroll wheel to complete the setting.
2. Press the F4 (Define) button to define terminated condition.
BASIC OPERATION
Power
Stop Type Operation ON/OFF
3. Press the F5 (Logic) button to define logical pattern of other conditions.
Press the Advance key on control panel. Select the F4 (Monitor) function
followed by pressing the F3 (Power) button to enter the power setting.
1. Press the F1 (Set) button. The setting on LCD is activated and appears in
red font color. Use number pad to set the parameters directly; or use arrow
keys along with scroll wheel to complete the setting.
2. Press the F4 (Define) button to define terminated condition.
3. Press the F5 (Logic) button to define logical pattern of other conditions.
Press the Advance key on control panel. Select the F4 (Monitor) function
followed by pressing the F4 (Outoff) button to set output disable; select F2
(Alarm) to set content notice; select F3 (Beeper) to set audible alarm. Buzzer
should be turned on in system settings when Beeper is enabled, refer to page
96.
Press the F5 (MON. On) button to enter live monitor. MON appears on the status
bar (the color of channel
79
GPP-3060/6030 User Manual remains the original when single channel is enabled,
whilst it turns to white when multiple channels are activated).
80
BASIC OPERATION
Recorder Function
Description
In order to have well understanding of the channel under long-term output, the GPP series has the additional live record function, which saves file via media for further analysis later.
Warning: this feature is Not applicable to CH3.
Set Recorder
Parameter Period Description
Groups
Channel
Memory
Parameter Period Setting
Set period of each recorded.
Set recorded group number.
Set recorded channel.
Set saving location of record.
Press the Advance key on control panel. Select F5 (Recorder) function. Press
F1 (Period) button to enter setting of recorded period. The setting on LCD is
activated and appears in red font color. Use
81
Groups Channel Memory
GPP-3060/6030 User Manual
number pad to set the parameters directly and then press the F1 (s) button to
confirm; or use arrow keys along with scroll wheel to complete the setting.
Press the Advance key on control panel. Select the F5 (Recorder) function.
Press the F2 (Groups) button to enter setting of recorded group number. The
setting on LCD is activated and appears in red font color. Use number pad to
set the parameters directly and then press the F1 (Done) button to confirm; or
use arrow keys along with scroll wheel to complete the setting.
Press the Advance key on control panel. Select the F5 (Recorder) function.
Press the F3 (Channel) button to enter setting of recorded channel. F1 (CH1),
F2 (CH2), F3 (CH3) are available for selection. The numbers of channel may
vary by models.
Press the Advance key on control panel. Select the F5 (Recorder) function
followed by pressing F4 (Memory) button to setting of recorded saving.
Recorded data can be stored in internal memory or external USB Flash.
82
BASIC OPERATION
Internal Storage
1. Press right arrow button to enter the list of 10 groups. Rotate the scroll wheel (Encode) to select target file. Also rotate the scroll wheel (Encode) to enter the flash drive when necessary.
2. Press F3 (Save) button to save the temporary data into the corresponding
file.
3. Press F4 (Recall) button to save the record data of file into the
temporary storage for further saving into flash drive later.
83
Flash drive operation descriptio n
GPP-3060/6030 User Manual
Type/.CSV/ .REC/New File/Select buttons appear when flash drive is selected.
Note: Type is used to select .CSV and .REC file types.
New File is used to create new file.
Select is used to open the required file folder.
Operation ON/OFF
Press F5 (REC.On) button to enter live record function. REC appears on the status bar (the color of channel remains the original when single channel is enabled, whilst it turns to white when multiple channels are activated).
84
BASIC OPERATION
External I/O Control
Description Function
The GPP series models provides user with a programmable external trigger port,
which is used to dock certain functions control.
It can turn each Data Line (D0,D1,D2,D3,D4) into input signal respectively to
have command of the following four functions:
1. Control of channel On/Off
2. Control of Tracking mode
3. Toggle between PWR/Load modes
4. Toggle between CC/CV/CR modes under Load
The conditions listed below for output signal setting:
1. Channel output On/Off
2. Beyond the setting of Voltage/Current/Power
85
GPP-3060/6030 User Manual
Rear Pannel Control Port
Schematic diagram for control signal
Up to 10 terminals within the control port; the upper 5 terminals can be set
input/output functions, while the lower 5 are ground terminals. See diagram in
right side for details (rear view).
The control circuit of each port is illustrated as the diagram below (D1 for
example)
I/O port Input
Output
Electrical characteristics
Low Level DC Voltage High Level DC Voltage
Low Level DC Voltage High Level Voltage DC output Current
0.3V 3.3V 0.3V 3.3V 0.6mA
86
BASIC OPERATION
Key Function Description
Input/Output Mode:
Key Function Operation Result
F1 Data Line Select object to be set from D0 to F4
F2 Enable
Set to Enable or Disable function of the port
F3 Mode
Set which mode to adopt: Input Mode or
Output Mode
F4 Channel Select corresponding channel: F1(CH1), F2
(CH2), F3 (CH3)
F5 More
F6 Return
F5 (More) under Input Mode setting:
Key Function Operation Result
F1 Type
Select trigger type: F1(RiseEdge), F2
(FallEdge), F3 (Hi-Level), F4 (Lo-Level), ,
F5(States Input)
- “States Input” equivalent to edge trigger
(RiseEdge + FallEdge)
F2 Response Set result after trigger response:
F1(Output) sets as ON, OFF or reverse
Toggle
F2 (PWR.Mode) sets channel as power mode
F3 (Load Mode) set channel as load
CV/CC/CR mode
F4(Track Mode) sets tracking mode of
CH1/CH2. This function will only work if
channels CH1 and CH2 are selected
simultaneously(only source mode),GPP-1326
does not have such function.
F3 Sensitivity Set sensitivity of trigger: High/Middle/Low
F4
F5
F6 Return
87
GPP-3060/6030 User Manual
F5 (More) under Output Mode setting:
Key Function Operation Result F1 Condition Set response type: F1(Output), F2
(Voltage),
F3 (Current), F4 (Power), F5 (Auto)
F2 F3,F4 F5 F6
Polarity
State Out. Return
Note: F5 (Auto) triggers automatically only when voltage, current or power
triggers meet at least one condition. Set the polarity of output signal
Enable or disable the state output
Description
Operation
Press the System key on control panel. Select the F1 (Interface) function followed by pressing the F5 (Control I/O) button to enter the setting of external I/O.
Press the F1 (Data Line) button. Select required data line from D0 through D4: F1(D0), F2(D1) , F3(D2) , F4(D3) , F5(D4).
Press the F2 (Enable) button to set this terminal as input or output function. This button enables Enable or Disenable to be selected in turn.
Press the F3 (Mode) button to set this terminal as input or output function. This button enables Input Mode or Output Mode to be selected in turn.
Press the F4 (Channel) button to activate the Channel of this terminal:F1(CH1), F2(CH2), F3(CH3).
Key F5 (More)
After pressing the F3 (Mode) button, Trigger in and Trigger out will bring about different results individually. Refer to the table above for details.
88
FILE OPERATION
FILE OPERATION
Restore Factory Default Settings ………………………… 93
89
GPP-3060/6030 User Manual
Save/Recall
Description
System provides user with 4 different files, each of which has 10 groups including parameter setting .set, use record .rec, sequence output .seq and delay output .dly.
Note: Both file folder and name in flash drive are limited within 8 characters.
Set file 1. Press the Memory button to enter the interface. Rotate
operation
the scroll wheel (Encode) to select file of either
*.set
internal memory or flash drive.
90
FILE OPERATION
2. Press the right arrow button to enter the file group. Rotate the scroll
wheel (Encode) and stop at the file in need
3. Press the F3 (Save) button to have the settings of current model saved into the corresponding file.
4. Or press the F4 (Recall) button to recall the corresponding file, whose file name will be shown on the status bar.
Recorded file operation *.SEQ
Refer to page 63 for chapter of save and recall Sequence data.
Note: .SEQ file can be edited in PC by the specified format (.CSV or *.SEQ)
and imported, via flash drive, into machine.
Recorded file operation *.DLY
Refer to page 74 for chapter of save and recall Delay data.
Note: .DLY file can be edited in PC by the specified format (.CSV or *.DLY)
and imported, via flash drive, into machine.
91
GPP-3060/6030 User Manual
Recorded file operation *.REC
Power-on setting
Refer to page 84 for chapter of Memory operation of Record.
Note: .REC file can be edited in PC by the specified format (.CSV or *.REC)
and imported, via flash drive, into PC.
In the System Setting menu, the interface parameter settings area shows Power
On. There are 2 settings to choose from, Last (the last shut down status) and
Default (non-modifiable factory default setting).
To enter the function, press the System button to enter the interface followed
by pressing the F2 (Power on) button.
92
FILE OPERATION
Restore Factory Default Settings
Description
There’s a group of Default value, the nonmodifiable factory default setting. User is able to restore Default or proceed to Preset operation from Power On under System.
Operation
Press the System button to enter the interface followed by pressing either the F2 (Power On) or the F5 (Preset) button to select Default.
Default setting of each channel
Channel item Voltage OVP
Disp Type Model Tracking
Parameter
00.000V 5V(CH3) CH1/2:
Off, 35V(3060) Off, 65V(6030)
CH3:
Off, 5.5V
Type1 PWR Indep.
Channel item Parameter
Current
0.0000A
OCP
Vset(Load) Iset (Load) Rset(Load)
CH1/2:
Off, 6.5A(3060) Off, 3.5A(6030)
CH3 usb port:
On, 3.1A
1.500V 0.000A 0050
Default setting of system
System item Parameter
Beeper Backlight Power On Output Panel
On High Default Front
System item
Subnet Mask HOST Name
Parameter
255.255.0.0 GPP
93
SYSTEM SETTINGSREMOTE CONTROL
SYSTEM SETTINGS
System Information
System Information
The picture below shows complete system information. If the selected model is without ports (GPIB, LAN), the corresponding info will disappear.
GPIB
LAN
Check operation System Version
Check operation
Press the System button on the panel to show the screen as above.
Model
View the device Model.
Firmware
View the system software version.
Serial Number
View the machine serial number.
Press the System button followed by pressing the F4 (Version) button to show the above system version window.
95
GPP-3060/6030 User Manual
System Settings
Description
It can be used to perform system operations for machine.
Setting
Interface
information
Remote control and relevant data output setting
Power On
Power on initial state setting
Language
menu language setting
BackLight
Adjust the LCD brightness.
Beeper
Sets when the buzzer is turn on.
Upgrade
Firmware upgrade
Hardcopy
For Screenshot operation
Preset
Restore to Factory Settings
Output panel
Select front or rear output
Remote control setting
The System menu, press the F1 (Interface) button to select port in need. For more details, refer to page 101.
Power on initial state setting
In the System menu, press the F2 (Power On) button to select required power on setting: Last (the last shut down setting) and Default (factory default setting).
Menu language setting
The System menu, press the F3 (Setting) button followed by selecting the F1 (Language) to locate the F1 (English) button or the F2 (Chinese) button.
96
SYSTEM SETTINGS
Backlight brightness adjustment
Buzzer operation
Firmware upgrade
Screenshot operation
Restore to Factory Settings
In the System menu, press the F3 (Setting) button followed by selecting the F2
(Backlight) to adjust backlight brightness. There are three brightness levels:
High, Middle, and Low. Select from pressing the F1 (Low) or F2 (Middle) or F3
(High) button.
In the System menu, press the F3 (Setting) button followed by selecting the F3
(Beeper) to turn on or turn off the buzzer beeper.
In the System menu, press the F3 (Setting) button followed by selecting the F4
(Upgrade) button to upgrade the machine to the latest software version. For
more details, refer to page 97.
In the System menu, press the F3 (Setting) button followed by selecting F5
(Hardcopy) to proceed to screenshot operation. For more details, refer to page
99.
In the System menu, press the F5 (Preset) button to restore to the factory
default setting. For more details, refer to page 93.
Select front or rear output
Double click system key, press F1 (front) key to select front port output or F2 (rear) key to select rear port output, refer to page 31.
97
GPP-3060/6030 User Manual
Firmware Upgrading
When to Upgrade Firmware Upgrade Requirement Operation
Note
When system is failure, request by customer GW Instek. When the system fails, firmware can requested by GW Instek customers.
Firmware file
Supplied by GW Instek
After plugging in flash drive, the corresponding symbol appears in the status
bar.
Press System button;
Press F3 (Setting) button;
Press F4 (Upgrade) button;
Rotate the scroll wheel to select corresponding file;
Press the F4 (Recall) button and start to upgrade;
The procedure is done when the message, upgrading successful, shows up.
Flash drive only support USB2.0/USB3.0,FAT32 file system,16G MAX.
98
SYSTEM SETTINGS
Description of Using Flash Drive
Description
Operation
Software Update Screenshot operation
It can be used when upgrading the software upgrades, screenshot operation and
importing or exporting files. Flash drive only support USB2.0/USB3.0,FAT32
file system,16G MAX.
Insert flash driver into the USB Host port. Then the system identifies the
flash driver and the indentification appears in the status bar.
refer to page 97
In the target interface, press System button > F3 (Setting) > F5 (Hardcopy)
button and rotate the scroll wheel (Encode) to locate the target interface
followed by pressing Enter key to save screenshot. A confirm voice will sound
when successful.
The file format of screenshot is *.BMP and is saved in the root directory of
flash drive by default.
99
Exporting the Sequence data
GPP-3060/6030 User Manual
The files of Sequence (.SEQ), Recorder (.REC), Delay (.DLY), etc within
machine can be, in addition to individual format, converted to .CSV file
format for easy check and edit in PC by user. For more details, refer to page
90.
100
REMOTE CONTROL
REMOTE CONTROL
Connection Usage
This chapter describes how to set and enable port, as well as all the required
preparations prior to operation.
Port type
The GPP series has 2 standard remote control ports (RS-232, USB), and 2 optional ports (GPIB, LAN).
Port selection
It is allowed to control the GPP series by only single remote control method once time. Before to use, it’s required to select or confirm beforehand.
Operation
Press the System button followed by pressing
the F1 (Interface) button to select the target
port: F1 (RS-232), F2 (USB), F3 (GPIB), F4
(LAN). The available ports
will
appear on the LCD.
State
The selected port will appear in the status bar with font color in gray, for instance , whilst it will change to white color after successful commnad operation.
103
RS-232
Description Interface Connection
Parameter Setting
Display
GPP-3060/6030 User Manual
The GPP series models can be remotely controlled by RS-232 connection.
Rear panel RS-232 port
Under power-off state, connect RS-232 cable and select RS-232 port in the
Interface. The message USB232 will appear gray in the status bar when
connection, and turns to white color while the first command connects
succesfully.
Panel control will be automatically under lock state when connection is
successful.
Press the System button followed by pressing the F1 (Interface) button to
select the target port: F1 (RS-232). The setting of baud rate will appear
automatically, please then choose desired setting.
The parameter information of RS-232 will appear on LCD. Refer to the
description below:
8 —>data bit 8bit N —>no parity bit 1 —>stop bit 1bit N —>no flow control bit
104
REMOTE CONTROL
Function check
Perform the following query:
*IDN?
The unit will return the manufacturer, model, serial number and software version.
GW INSTEK, GPP-3060, SN: xxxxxxxx, Vx.xx
Disable Remote Control Mode
Send a remote command Local from the PC.
Long-press the F6 (unlock) key on the front panel.
Warning: RS-232 is Not hot-plug device. Please proceed to the connection procedure under the power-off state.
105
GPP-3060/6030 User Manual
USB
Description Interface
GPP can be connected via USB using the USB Communications Device (CDC) class.
Rear panel USB device port.
Installing the Driver
Install the USB driver provided by suppiler in PC.
Select USB port in the Interface after connecting the USB cable. The message USB will appear gray in the status bar when connection, and turns to white color while the first command connects succesfully.
The front panel keys are automatically locked when the connection is successful.
Parameter Setting
Press the System button followed by pressing the F1 (Interface) button to select the target port: F2 (USB). The setting of baud rate will appear automatically, please then choose desired setting.
Display
The parameter information of USB will appear on LCD. Refer to the description below:
115200—-> transmission baud rate
106
REMOTE CONTROL
Function Check
Perform the following query:
*IDN?
The unit will return the manufacturer, model, serial number and software version.
GW INSTEK, GPP-3060, SN: xxxxxxxxx, Vx.xx
Send a remote command from the PC Disabling Remote Control Mode Long-press the
F6 (unlock) key on the front
panel.
Unplug the USB cable from the rear panel.
Note
USB devices are hot-plug devices. You can directly remove the cable and exit.
107
GPP-3060/6030 User Manual
GPIB
Description Interface
The communication data format, compatibility settings and GPIB address must
all be configured before using GPIB remote control.
Rear panel GPIB port.
Connection
Select GPIB port in the Interface after connecting the GPIB cable. The message GPIB will appear gray in the status bar when connection, and turns to white color while the first command connects succesfully.
The front panel keys are automatically locked when the connection is successful.
Parameter Setting
Press the System button followed by pressing the F1 (Interface) button to select the target port: F3 (GPIB). The setting of communication address will appear automatically. Input required address when the setting of GPIB Addr turn red color and press the F1 (Enter) button to confirm.
Display
The address information of GPIB will appear on LCD. Refer to the description below:
11—-> GPIB address of the current unit 108
REMOTE CONTROL
Exiting from Remote Control Mode
Send a remote command from the PC
Long-press the F6 (unlock) key on the front panel.
109
GPP-3060/6030 User Manual
LAN
Description Connection Set port
Edit Host name
When using the LAN port, the relevant parameters are supposed to be set
earlier.
Select LAN port in the Interface after connecting the LAN cable. The message
LAN will appear gray in the status bar when connection, and turns to white
color while the first command connects succesfully.
The front panel keys are automatically locked when the connection is
successful.
A. Press the System button to enter the system interface followed by pressing
the F1 (Interface) button to configure port parameter.
B. Press the F4 (LAN) button to configure internet port parameter.
A. Press the System button to enter the system interface followed by pressing
the F1 (Interface) button to configure port parameter.
B. Press the F4 (LAN) button to configure internet port parameter.
C. Press the F1 (Config) button to configure relevant parameter.
110
IP Mode Manual IP
REMOTE CONTROL
D. press the F4 (Host Name) button to manually input. The Name area will be
activated and become red color after setting. The default first letter is A,
and can be changed to other string by rotating scroll wheel Encoder (A, B…Z,
a, b…z, 1, 2…9, 0, – in clockwise sequence). Press the F1 (Enter) button to
confirm current string and automatically enter the next string input. Repeat
the process above until completing a full name.
The IP address can be obtained by using either DHCP or Manual IP.
A. Press the System button to enter the system interface followed by pressing
the F1 (Interface) button to configure port parameter.
B. Press the F4 (LAN) button to configure internet port parameter.
C. Press the F2 (Config) button to configure relevant parameter.
D. Press the F3 (Manual) button to manually configure.
E. press the F1 (IP Addr) button to manually input IP address. The set content
will be activated to become red color. Input required data and confirm by
pressing the F1 (Done) button. Press the F5 (Clear) button to clear and input
again if error occurs.
111
GPP-3060/6030 User Manual
F. return to the Manual configuration menu and repeat manually configuring
NetMask. Press the F2 (NetMask) button to manually input data. The set content
will be activated to become red color. Input required data and confirm by
pressing the F1 (Done) button. Press the F5 (Clear) button to clear and input
again if error occurs.
G. return to the Manual configuration menu and repeat manually configuring
GateWay. Press the F3 (GateWay) button to manually input data. The set content
will be activated to become red color. Input required data and confirm by
pressing the F1 (Done) button. Press the F5 (Clear) button to clear and input
again if error occurs.
Parameter Settings:
IP Address: IP address range: 1.0.0.0 to 223.255.255.255 (excluding
127.nnn.nnn.nnn).
Subnet Mask: Subnet Mask Range: 1.0.0.0 to 255.255.255.255.
Gateway: Gateway range: 1.0.0.0 to 223.255.255.255 (excluding
127.nnn.nnn.nnn).
VISA Resource name TCPIP0::169.254.129.17::1026::SOCKET
112
DHCP PC Operation
REMOTE CONTROL
A. Press the System button to enter the system interface followed by pressing
the F1 (Interface) button to configure port parameter.
B. Press the F4 (LAN) button to configure internet port parameter.
C. Press the F1 (Config) button to configure relevant parameter.
D. Press the F1 (DHCP) button. The unit will be assigned an IP address, subnet
mask, the default gateway and other network parameters from the DHCP server.
The corresponding parameters will be shown in the parameter area.
1. Enter the IP address into Microsoft Internet Explorer (IE). After entering
the IP address you will be shown the Welcome screen which displays the
instrument information. The page also provides three links: Welcome Page,
Browser Web Control and View & Modify Configuration (network settings).
113
GPP-3060/6030 User Manual 2. Click on “Browser Web Control” to execute
commands through the browser, as shown below.
3. Press the “View & Modify Configuration” icon to enter the Modify Config
menu, as shown below.
114
REMOTE CONTROL
4. Click “Modify Config” to enter the network configuration setting menu, as
shown below. Use the mouse to click on “Save and Restart” to change the remote
settings for the GPP series.
Note
Click “Undo Edits” to cancel all the edited settings. Click “Factory Defaults” to restore to the factory default settings.
Exiting from Remote Control Mode
Send a remote command from the PC
Long-press the F6 (unlock) key on the front panel.
Unplug the USB cable from the rear panel.
Note
Hot-swappable LAN devices can be directly disconnected to exit.
115
GPP-3060/6030 User Manual
Command Syntax
The commands that are used with the GPP meet IEEE488.2 and SCPI standards.
SCPI Commands Overview SCPI
Command Format SCPI is an ASCII based command language designed for test and
measurement instruments. SCPI commands uses a hierarchical structure (tree
system), and is divided into different subsystems. Each subsystem is defined
by a different root keyword. Each command consists of a root keyword and one
or more hierarchical key words separated by a colon “:” and followed by a
parameter. There is always a space between the keywords and the parameters.
Any commands followed by a question mark (?) are queries.
For Example: :SYSTem:BEEPer:STATe {0|1|OFF|ON} :SYSTem:BEEPer:STATe?
SYSTem is the root level keyword and BEEPer and STATe are the secondary and
tertiary level keywords. All levels have a “:” separating each keyword.
Parameters are enclosed in “{ }”. The commands SYSTem:BEEPer:STATe has
{0|1|OFF|ON } as parameters. The parameters are separated with a space.
SYSTem:BEEPer:STATe? indicates that the command is a query. In addition some
commands have multiple parameters that are usually separated by a comma “,”.
For example: :STATus:QUEue:ENABle (-110:-222, -220).
116
REMOTE CONTROL
Symbol Description SCPI commands have the following conventional symbols.
These symbols are not commands but are used to describe the command
parameters.
1. Curly Brackets { } Curly Bracket enclose command string parameters, for
example: {OFF|ON}
2. Vertical Bars | Vertical bars are used to separate one or more optional
parameters. Only one command can be selected. With the following two
parameters, {ON|OFF} only ON or OFF can be selected.
3. Square Brackets [ ] The contents inside square brackets represent keywords
or parameters that can be omitted when executing a command. For example: For
the commands :OUTPut[:STATe] {ON|OFF}, [STATe] can be omitted.
4. Angle Brackets < > The parameters in angle brackets must be substituted
with a valid parameter. For example: For the command :DISPlay: CONTrast
Parameter Types
GPP-3060/6030 User Manual
The commands have a number of different parameter categories. How the parameters are set depend on the parameter categories.
1. Boolean Commands parameter that have to states “OFF” and “ON”, for example, DISPlay:FOCUs {ON|OFF}. “ON” will turn on the focus display function, while “OFF” will turn it off.
2. Consecutive Integers Parameters that use consecutive integers, for
example: For the command :DISPlay:CONTrast
3. Continuous Real Number Parameter that must be a continuous real number can
have any value within the effective range and accuracy. For example: The
command CURRent {
4. Discrete For discrete parameters, only those values that are listed can be used. For example: The *RCL {0|1|2|3|…|9} command can only use 0, 1, 2, 3, …, 9.
118
REMOTE CONTROL 5. ASCII Strings
ASCII string parameters must use a combination of ASCII characters in a
string. For example: For the command: MODE
Command Abbreviations The syntax for SCPI commands contains a combination of
upper and lower case letters. The upper case letters in a command represent
the short form of that command. Commands are not case sensitive and can used
in both upper and lower case. Note, however, to use the short form of the
command, only the capital letter part of the command can be used (no other
abbreviation can be used). For example:
:MEASure:CURRent? Can be abbreviated to: :MEAS:CURR?
Command Terminators When sending a command to the function generator, the
command must be terminated with a
119
Command List
GPP-3060/6030 User Manual
Command Details
When using commands to select a specific channel, [1] stands for CH1, [2]
stands for CH2. “1” can be omitted when you want to select CH1 as it is
selected by default. However if you wish to select CH2, “2” must be selected.
Measurement Commands
Command :MEASure[1|2|3] :
Function
Performs a “READ?” query on the specified measurement function.
Description
VOLTage[:DC]:Measures the voltage.
POWEr[:DC]:Measures the power.
Example :MEASure2:CURRent?
Reads back the CH2 current value.
Note
About CH3 , The query voltage will return the set value, current and power will return zero.
Command Function Example
Note
:MEASure[1|2|3]:ALL? Query the all measurement functions. :MEASure2:ALL? Reads back the CH2 voltage ,current and power value. CH3 will return: voltage setting,0,0.
Command Function
:MEASure:
Query the specified measurement function in all channels.
130
REMOTE CONTROL
Description < function >: VOLTage,CURRent,POWEr
Example :MEASure:VOLTage:ALL?
Reads back the all channels voltage value.
Note
About CH3 , The query voltage will return the set value, current and power will return zero.
Command VOUT
Function Returns the actual output voltage.
Description X 1= CH1, 2= CH2
Example VOUT1?
Returns the CH1 output voltage.
Note
About CH3, The query voltage will return the set value.
Command IOUT
Function Returns the actual output current.
Description X 1=CH1, 2=CH2
Example IOUT1?
Returns the CH1 output current.
Note
About CH3 , The query current will return zero.
131
GPP-3060/6030 User Manual
Display Commands
Command :DISPlay:ENABle
Function
Turn the LCD display on or off.
Description b 0/OFF: Turns the display off.
1/ON: Turns the display on.
Example
:DISPlay:ENABle ON
Turns the LCD display on.
Command Function Return
Example
:DISPlay:ENABle? Queries the state of the display. 0/OFF: Display turned off. 1/ON: Display turned on. :DISPlay:ENABle? Returns the state of the display.
Command Function Description
Example
:DISPlay:BRIGhtness
Middle High :DISPlay:BRIGhtness Low Sets the backlight to Low.
Command Function
:DISPlay:BRIGhtness? Queries the brightness of the display.
132
Return Example
REMOTE CONTROL
Low: The brightness is low, Middle: The brightness is low, High: The
brightness is low. :DISPlay:BRIGhtness? Returns the brightness of the display.
Command Function Example
:DISPlay:TYPE {1|2|4|5|6|7}
Sets the display screens. For details, see page 34. :DISPlay:TYPE 4 Sets the
display screens of TYPE4.
Command Function Return
Example
:DISPlay:TYPE?
Queries the TYPE of display screens. 1: The type of display is TYPE1, n: The
others are similar to 1. :DISPlay:TYPE? Returns the TYPE of display screens.
133
GPP-3060/6030 User Manual
Output Commands
Command :OUTPut[1|2|3][:STATe]
Function
Turns the output on or off.
Description
0/OFF: Turn off the output
1/ON: Turn on the output
Example
:OUTPut1:STATe ON
Turns on the output of CH1.
Command Function Return
Example
:OUTPut[1|2|3][:STATe]? Queries the output state. 0/OFF: The output is turned off. 1/ON: The output is turned on. :OUTPut1:STATe? Returns the output state of CH1.
Command Function Example
:ALLOUTON Turns the channels output on. :ALLOUTON Turns the channels output on.
Command Function Example
:ALLOUTOFF Turns the all channels output off. :ALLOUTOFF Turns the all channels output off.
Command Function 134
OUT
Example
REMOTE CONTROL
Command Function Example
ROUTe:TERMinals {FRONt/REAR} Set the front or rear terminal output. ROUTe:TERMinals REAR Set output from rear terminal.
Command Function Return
Example
ROUTe:TERMinals? Query front or rear terminal output. FRONt: Output from front terminal. REAR: Output from rear terminal. ROUTe:TERMinals?
Command Function Description
Example
:OUTPut[1|2|3]:OVP:STATe
Turns OVP protection on/off.
0/OFF:Turns OVP off.
1/ON:Turns OVP on.
:OUTPut2:OVP:STATe ON
Turn on OVP on CH2.
Command Function Return
:OUTPut[1|2|3]:OVP:STATe? Queries the status of the OVP function. 0/OFF: OVP function is off. 1/ON: OVP function is on.
135
Example
GPP-3060/6030 User Manual
:OUTPut2:OVP:STATe? Returns the status of the OVP function on CH2.
Command Function Return
Example
:OUTPut[1|2|3]:OVP:TRIGer?
Query whether the OVP protection function has been triggered.
0/OFF: The channel OVP protection is not triggered.
1/ON: The channel OVP protection has been triggered.
:OUTPut2:OVP:TRIGer?
Return whether the OVP protection function of channel 2 has been triggered.
Command Function Description Example
Note
:OUTPut[1|2]:OVP
Sets the OVP level.
Refer to the specification sheet on page 200 for value.
:OUTPut2:OVP 10.5
Sets the OVP voltage to 10.5V for CH2.
About CH3, The OVP value can not be set.
Command Function Example
Note
:OUTPut[1|2|3]:OVP? Queries the OVP voltage level. :OUTPut2:OVP? Queries the OVP voltage level on CH2. About CH3, OVP query value is 5.5V.
136
REMOTE CONTROL
Command Function Description
Example
:OUTPut[1|2|3]:OCP:STATe
Turns OCP protection on/off.
0/OFF:Turns OCP off.
1/ON:Turns OCP on.
:OUTPut2:OCP:STATe ON
Turn on OCP on CH2.
Command Function Return
Example
:OUTPut[1|2|3]:OCP:STATe? Queries the status of the OCP function. 0/OFF: OCP function is off. 1/ON: OCP function is on. :OUTPut2:OCP:STATe? Returns the status of the OCP function on CH2.
Command Function Return
Example
:OUTPut[1|2|3]:OCP:TRIGer?
Query whether the OCP protection function has been triggered.
0/OFF: The channel OCP protection is not triggered.
1/ON: The channel OCP protection has been triggered.
:OUTPut2:OCP:TRIGer?
Return whether the OCP protection function of channel 2 has been triggered.
Command Function Description
:OUTPut[1|2]:OCP
Sets the OCP level.
Refer to the specification sheet on page 200 for value.
137
Example Note
GPP-3060/6030 User Manual
:OUTPut2:OCP 1.5 Sets the OCP voltage to 1.5A for CH2. The USB port, OCP value
can not be set.
Command Function Example
Note
:OUTPut[1|2|3]:OCP? Queries the OCP current level. :OUTPut2:OCP? Queries the OCP current level on CH2. The USB port , CH3 OCP query value is 3.10A.
138
REMOTE CONTROL
Source and Load Commands
Command Function Description Example
Note
:SOURce[1|2]:CURRent
Sets the current level.
0.0000-6.2000 (Refer to the specification sheet for MAX value).
:SOURce2:CURRent 1.0005
Sets the current level to 1.0005A for CH2.
About CH3, The current value can not be set.
Command Function Description
Example
Note
ISET
Command Description Example
:SOURce[1|2]:CURRent? Queries the current limit level. :SOURce2:CURRent? Queries the current limit level on CH2.
Command Function Description
ISET
139
Example
GPP-3060/6030 User Manual
ISET1? Returns the CH1 output current setting.
Command Function Return
Example
Note
:SOURce[1|2]:CURRent[:LIMit]:STATe? Queries the current limit state. 0: The current limit has not been reached. 1:The current limit has been reached. :SOURce2:CURRent:STATe? Return the current limit state of CH2. At output off or Load Mode,The return value of is 0.
Command Function Description Example
Note
:SOURce[1|2]:VOLTage < NRf >
Sets the output voltage amplitude.
0.000-MAX
:SOURce2:VOLTage 5.321
Sets the output voltage to 5.321V for CH2.
About CH3, If the settings are not 1.8V/ 2.5V/3.3V or 5V, the existing output will not be affected and errors message will occur, Please refer to “:SYSTem:ERRor?” .
Command Function Description
Example
VSET
Sets the Voltage level.
X 1= CH1, 2= CH2
140
REMOTE CONTROL
Command Function Example
:SOURce[1|2]:VOLTage? Queries the output voltage setting. :SOURce2:VOLTage? Queries the output voltage setting on CH2.
Command Function Description Example
VSET
Command Function Description Example
:SOURce[1|2]:RESistor < NRf >
Set the resistor value.
NRF
1-1000
:SOURce2:RESistor 1000
Set the resistor value as 1000 for CH2.
Command Function Example
:SOURce[1|2]:RESistor? Queries the setting resistor value.
:SOURce2:RESistor? Queries the setting resistor value and returns the readback
value for CH2.
Command Function
:SOURce:CURRent:ALL? Queries the setting current value in all channnels.
141
Example Note
GPP-3060/6030 User Manual
:SOURce:CURRent:ALL? Queries the setting current value and returns the
readback value for all channels. About CH3, current value will returns
5.0000A.
Command Function Example
:SOURce:VOLTage:ALL? Queries the setting voltage value in all channnels.
:SOURce:VOLTage:ALL? Queries the setting voltage t value and returns the
readback value for all channels.
Command Function Description
Example
:OUTPut:SERies {ON|OFF}[,FAST] Sets CH1/CH2 as tracking series mode.
[FAST]: In order to protect the function switching device” relay”, it is
necessary to wait until the voltage and current drop to zero under normal
conditions. When FAST is enabled, this factor will not be considered, but it
is easy to damage the “relay”, so it is recommended to use it with caution.
:OUTPut:SERies ON
Sets CH1/CH2 as Tracking series mode.
Command Function Description
:OUTPut:PARallel {ON|OFF}[,FAST] Sets CH1/CH2 as tracking parallel mode.
[FAST]: In order to protect the function switching device” relay”, it is
necessary to wait until the voltage and current drop to zero under normal
conditions. When FAST is enabled, this factor will not be considered, but it
is easy to damage the “relay”, so it is recommended to use it with caution.
142
Example
REMOTE CONTROL
:OUTPut:PARallel ON Sets CH1/CH2 as tracking parallel mode.
Command Function
Example
TRACK
Selects the operation mode: independent, tracking series, or tracking
parallel. Series-parallel mode is not supported under LOAD. NR1 0:
Independent, 1: Series, 2: Parallel
TRACK0 Selects the independent mode.
Command Function Description
Example
:LOAD[1|2]:CV {ON|OFF}[,FAST] Sets CH1/CH2 as Load CV mode. Automatically
switch to power mode after closing LOAD mode.
[FAST]: In order to protect the function switching device” relay”, it is
necessary to wait until the voltage and current drop to zero under normal
conditions. When FAST is enabled, this factor will not be considered, but it
is easy to damage the “relay”, so it is recommended to use it with caution.
:LOAD2:CV ON
Sets CH2 as Load CV mode.
Command Function
:LOAD[1|2]:CC {ON|OFF}[,FAST] Sets CH1/CH2 as Load CC mode.
143
GPP-3060/6030 User Manual
Description Example
[FAST]: In order to protect the function switching device” relay”, it is
necessary to wait until the voltage and current drop to zero under normal
conditions. When FAST is enabled, this factor will not be considered, but it
is easy to damage the “relay”, so it is recommended to use it with caution.
:LOAD2:CC ON
Sets CH2 as Load CC mode.
Command Function Example
:LOAD[1|2]:CR {ON|OFF} Sets CH1/CH2 as Load CR mode. :LOAD2:CR ON Sets CH2 as Load CR mode.
Command Function
Example
:MODE[1|2]? Queries CH1 or CH2 work mode. 6 modes below: SERies, PARallel, INDEpendent, CV Load, CC Load, CR Load. :MODE1? Queries CH1 work mode.
Command Function Description Example
:LOAD[1|2]: RESistor
Sets the Load CR level.
1-1000
:LOAD2:RESistor 100
Sets the Load CR level to 100 for CH2.
144
REMOTE CONTROL
Command Function Description Example
:LOAD[1|2]: RESistor?
Queries the Load CR level.
1-1000
:LOAD2:RESistor?
Return the Load CR level for CH2.
Command Function
Description Example
:LOAD:DISPlay {Low|Middle|High}
In load mode, set the minimum voltage value that can be displayed. The factory
default is high. Below this value, it will display “–.—-“. Low: 0.5VMiddle:
0.75VHigh:1V
:LOAD:DISPlay Low
In load mode, the minimum voltage value that can be displayed is 0.5V.
Command Function
Example
:LOAD:DISPlay?
Query the minimum voltage value that can be displayed in load mode.
:LOAD:DISPlay?
In load mode, query the minimum voltage value that can be displayed. The
return variables are low, 0.5V; middle, 0.75V; high, 1V.
Command Function Description
:DELAy[1|2]:CYCLEs {N|I}[,
145
Example
GPP-3060/6030 User Manual
:DELAy2:CYCLEs N,100 Sets the cycle number of Delay as 100 for CH2.
Command Function Example
:DELAy[1|2]:CYCLEs? Queries the cycle number of Delay.
:DELAy2:CYCLEs? Return to I or N,
Command Function Description
Example
:DELAy[1|2]:ENDState {ON|OFF|LAST} Sets the termination state of Delay. ON|OFF|LAST ON: output enabled. OFF: output disabled. LAST: stay at the last group of output state. :DELAy2:ENDState OFF Sets the termination state of Delay as output disabled for CH2.
Command Function Description
Example
:DELAy[1|2]:ENDState? Queries the termination state of Delay. ON|OFF|LAST ON: output enabled OFF: output disabled LAST: stay at the last group of output state. :DELAy2:ENDState? Return the termination state of Delay for CH2.
Command 146
:DELAy[1|2]:GROUPs
REMOTE CONTROL
Function Description Example
Sets the output number of Delay.
Command Function Example
:DELAy[1|2]:GROUPs? Queries the output number of Delay. :DELAy2:GROUPs? Return the output number of Delay for CH2.
Command Function Description
Example
:DELAy[1|2]:PARAmeter