EA antipollution check valve with shut-off valve
Installation and Operation Manual
EA anti-pollution check valve
The Basic CC is a EA type protection set assembly in accordance with standard
EN 1717. It is composed of a ball valve on the upstream side, a non-return
valve on the downstream side and four plugged bosses on which drain or/and
pressure gauge can be installed.
DN 15, 20 and 25 it is able to seal the valves in open or closed position
through a means located on the handle.
Technical features
Nominal pressure: PN10
Minimum operating temperature: 5°C
Continuous temperature: 65°C
Peak temperature: 85°C/1 hr a day
Connection: BSP
Drain cock included: G1/4”
Mounting: any position
Protection system: EA type
Fluid categories: 1 and 2
KIWA certificate no.: K41686/05
Approvals
ACS
KIWA-ATA (BRL 604-629), BELGAQUA.
Standards / Regulations
EN 1717, NF EN 13828, EN ISO228-1.
Materials
Body, fittings and plug : brass CW617N – 4MS
Spring: stainless steel
Seals : EPDM
Handlever : Steel and PVC
Check valve : POM
Installation / Commissioning instructions
Prior to commissioning, check that :
- the device is suitable for the installation category
- the conditions of operation are compatible with the fluid category
- the check valve is working properly, by testing it a couple of times
On a new installation or after maintenance, the circuit should be rinsed in
order to flush out any solid bodies which might damage the internal parts of
the valve.
The circuit should be gradually brought up to pressure to avoid damaging the
internal parts of the valve. Check that when the flow stops, the check valve
does indeed maintain the pressure. After a prolonged stoppage, a change in the
fluid state can cause damage when the installation is restarted
(solidification, etc.).
An opening/closing manipulation must be done every three months to avoid valve
scaling.
Part no.| Description – Fitting| Lenght (mm)| Width
(mm)| Height (mm)| Weight (g)
---|---|---|---|---|---
Compression fitting| | | |
228015242| TBE-EA / Basic CC – compression / 15 mm| 92| 44| 47| 321
228020242| TBE-EA / Basic CC – compression / 22 mm| 99| 48| 57| 442
228025242| TBE-EA / Basic CC – compression / 28 mm| 114| 55| 64| 619
Femelle x Femelle| | | |
228015243| TBE-EA / Basic CC – female / 1/2”| 81| 44| 47| 285
228020243| TBE-EA / Basic CC – female / 3/4”| 84| 48| 54| 350
228025243| TBE-EA / Basic CC – female / 1”| 97| 55| 62| 518
228032243| TBE-EA / Basic CC – female 1”1/4| 115| 61| 99| 840
228040243| TBE-EA / Basic CC – female / 1”1/2| 135| 71| 125| 1459
228050243| TBE-EA / Basic CC – female / 2”| 160| 80| 136| 2185
Male x Male| | | |
228015244| TBE-EA / Basic CC – male / 3/4”| 81| 44| 48| 290
228020244| TBE-EA / Basic CC – male / 1”| 84| 48| 55| 373
228025244| TBE-EA / Basic CC – male / 1”1/4| 97| 55| 62| 571
228032244| TBE-EA / Basic CC – male / 1”1/2| 111| 61| 99| 850
228040244| TBE-EA / Basic CC – male / 2”| 135| 71| 125| 1524
Swivel nut x Male| | | |
228015245| TBE-EA / Basic CC – swivel nut x male / 3/4”| 90| 40| 50| 298
228015253| TBE-EA / Basic CC – M 3/4» x swivel nut 3/4»| 92| 44| 52| 325
228020245| TBE-EA / Basic CC – swivel nut x male / 1”| 94| 48| 58| 417
Press fit connection| | | |
228015251| TBE-EA / Basic CC 3/4” -press fitting / Ø15| 129| 44| 52| 445
228015252| TBE-EA / Basic CC 3/4” -press fitting / Ø22| 166| 44| 52| 517
228025251| TBE-EA / Basic CC 1”1/4 -press fitting / Ø28| 164| 55| 67| 974
WATTS INDUSTRIES France
1590 avenue d’Orange • CS 10101 Sorgues 84275 VEDENE CEDEX • France
Tél. +33 (0)4 90 33 28 28 • Fax +33 (0)4 90 33 28 39
contact@wattswater.com •
www.wattswater.fr
© 2021 Watts
BASIC_CC-IM-FR-S-ML-12-20-Rev.1
W949000734
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>