Schneider Electric MTN6003-0012 KNX Flush Mounted Blind Switch Actuator 2g With 3 Binary Inputs User Manual

June 10, 2024
Schneider Electric

Schneider Electric MTN6003-0012 KNX Flush Mounted
logo

Schneider Electric MTN6003-0012 KNX Flush Mounted Blind Switch Actuator

2g With 3 Binary Inputs

Product Information

The Space Logic KNX Flush Mounted Blind/Switch Actuator 2g with 3 binary inputs (MTN6003-0012) is an electrical device that can be used to control blinds and switches. Detailed product information is available on the internet, which can be accessed by scanning the QR code provided.
It is important to note that safe electrical installation must be carried out only by skilled professionals who have profound knowledge in the areas of connecting to installation networks, connecting several electrical devices, laying electric cables, connecting and establishing KNX networks, and safety standards, local wiring rules, and regulations. Failure to follow these instructions will result in death or serious injury.

Product Usage Instructions

  1. Ensure that the device is installed by a skilled professional who has a thorough knowledge of electrical installations and safety standards.
  2. Do not connect the bus/extensions and mains voltage wires in a shared appliance box. Use an appliance box with a fixed partition wall or separate appliance boxes to avoid endangering the safety of the entire KNX installation.
  3. Follow all safety instructions provided to avoid the risk of electric shock, explosion, or arc flash.
  4. Refer to the detailed product information available on the internet for specific usage instructions and troubleshooting information.

About this document

You can find all the information required for safe installation in this document.
For your safety
DANGER!
HAZARD OF ELECTRIC SHOCK, EXPLO-SION, OR ARC FLASH
Safe electrical installation must be carried out only by skilled professionals. Skilled professionals must prove profound know-ledge in the following areas:

  • Connecting to installation networks
  • Connecting several electrical devices
  • Laying electric cables
  • Connecting and establishing KNX networks
  • Safety standards, local wiring rules and regulations
    Failure to follow these instructions will result in death or serious injury.

Safety instructions
Electrical devices may only be mounted and connected by electrically skilled persons.
The device may not be opened or operated outside the technical specifications.
Danger of electric shock. Device is not suitable for disconnection from supply voltage. The load is not electrically isolated from the mains even when the output is switched off.
Danger of electric shock. Make sure during the installation that there is always sufficient insulation between the mains voltage and the bus. A minimum distance of at least 4 mm must be maintained bet-ween bus conductors and mains voltage cores.
Danger of electric shock on the KNX installation. Do not connect any external voltage to the inputs. The device might be damaged, and the SELV potential on the KNX bus line will no longer be available.
Fire hazard. For operation with inductive transformers, each transformer must be fused on the primary side in accordance with the manufacturer’s instructions. Only safety transformers according to EN 61558-2-6 may be used.
Risk of destruction of the dimmer and load if the set operating mode and load type do not match. Set the correct dimming principle before connecting or ex- changing the load.
These instructions are an integral part of the pro-duct, and must remain with the end customer.

Function

Intended use

  • Operating in KNX systems
  • Switching and dimming of lighting
  • Reading in switching states of installation switches or push-buttons and other potential-free contacts at inputs 1…3
  • Acquisition of temperature values via NTC temperature sensor at input 3 (see accessories)
  • Mounting in appliance boxes according to DIN 49073

Information for electrically skilled persons

DANGER!
Mortal danger of electric shock.
Disconnect the device. Cover up live parts.
DANGER!
When connecting the bus/extensions and mains voltage wires in a shared appliance box, the KNX bus line may come into con-tact with the mains voltage.
This endangers the safety of the entire KNX installation. People at remote devices may also receive an electric shock.

  • Do not place bus/extensions and mains voltage terminals in a shared connection compartment. Use an appliance box with a fixed partition wall or separate applian-ce boxes.

Connecting and fitting the device
In secure operation (preconditions):

  • Secure commissioning is activated in the ETS.
  • Device certificate entered/scanned or added to the ETS project. A high resolution camera should be used to scan the QR code.
  • Document all passwords and keep them safe.

Mounting in suitable appliance box (recommendation: electronic device box with partition). Observe cable routing and spacing

  • (5) Appliance box
  • (6) Partition
  • (7) potential-free contacts (e.g. series push-but- ton)
  • (8) NTC temperature sensor (optional)Schneider Electric MTN6003-0013 KNX Flush Mounted 1

Minimum spacing between the mains voltage and bus/extension wires: 4 mmSchneider Electric MTN6003-0013 KNX Flush Mounted 2Observe ambient temperature. Ensure adequate cooling.

  • Connect the device to KNX with the correct polarity.
  • Connect load as shown in the connection example.Schneider Electric MTN6003-0012 KNX Flush Mounted 1
  • If required, connect potential-free contacts to inputs 1…3, or NTC temperature sensors to in-put 3 .Schneider Electric MTN6003-0013 KNX Flush Mounted 4
  • Install the device in the appliance box.
  • In secure operation: The device certificate must be removed from the device and stored securely.
    The COM reference potential must not be connected together with COM connections of other devices!

Technical data

Ambient conditions

  • Ambient temperature                         -5 … +45 °C
  • Storage/transport temperature          -25 … +70 °C
  • Dimensions (W × H × D)                48 x 50 x 28 mm

KNX

  • KNX medium                                TP256
  • Commissioning mode                    S-mode
  • Rated voltage KNX                       DC 21 … 32 V SELV
  • Current consumption KNX          5 … 18 mA
  • Connection mode KNX                Connection terminal on control cable

Output

  • Connection mode                         Screw terminals
  • Switching voltage                          AC 250 V ~
  • Switching current                          16 AX, IEC 60669-1 §19.2
  • Switch-on current 200 μs              10 A, IEC 60669-2-5 max. 800 A
  • Switch-on current 20 ms               max. 165 A

Power consumption per output
Schneider Electric MTN6003-0012 KNX Flush Mounted
2Reduction of connected load

  • per 5 °C in excess of 35 °C                                                   -10%
  • when installed in wooden or dry construction walls              -15%
  • when installed in multiple combinations                                -20%

Clampable conductor cross-section

  • Connection torque screw terminals                          Max. 0.8 Nm

Inputs

  • Control cable (pregerminated)                                   YY6x0.6
  • Input type                                                                  Potential-free
  • Number                                                                     3
  • Total length of extension device cable                      max. 10 m
  • Cable type (preferably)                                              J-Y(St)Y
  • Poll voltage, extension inputs                                    approx. 5 V

Accessories

Remote sensor for room temperature measurement            MTN616790
Schneider Electric Industries SAS
If you have technical questions, please contact the Customer Care Centre in your country.
se.com/contact

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals