Polaris ISPBO Multi-Tap Cable Connectors Instruction Manual
- June 4, 2024
- Polaris
Table of Contents
Polaris ISPBO Multi-Tap Cable Connectors
Installation Instructions
- The conductor must have insulation acceptable for wet or damp locations
- Wipe off any foreign material (dirt, water, oil, etc.) on the insulation of the conductor to be spliced
- Mark the conductor insulation 3/4” and 2-1/4” from the end. Insulation strip length imprinted on the connector
- Remove the conductor insulation up to the 3/4” strip length, be sure not to “score” or “nick” the conductor (bare wire). TIP – For wire sizes #1 and larger bevel edge of insulation
- Brush all conductors before inserting them into the connector.
- Remove the conductor sleeve from the connector. Discard sleeve for 1/0 – 2/0 AWG (if discarded go to step 9)
- Select and cut off the step appropriate for the size indicated on the sleeve. Make sure to cut the sleeve straight across the end of the appropriate size step
- Reinsert the conductor sleeve into the wiring
- Remove set-screw access plug and loosen set-screw to allow conductor insertion
- For easier assembly lubricate the exterior of conductor insulation with the included dielectric silicone grease
- Insert the conductor into the cable outlet or conductor sleeve until the cable outlet or conductor sleeve until the 2-1/4” reference mark is even with the end of the cable outlet. The end of the conductor should hit the back of the connector
- Tighten the pressure screws to the recommended torque per the Chart below
- Replace set-screw access plug
ISPBO
ISPB
ISPBS
- 2019 NSI Industries, LLC
- NSA Industries
- 800.321.5847
- www.nsiindustries.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>