Polaris ISPBO Multi-Tap Cable Connectors Instruction Manual

June 4, 2024
Polaris

Polaris ISPBO Multi-Tap Cable Connectors

Installation Instructions

  • The conductor must have insulation acceptable for wet or damp locations
  • Wipe off any foreign material (dirt, water, oil, etc.) on the insulation of the conductor to be spliced
  • Mark the conductor insulation 3/4” and 2-1/4” from the end. Insulation strip length imprinted on the connector
  • Remove the conductor insulation up to the 3/4” strip length, be sure not to “score” or “nick” the conductor (bare wire). TIP – For wire sizes #1 and larger bevel edge of insulation
  • Brush all conductors before inserting them into the connector.
  • Remove the conductor sleeve from the connector. Discard sleeve for 1/0 – 2/0 AWG (if discarded go to step 9)
  • Select and cut off the step appropriate for the size indicated on the sleeve. Make sure to cut the sleeve straight across the end of the appropriate size step
  • Reinsert the conductor sleeve into the wiring
  • Remove set-screw access plug and loosen set-screw to allow conductor insertion
  • For easier assembly lubricate the exterior of conductor insulation with the included dielectric silicone grease
  • Insert the conductor into the cable outlet or conductor sleeve until the cable outlet or conductor sleeve until the 2-1/4” reference mark is even with the end of the cable outlet. The end of the conductor should hit the back of the connector
  • Tighten the pressure screws to the recommended torque per the Chart below
  • Replace set-screw access plugPolaris-ISPBO-Multi-Tap-Cable-Connectors-FIG-3

ISPBO