Product Information
The LED Tube T5 AC Mains is a replacement for T5 fluorescent lamps with G5 bi- pin bases. It is suitable for use with AC mains 220-240V (without ballast) and has a restricted operating temperature range. The lamp is available in different wattage options and suitable for dry conditions or luminaire that provides protection.
Specifications
- Available Wattage Options: 36W, 26W, 16W, 10W, 18W, 7W
- Length Options: 1449mm, 1149mm, 849mm, 549mm
- Operating Voltage: AC 220-240V
- Suitable for dry conditions or luminaire that provides protection
- Suitable for 50 Hz or 60 Hz operation
- Not suitable for emergency operation
- Dimming not allowed
- Not suitable for high frequency operation (ECG)
Product Usage Instructions
- Remove ballast from the fixture electrical circuit/wiring. Note that the fixture has been modified and can no longer operate originally specified T5 Fluorescent lamp. Use only approved LEDVANCE LED TUBE T5 AC Mains.
- Connect the LED Tube T5 AC Mains directly to AC mains.
- Ensure that the lamp is suitable for the length of the fixture.
- Ensure that the operating voltage of the fixture matches the LED Tube T5 AC Mains.
- If using multiple lamps, ensure that they are connected properly and in parallel.
- Install the lamp in dry conditions or in a luminaire that provides protection.
- The lamp is suitable for 50 Hz or 60 Hz operation.
- The lamp is not suitable for emergency operation.
- Dimming is not allowed.
- The lamp is not suitable for high frequency operation (ECG).
Note: The operating temperature range of the LED Tube T5 AC Mains is restricted. Do not use the lamp if the temperature exceeds the specified range. If you have any doubts about the suitability of the product, please contact the manufacturer or a qualified electrician.
- LED TUBE T5 AC Mains is suitable as replacement for T5 fluorescent lamps with G5 bi-pin bases.
- The operating temperature range of LED TUBE T5 AC Mains is restricted. In case of doubt regarding suitability of the application please measure Tc max temperature on the product. In case of multi lamp luminaire application measure Tc max temperature of all installed lamps. Please use a flexible thermo sensor (e.g. “Type K”)
- LED TUBE T5 AC Mains operated above Tc max can lead to premature aging and failure of devices.
- LED TUBE T5 AC Mains emits light only with a limited beam angle not like a fluorescent tube with 360° output.
- The LED TUBE T5 AC Mains is designed for general lighting application (excluding for example explosive atmosphere).
Instructions on AC mains 220-240 V (without ballast):1)
Warning : The fixture electrical circuit/wiring has been modified and can no longer operate originally specified T5 Fluorescent lamp. Use only approved LEDVANCE LED TUBE T5 AC Mains.2)
LED TUBE T5 AC MAINS
| Replacement of T5 FL 3)| Storage temperature 4) (Ts)|
Ambient temperature of lamp 5) (Ta )
---|---|---|---
LED TUBE T5 AC HO80 P 1449 36 W 8XX| 80 W: 1449 mm| -20°C … 80°C| -20°C … 45°C
LED TUBE T5 AC HO54 P 1149 26 W 8XX| 54 W: 1149 mm| -20°C … 80°C| -20°C … 45°C
LED TUBE T5 AC HO49 P 1449 26 W 8XX| 49 W: 1449 mm| -20°C … 80°C| -20°C … 45°C
LED TUBE T5 AC HO39 P 849 16 W 8XX| 39 W: 849 mm| -20°C … 80°C| -20°C … 45°C
LED TUBE T5 AC HO24 P 549 10 W 8XX| 24 W: 549 mm| -20°C … 80°C| -20°C … 45°C
LED TUBE T5 AC HE35 P 1449 18 W 8XX| 35 W: 1449 mm| -20°C … 80°C| -20°C … 45°C
LED TUBE T5 AC HE28 P 1149 16 W 8XX| 28 W: 1149 mm| -20°C … 80°C| -20°C … 45°C
LED TUBE T5 AC HE21 P 849 10 W 8XX| 21 W: 849 mm| -20°C … 80°C| -20°C … 45°C
LED TUBE T5 AC HE14 P 549 7 W 8XX| 14 W: 549 mm| -20°C … 80°C| -20°C … 45°C
(8XX = 830, 840, 865)
-
Remove ballast, connect directly on AC mains 6)
-
Lamp not suitable for emergency operation 9)
-
Lamp to be used in dry conditions or in a luminaire that provides protection 7)
-
Dimming not allowed 10)
-
Lamp suitable for 50 Hz or 60 Hz operation 8)
-
Lamp not suitable for high frequency operation (ECG) 11)
- LED TUBE T5 AC Mains is suitable as replacement for T5 fluorescent lamps with G5 bi-pin bases.
- The operating temperature range of LED TUBE T5 AC Mains is restricted. In case of doubt regarding suit-ability of the application please measure Tc max temperature on the product. In case of multi lamp luminaire application measure Tc max temperature of all installed lamps. Please use a flexible thermo sensor (e.g. “Type K”).
- LED TUBE T5 AC Mains operated above Tc max can lead to premature aging and failure of devices.
- LED TUBE T5 AC Mains emits light only with a limited beam angle not like a fluorescent tube with 360° output.
- The LED TUBE T5 AC Mains is designed for general lighting application (excluding for example explosive atmosphere).
- Instructions on AC mains 220-240V (without ballast).
- Warning! The fixture electrical circuit/wiring has been modified and can no longer operate originally specified T5 Fluorescent lamp. Use only approved LEDVANCE LED TUBE T5 AC Mains.
- Replacement of T5 FL.
- Storage temperature.
- Ambient temperature of lamp.
- Remove ballast, connect directly on AC mains.
- Lamp to be used in dry conditions or in a luminaire that provides protection.
- Lamp suitable for 50 Hz or 60 Hz operation.
- Lamp not suitable for emergency operation.
- Dimming not allowed. 11) Lamp not suitable for high frequency operation.
LEDVANCE GmbH
Steinerne Furt 62
86167 Augsburg, Germany
www.ledvance.com
LEDVANCE Ltd, Aquila House Delta Crescent, Westbrook, Warrington WA5 7NR,
United Kingdom
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>