nVent RAYCHEM VIA-DU-20 Electronic Control Unit Instruction Manual
- June 10, 2024
- nVent RAYCHEM
Table of Contents
nVent RAYCHEM VIA-DU-20 Electronic Control Unit Instruction Manual
1. APPLICATION
The VIA-DU-20 is an electronic control device designed to regulate nVent RAYCHEM ramp heating systems in garage driveways, staircases, inclines etc. The buried heating cable is controlled by sensing both ground temperature and moisture. The heater operates only when the temperature falls below the set value and there is moisture. Use of this controller results in significant energy savings if compared to other devices that regulate according to temperature only.
2. FUNCTION
The ground temperature and moisture are measured with the help of one sensor.
The sensor is heated so that it can also measure dry snow.
The control device evaluates the data from the sensor and switches the heating
on, if the ground temperature falls below a value set by menu and the ground
moisture exceeds a value set by menu.
In addition the device is capable of identifying a risk of freezing rain. This
function serves to switch the heating on when freezing rain is predicted.
The controller also has what is called an overruling entry. This can be
configured using the menu and serves to prevent over-loading or to allow the
device to be controlled remotely via the BMS.
3. DISPLAY AND CONTROLS
The device has a display which is lit when the device is being operated (see A). Under normal operating conditions the device alternately shows the moisture, the ground and air temperature and the status of the heating output (on/off). Only the values, which are relevant for controlling, are shown. Air temperature e.g. is only shown, if “sleet precaution” is set to “local detection”.
4. OPERATION
4.1 Selecting a language
You can select a language by pressing the button once or more. The languages available are German, English, French, Italian, Polish, Finnish, Hungarian. The language can be changed regardless of the operating status.
After 2 seconds the device automatically returns to where it was when the language selection procedure was called up (Normal display, test or parameter menu). Example of display when selecting a language:
4.2 Testing mode
Pressing the once switches the heating timer on for 30 min. The display indicates the time remaining, the software version number and the status of the heating output. The test mode can be selected at any stage. It should however be remembered that any heating periods underway will be interrupted. So for example, selecting the test mode will interrupt the post-heating period. The test finishes once the test time has elapsed, but can also be terminated by pressing the button while the test is still underway. When the test mode has been terminated the device will return to the standard display. Display in test mode (example):
4.3 Operation of the parameter menu
The parameter menu can be called up by pressing the the and buttons. button. The parameter displayed may be modified using
If the buttons are pressed down for an extended period the value changes automatically (autorepeat function). Pressing and down at the same time will reset the parameter to the default setting.
Now you can switch to the next parameter with the button button. or you can leave the parameter menu by pressing the If you have changed a parameter and want to switch to the next or leave the menu, there appears “SAVE CHANGES” in the display. You can select “YES” or “NO” using the and buttons. Having confirmed this with the button, device switches to the next parameter or leaves the parameter menu with or without saving changes. Confirming the final parameter, the device goes back to the standard display
The temperature threshold is used to set the value below which the ground
temperature must fall for the heating to come on, providing there is
sufficient moisture. The temperature threshold also is the set point for the
sensor heating, i.e. there is the possibility to control the sensor heating by
this value.
Attention: If the temperature threshold is set to 1.0°C or 2.0°C, the sensor
may freeze in. In this case reliable detection of moisture can not be
guaranteed.
The value of moisture is no longer indicated in the display.
The moisture threshold determines the level of moisture which must be exceeded for the heating to come on, providing the temperature is low enough. 1 is the most sensitive setting, i.e. very little moisture is enough to reach EN this value.
If the moisture threshold is set to `OFF’, the control device will always switch the heating on, as long as the temperature falls below the threshold value. No moisture is required. The value of moisture is no longer indicated in the display.
- For the purpose of the use of VIA-DU-20 in the UK, `sleet’ is used to describe the condition and effect of freezing rain.
This can be done in two different ways:
1. Local detection freezing rain warning
If the device is set to LOCAL DETECTION, i.e. local detection of risk of
freezing rain, the device will heat the surface as soon as it notices a sharp
rise in temperature after a lengthy period of cold weather.
The rise in air temperature is performed by an air temperature sensor which is
delivered together with the device.
The device can recognise a lengthy period of cold weather by means of a ground
temperature sensor, if the ground temperature has been below a set value for
18 hours. See also the sections on the rise in temperature and the low ground
temperature for an 18 hour period in the paragraphs relating to the following
parameters.
2. Freezing rain warning via the weather service With this function, the
device waits for a logic signal sent from an additional device to the
terminals of the air temperature sensor. The additional device, which is not
part of the standard package, evaluates information from the weather service
and converts these into the relevant logic status.
The control device expects the following logic status:
Logic status 0 1
Input in control device open short circuit
Reaction of the control device Heating OFF (no risk of freezing rain) Heating
ON (risk of freezing rain)
Instructions for early recognition of freezing rain
- If it has recognised the possibility of a fall of freezing rain, the device switches on for 5 hours. If the warning has come via the weather service, the five-hour period begins from the moment the logic status signal changed from 0 to 1. The heating is switched off as soon as the ground temperature reaches the threshold value or the five hours have elapsed. If however, after five hours, the ground temperature and moist conditions are present for heating to continue, the heating is not turned off, i.e. following the five-hour period the device continues to operate under normal operating conditions.
- If the device is set for the local detection freezing rain warning, you should ensure that the base temperature is lower than the 18-hour ground temperature value, since otherwise the temperature will never fall below the 18-hour value and the freezing rain warning will not function.
- The reliability of the early recognition function heavily depends on the correct setting of the parameters. It is possible that ice may build up on the surface or the device may come on unnecessarily.
The OVERRULING parameter is used to configure the relevant logic input. If the
parameter is set to OFF’ the input is not evaluated by the control device. The control device is not affected. In the
ON’ setting the control device cannot switch the heating on for 10
min. if the input is or was short-circuited. This prevents peakloads in
buildings. If the input is still short-circuited or has short-circuited again
after 10 minutes have elapsed, the device cannot turn on the heating for
another 10 minutes.
If the device is set to `BMS’ the heating output is remote controlled. If the
input is short-circuited, the control device switches the heating off. If the
input is open, the device will switch on the heating in any event.
The sensor values of the ice indicator are not displayed and not evaluated.
5. ADVICE, FAULT MESSAGES AND SERVICING
5.1 What to do during set up
When the device is first put into operation it carries out an auto-test.
During this test the display indicates, “POWER-UP TESTS”. If the device finds
a fault during this test, it displays a number on the second line of the
display. FR Otherwise the device goes into the standard operating mode.
IT * This parameter is indicated only when “local detection” is selected.
If a fault is identified, you should carry out another test by switching the
device off and on again. If the fault message is displayed again, the device
is faulty and must be replaced. If the fault message is displayed indicating
the number `6′, perhaps one of the buttons is stuck. In this case, the
keyboard must be checked. Then switch the device off and on again for another
test.
5.2 What to do in the event of a loss of power
If there is a loss of power, all parameters will remain saved in the memory. Both relays (heating and alarm) will stop working. After the power failure, the device will continue to operate in its state when the power loss occurred. The timers will remain constant during power loss (no reserve power supply).
5.3 Sensor monitoring
The ground temperature and moisture sensor and the air temperature sensor are monitored for faults (breakage and short circuits) by the control device. If a fault occurs, the alarm relay switches and the display indicates, “SENSOR FAULT” and a corresponding fault message is emitted. The following fault messages are used:
A failure will interrupt heating times, such as the post-heating period. The heating output will be turned on or off as set under the parameter “IN THE CASE OF FAILURE HEATING…”
- The monitoring of air temperature is only active when “local detection” is selected.
5.4 Trouble shooting
Attention: Please change settings step by step to ensure reliable function. Also with careful settings it can’t be guaranteed, that the heated area is always free of snow and ice.
5.5 Servicing
Neither control device nor any of the sensors require any servicing. The surface of the ground sensor needs to be cleaned regularly, to ensure that it gives correct moisture measurements. A flannel and tap water may be used. The surface of the sensor must not be scratched with sharp objects. It is recommended that you check that the device is working before the onset of winter.
6. SAFETY INSTRUCTIONS
Only for electricians! Attention: mistakes made when connecting up the device
can cause damage to the control unit. nVent is not liable for any damage
caused by faulty connections and/or incorrect handling.
– Before working on the device, switch off the power supply.
– The device may only be connected up and serviced by authorised, trained
personnel.
– The device is only designed to be connected to fixed cables.
– When installing the device, make sure that high-voltage cables, such as the
mains supply and extensions do not come into contact with low-voltage cables
such as sensor cables.
– Moreover, you must ensure adequate protection against all the extension
leads disconnecting in compliance with the requirements of EN 60730, part I.
This can be achieved for example by fixing the cables with cable clips.
– Local standards for electrical connection must be observed.
– If the device does not work, please first check all connections and the
mains power supply
7. INSTALLATION
7.1 Installation of the control device
This device is installed in a housing to be snapped onto DIN rails (DIN EN
50022-35). It is designed to be mounted in switchboxes and distribution
panels.
The housing has the following dimensions: see B
7.2 Installation of the ground temperature and moisture sensor VIA-
DU-S20
RU The sensor is yellow and can be recognised by its 5-core connection lead.
It has the following dimensions: see C
The ground temperature and moisture sensor is to be installed within the heated area at least 2.5 cm and maximum 15 cm away from the heating cables (see diagram). The sensor must be able to directly detect weather conditions (rain, snow, melted snow and ice). The sensor may not be covered up (e.g. when clearing snow). Take care that VIA-DU-S20 is not installed in an area which is continuously flooded with water (e.g. drain line), neither in an area which is continuously under ice due to external parameters (e.g. freezing of condensation water in cooling rooms). The piece of wood is placed into the ground surface as a dummy for the sensor. A metal protective pipe is to be installed up to the wooden piece.
The pipe is to be secured on the wooden piece to prevent concrete, asphalt, etc. from getting in. Once the material has been put on and if necessary cooled, the piece of wood is removed and the sensor fitted into the hole. The sensor must be mounted absolutely horizontal. The remaining space around the sensor is to be filled with, for example, silicon, mortar or asphalt. The temperature of the filling material must not exceed 80°C. Furthermore, it has to be ensured that there is a good connection without hollow space between the sensor and the filling material. The sensor connection lead may be extended from 15 m (standard length) to a maximum of 50 m with a diameter of 1.5 mm² .
7.3 Installation of air temperature sensor VIA-DU-A10
The sensor has the following dimensions: see D
The air temperature sensor should be installed approx. 2-3 m above the ground
in a protected place (with a shelter). It must not be exposed to direct
sunlight. It must also be protected from external influences, i.e. it must not
be installed above doors or windows or near lamps or headlights. The sensor
connection lead may be up to 100 m long, given a diameter of 1.5 mm².
8. TECHNICAL DATA
Ground temperature and moisture sensor VIA-DU-S20
*Air temperature sensor VIA-DU-A10**
VIA-DU-A10 and VIA-DU-S20 (yellow- brown wire)
9. WIRING DIAGRAM
9.1 VIA-DU-20 with contactor DE L1 FR L2
When using MI heating cables a 300 mA RCD should be used.
- Local values, standards and rules require two- or four-pole switching using a electrical protection
** Depending on the application, both one- and three pole circuit breakers of contactors are possible.
* Optional and can be activated in a BMS.
** Air temperature sensor will be needed only if in menu freezing rain
precaution the parameter “local detection” has been selected. When weather
forecast has been selected you have to connect the vulture contacts of
additional device to these terminals.
9.2 Alarm output
België/Belgique
Tel +32 16 21 35 02
Fax +32 16 21 36 04
salesbelux@nVent.com
Bulgaria
Tel +359 5686 6886
Fax +359 5686 6886
salesee@nVent.com
Česká Republika
Tel +420 602 232 969
czechinfo@nVent.com
Danmark
Tel +45 70 11 04 00
salesdk@nVent.com
Deutschland
Tel 0800 1818205
salesde@nVent.com
España
Tel +34 911 59 30 60
Fax +34 900 98 32 64
ntm-sales-es@nVent.com
France
Tél 0800 906045
salesfr@nVent.com
Hrvatska
Tel +385 1 605 01 88
Fax +385 1 605 01 88
salesee@nVent.com
Italia
Tel +39 02 577 61 51
Fax +39 02 577 61 55 28
salesit@nVent.com
Lietuva/Latvija/Eesti
Tel +370 5 2136633
Fax +370 5 2330084
info.baltic@nVent.com
Magyarország
Tel +36 1 253 7617
Fax +36 1 253 7618
saleshu@nVent.com
Nederland
Tel 0800 0224978
salesnl@nVent.com
Norge
Tel +47 66 81 79 90
salesno@nVent.com
Österreich
Tel 0800 29 74 10
salesat@nVent.com
Polska
Tel +48 22 331 29 50
Fax +48 22 331 29 51
salespl@nVent.com
Republic of Kazakhstan
Tel +7 7122 32 09 68
Fax +7 7122 32 55 54
saleskz@nVent.com
Pоссия
Тел. +7 495 926 18 86
Факс +7 (495) 926 18 86
salesru@nVent.com
Serbia and Montenegro
Tel +381 230 401 770
Fax +381 230 401 770
salesee@nVent.com
Schweiz/Suisse
Tel +41 (41) 766 30 80
Fax +41 (41) 766 30 81
infoBaar@nVent.com
Suomi
Puh 0800 11 67 99
salesfi@nVent.com
Sverige
Tel +46 31 335 58 00
salesse@nVent.com
Türkiye
Tel +90 560 977 6467
Fax +32 16 21 36 04
salesee@nVent.com
United Kingdom
Tel 0800 969 013
salesthermalUK@nVent.com
©2023 nVent. All nVent marks and logos are owned or licensed by nVent Services
GmbH or its affiliates. All other trademarks are the property of their
respective owners. nVent reserves the right to change specifications without
notice.
RAYCHEM-IM-INST197-VIADU20-ML-2301