HAYWARD HCSC60 Saline C 6.0 Commercial Salt Chlorine Generator Owner’s Manual

June 10, 2024
Hayward

HAYWARD HCSC60 Saline C 6.0 Commercial Salt Chlorine Generator

Description

The Saline CTM 6.0 is a commercial salt chlorine generator designed to produce sodium hypochlorite from salt and water. The system includes an electrolytic cell assembly and a power supply/control box.

Installation

  1. Choose a suitable location for the Saline CTM 6.0 that provides easy access for maintenance and service.
  2. Mount the power supply/control box to a sturdy surface using the provided mounting brackets.
  3. Install the electrolytic cell assembly in the pool plumbing system according to the manufacturer’s instructions.
  4. Connect the power supply/control box to a circuit protected by a ground-fault circuit-interrupter.
  5. Connect the electrolytic cell assembly to the power supply/control box using the provided cable.

Operation

  1. Add salt to the pool water according to the manufacturer’s instructions.
  2. Set the chlorine output level on the power supply/control box to the desired level.
  3. The Saline CTM 6.0 will automatically produce sodium hypochlorite as needed to maintain the desired chlorine level in the pool water.
  4. Monitor the pool water chemistry regularly and adjust the chlorine output level as needed.

Maintenance

  1. Check the salt level in the pool water regularly and add salt as needed.
  2. Inspect the electrolytic cell assembly regularly for signs of damage or deterioration and replace if necessary.
  3. Clean the electrolytic cell assembly regularly according to the manufacturer’s instructions.
  4. Check the chlorine output level regularly and adjust as needed.
  5. Follow all other maintenance procedures outlined in the manufacturer’s instructions.

Parts Guide

The parts guide provides a list of all components included with the Saline CTM 6.0, along with their designated part numbers.

Warranty

The Saline CTM 6.0 is covered by a manufacturer’s warranty. Contact the manufacturer for details.

Important Safety Instructions

  • Read and follow all safety and operation instructions before using the Saline CTM 6.0.
  • To reduce the risk of electrical shock, connect the equipment assembly to a circuit protected by a ground-fault circuit-interrupter.
  • Wear eye and skin protection while maintaining or servicing this unit.
  • Do not permit children to use or climb on this product. Closely supervise children at all times.

IMPORTANT SAFETY INSTRUCTIONS

  • Basic safety precautions should always be followed, including the following: Failure to follow instructions can cause severe injury and/or death.
  • This is the safety-alert symbol. When you see this symbol on your equipment or in this manual, look for one of the following signal words and be alert to the potential for personal injury.
    • WARNING warns about hazards that could cause serious personal injury, death or major property dam- age and if ignored presents a potential hazard.
    • CAUTION warns about hazards that will or can cause minor or moderate personal injury and/or property damage and if ignored presents a potential hazard. It can also make consumers aware of actions that are unpredictable and unsafe.
  • The NOTICE label indicates special instructions that are important but not related to hazards.
  • WARNING Read, understand, and follow all safety and operation instructions. Failure to follow safety and operation instructions can result in severe personal injury or death.
  • WARNING -Risk of Electric Shock. Hazardous voltage can, shock, burn and cause death or serious property damage. To reduce the risk of electrical shock, connect the equipment assembly to a circuit protected by a ground-fault circuit-interrupter. Do not bury cord. If cord is damaged, replace immediately.
  • WARNING – When installing the system, ensure that power is interlocked with the main recirculation pump power source for the pool/spa to ensure that the Saline C 6.0 system cannot operate when the pumps are off.
  • WARNING Chemical Hazard. Chemicals can cause burns both internally and externally. To avoid death, serious injury or property damage: Wear eye and skin protection while maintaining or servicing this unit. Do not inhale fumes from the unit.
  • CAUTION To reduce risk of injury, do not permit children to use or climb on this product. Closely supervise children at all times. The ANSI/NSPI-4 Standard (above-ground and on-ground pools) advises that components such as the this system, filtration system, pumps, and heaters be positioned to prevent their being used as a means of access to the pool by young children.
  • WARNING – Hazardous Pressure. Pool and spa water circulation systems operate under hazardous pressure during start up, normal operation, and after pump shut off. Stand clear of circulation system equipment during pump start up. Failure to follow safety and operation instructions could result in violent separation of the pump housing and cover, and/or filter housing and clamp due to pressure in the system, which could cause property damage, severe personal injury, or death. Before servicing pool and spa water circulation system, all system and pump controls must be in off position and filter manual air relief valve must be in open position. Before starting system pump, all system valves must be set in a position to allow system water to return back to the pool. Do not change filter control valve position while system pump is running. Before starting system pump, fully open filter manual air relief valve. Do not close filter manual air relief valve until a steady stream of water (not air or air and water) is discharged.
  • Notice: This product should be installed and serviced only by a qualified pool professional.
    SAVE THESE INSTRUCTIONS

DESCRIPTION

General Information
The Saline C 6.0 is a saline chlorination system designed for commercial swimming pool applications. The Saline C 6.0 is certified to produce 5 pounds of equivalent chlorine per day (based on 3500 ppm of salt). The system produces chlorine continuously from a salt concentration of 3500 ppm to 5000 ppm added to the pool. The Saline C 6.0 is designed for commercial service and can be operated 24 hours a day and/or controlled by any pool controller. All models are reverse polarity for self cleaning and reduced cell maintenance.

Electrolytic Cell Assembly
The electrolytic cell assembly consists of a clear cell vessel containing an electrolytic cell made from precious metal coated cell plates. Pool water from the pool circulation system is directed through the cell. The pool water, maintained between 3500 and 5000 ppm salt concentration is converted in the electrolytic cell to free chlorine. The free chlorine is then circulated to the pool and combines with organics and further combines to form salt to be used again by the electrolytic cell. This is called a closed loop system because the salt is used repeatedly and is only lost through splash-out, backwashing, leaks and rainfall.

Power Supply and Control Box
The power supply provides the current to the electrolytic cells to produce the rated amount of sodium hypochlorite. The power supply houses all the safety features to prevent system operation in the event of a malfunction.

General Specifications

Model Designation| Part Number| Sodium Hypochlorite Production (lbs/day)| Rated Power in DC Amps| Rated Pressure| Minimum Water Flow Rate (gpm)| Maximum Water Flow Rate (gpm)| Inlet Diameter (Inches)| Outlet Diameter (Inches)
---|---|---|---|---|---|---|---|---
Saline C 6.0| HCSC60| 5.0lbs/day@ 3500 ppm| 36| 50 psi| 40 gpm| 100 gpm| 2 inch| 2 inch

Electrical Requirements

Model Designation| Part Number| Voltage (supply AC)| Phases| Frequency| Amps| GFCI

Breaker

---|---|---|---|---|---|---
Saline C 6.0| HCSC60| 120| 1| 60Hz| 6.5| 15

Sizing Guidelines
Chlorinator sizing must comply with local codes. Please contact your local health department for specific requirements or contact your local Hayward representative for assistance.

HAYWARD-HCSC60-Saline-C-6.0-Commercial-Salt-Chlorine-Generator-
fig-2

INSTALLATION

  • Unpacking
    Units are shipped from the factory. In the event of damage during shipping, it is the responsibility of the customer to notify the carrier immediately and to file a damage claim. Open the crate or packaging carefully and examine all material inside.

  • Storage
    When storing units, use the original packaging and store under a shelter to protect the contents from weather.

  • Plan Ahead

    • Almost every pump room encountered is different. It is imperative to have prior knowledge of the facility in which the unit is to be installed and to evaluate what type of tools, wall anchors, etc. will be needed to make the installation as problem free as possible.
    • The power supply must be installed at least 5 feet (1.5m) from the pool. It must also be mounted within 5 feet (1.5m) of the cell housing so the DC cables to the top of the electrolytic cell will reach. Also, any pool controller must be within 5 feet (1.5m) of the power supply so the control cord will reach.
    • The cell housing must be mounted at least 5 feet (1.5m) from the pool walls.
  • Power Supply Installation

    • The Saline C 6.0 system comes with 4 rubber feet on the bottom of the power supply and 4 keyhole mounting holes on the back of the power supply. The power supply can sit on a shelf or similar structure without any mounting or the system can be mounted on to a wall.
    • CAUTION To reduce the risk of injury – Never try to support the weight of the power supply using only drywall anchors. The power supply must have a stud for support!
    • Locate a space on the wall, in the pump room, that will accommodate the dimensions of the power supply. The two top keyhole mounting holes are 11-1/4 inches apart. Install screws and hang the power supply.
  • System Wiring

    • WARNING – Risk of Electric Shock. Hazardous voltage can shock, burn and cause death or serious property damage. To reduce the risk of electrical shock, turn off all power to the system.
    • CAUTION Chemical Hazard – Chemicals can cause internal and external burns, causing death, serious injury or property damage, to avoid: all systems must be wired so that when the pool circulation pump is off, the power to the Saline C 6.0 is off. Consult a Certified Electrician for the best wiring method to achieve this.
    • All Saline C 6.0 systems ship from the factory with a 3 foot black power cord and a 6 foot blue control cord.
    • Plug the power cord into a minimum 15 amp wall outlet protected by a ground fault circuit interrupter. Connect the blue control cord without the use of a chemical feed controller, plug the blue control cord into a 15 amp wall outlet protected by a ground fault circuit interrupter. This outlet must be interlocked with the circulation pump of the pool so that if the pump is turned off, power to the Saline C 6.0 is disconnected and the system is unable to operate.
  • Plumbing The System
    Saline C 6.0 systems require a minimum of 40 gpm of flow through the electrolytic cell housing to achieve the rated production of chlorine. The system can be plumbed with the full flow of the circulation system flowing through the cell housing or a bypass can be created to achieve 40 gpm of flow through the cell housing. In either case the cell housing must be installed as the last component in the return to the pool, after all other equipment. The vessel has 4 mounting holes for attaching to a floor or mounting surface. See the plumbing diagrams below.

HAYWARD-HCSC60-Saline-C-6.0-Commercial-Salt-Chlorine-Generator-
fig-4
HAYWARD-HCSC60-Saline-C-6.0-Commercial-Salt-Chlorine-Generator-
fig-5

  • Electrolytic Cell Housing Information
    • The cell housing may be installed in a “Z” configuration or in a “U” configuration. The water flow always enters at the bottom fitting (marked “Inlet”) and exits at one of the top fittings. The unused fitting is capped off with the supplied cap. The cell housing includes a slotted base for optional floor mounting. The inlet and outlet of the cell housing are 2 inch unions.
    • When installed correctly, the arrow on the electrode should align with the arrow on the vessel housing. This will ensure the gaps between the electrode blades are parallel to the ports allowing a clear water path between the blades.
    • NOTE: Do not to energize or operate the unit if the cell housing is damaged or improperly assembled.

HAYWARD-HCSC60-Saline-C-6.0-Commercial-Salt-Chlorine-Generator-
fig-6

  • Flow Switch Installation
    The 2 inch flow switch supplied with the system must be installed on the inlet side plumbing. Installing flow switch on the outlet side plumbing may cause premature flow switch failure. See diagrams on page 5. Flow switch must be pointed in the direction of water flow (refer to arrow on the T-fitting). Plug the flow switch into the power supply at the connector shown above.

  • Electrolytic Cell Wiring
    Connect the cell to the power supply with the connector provided.

OPERATION

Preparing The Water

  • Hayward® saline chlorination systems operate by electrolyzing sodium chloride, NaCl, (salt that has been added to the pool) to form free chlorine. In order for the Hayward system to operate, salt must be added directly to the pool at least 24 hours before the system is started.
  • 28 pounds of salt must be added for every 1000 gallons of pool water to reach 3500 ppm and 40 pounds of salt must be added for every 1,000 gallons of pool water to reach 5000 ppm. Once the salt has been added, brush the surface of the pool continuously until the salt has dissolved. Never leave large amounts of salt on the surface of the pool.
  • Only use pure NaCl. Do not use salt with additives. Contact your Hayward dealer for a list of approved salt.
  • Your pool water should be balanced in the following range before turning your Hayward system on:
    • Chlorine: 2 – 5 ppm
    • Total Chlorine: No more than 0.5 ppm above free chlorine
    • pH: 7.2 – 7.6
    • Alkalinity: 80 – 120
    • Hardness: 180 – 280 ppm
    • Salt: 3500 – 5000 ppm
    • Cyanuric acid: 20 – 50 ppm (Outdoor Pools only)
    • Phosphates: Less than 100 ppb
    • Temperaure:
    • 3,500ppm salt – Minimum Temp. – 78 Degrees F
    • 5,000ppm salt – Minimum Temp. – 60 Degrees F
    • Maximum Temp. – 104 Degrees F

Starting The System

  • Confirm that the salt concentration is 3500 to 5000 ppm.

  • Confirm that the valves to and from the cell are in the open position and water is flowing through the cell tube.

  • Confirm that the unit is plugged in and that the flow switch or controller relay is connected.
    The system will begin producing chlorine within 3 minutes.

  • Chemical Feed Controller: If the Saline C 6.0 system is linked to a chemical feed controller, adjust the output to maximum, which will allow for full production every time the controller calls for it. NOTE: The Saline C 6.0 system connected to a chemical feed controller will only operate when the controller is in feed mode. Make sure that the chemical feed controller is not set in proportional mode or system damage may occur.

  • Controlled Manually: If the system is being operated manually, start at 65% output. Over the following days, monitor the pool and increase/decrease the output in small increments based on the measured chlorine level. It may take several days of to find the ideal output setting.

System Operation

  • Saline C 6.0 systems operate when the main power supply cord is plugged in and the system has an input on the control connections from the flow switch and from a chemical feed controller. The Saline C 6.0 will continue to operate as long as there are inputs from those two sources.
  • Output is adjustable from 0 to 100% of the systems rating and is displayed as % output on the LCD display. To adjust the output, hold the output selector switch in the up position to increase output or in the down position to decrease output.
  • NOTE: Any time an output change is made with output selector switch, the Saline order for this to happen, the unit will wait 2 minutes from the time the change is made and shut down for 1 minute while it records the change. Output will resume after the 1 minute period.

Low Salt Alarm
In the event that salt falls to a level too low for system operation, the system will stop generating chlorine and the LCD display will flash “LO SALT”. To reset, correct the salt concentration and hold the output selector in the down position. When the fault is cleared, reset the output to the desired level.

Maintenance

  • This system produces free chlorine from the salt that you have added to the water. It will only continue to operate correctly if salt is maintained at a minimum 3500 ppm level.
    NOTICE: Low salt will lower the amount of chlorine produced, and cause damage to the electrolytic cell. The warranty will be void if the cell is damaged due to a low salt condition. Electrode life will be lengthened by keeping them clean and ensuring salt levels are at the correct level (see below).

  • Remember, the titanium plates that make up the cell are the most expensive part of the system and are going to need to be replaced roughly every 15,000 hours of operating time. By ensuring that salt is always at the correct level, and plates are cleaned regularly, you will increase their life.

    1. Check salt concentration. Salt must be maintained at no less than 3500 ppm. Check salt as often as necessary to ensure at least
      3500 ppm concentration. Salt concentration can be measured by using one or more of the following methods:
    • Salt test strips. Salt test strips are accurate as long as the expiration date has not expired and the cap is always replaced immediately. Follow the directions on the bottle.
    • A variety of hand held testers could be used. Hand held testers must be calibrated regularly, follow the manufacturer’s instructions.
    • Salt can be measured with a permanently mounted monitor or controller. These are typically accurate and require no calibration. A controller can be used to automatically keep the salt concentration at the desired level.
    • Adjust the salt concentration as often as needed to maintain the desired level.
    1. Test the flow switch for proper operation at least once a month.
    2. Evaluate the cell condition every week. Visually inspect the cell tube for leaks and the cell stack for calcium build up.
    3. The vessel is equipped with a drain plug for service. To drain the vessel, follow the procedure outlined below:
    • Disconnect power to the system
    • Close isolation valves to and from the vessel
    • Open the top of the vessel and remove the electrode stack
    • Remove the drain plug at the bottom of the vessel.
    1. Clean the cell when it needs it. Refer to the following instructions:
      The Saline C 6.0 system is designed to operate 24 hours a day and 7 days a week at maximum production rates. Please ensure the basic maintenance and cleaning instructions are followed to guarantee performance.
      CAUTION Chemical Hazard. Chemicals can cause burns both internally and externally. To avoid death, serious injury or property damage: Wear eye and skin protection while maintaining or servicing this unit. Do not inhale fumes from the unit.
  • Remove power from the system.

  • Close the isolation valves before and after the vessel.

  • Disconnect the blue connector between the power supply and vessel.

  • Remove the electrode stack by following these steps:

    1. Open the lid of the vessel by turning counter clockwise.
    2. When the lid meets resistance and stops turning, pull up on the black cables which will release the blue glamour cap.
    3. Once the blue glamor cap has been released, continue turning the vessel handles counter clockwise until completely loose.
    4. Remove the complete electrode stack assembly by pulling on the black cables.
  • In a clean plastic container, mix a 4:1 solution of water to muriatic acid (one gallon of water to one quart of muriatic acid). ALWAYS ADD ACID TO WATER – NEVER ADD WATER TO ACID. Be sure to wear rubber gloves and appropriate eye protection.

  •  Immerse the cell stack in the solution.

  • Leave the cell in the muriatic acid mix until the solution stops bubbling and the cell is clean.

  • Rinse the unit with clear clean water.

  • Reassemble the cell stack in the tube and reconnect the cables to the top of the cell stack

  • Once finished, insert the electrode stack assembly into the vessel and reconnect the blue connector to the power supply.

  • Turn the handles of the vessel clockwise until tight, and then push down on the blue glamour cap to avoid water from entering the top of the cell.

Winterization

  • In some cold climates it may be necessary to winterize the Saline C6 system. The procedure for this is as follows:
    • Disconnect power to the system
    • Close isolation valves to and from the vessel
    • Open the top of the vessel and remove the electrode stack
    • Remove the drain plug at the bottom of the vessel and drain all water
    • Once all water is drained, replace the drain plug, replace the electrode stack and close the vessel lid.
  • Make sure no water is in the vessel if there is a possibility of freezing.

Parts Guide

HAYWARD-HCSC60-Saline-C-6.0-Commercial-Salt-Chlorine-Generator-
fig-10

Number Part Number Description
1 HCXSCELL6 Replacement Cell & Cover
2 HCXSPS6 Power Supply
3 HCXSFLOS6 Flow Sensor
4 TBX122 2” PVC True Union Ball Valve Assembly Nut
5 ECX12T 2” PVC Pipe Connector Threaded
6 ECX12S 2” PVC Pipe Connector Socket
7 BSX1CAP2 2” PVC Port Cap
8 BSX1PLUG2 1” PVC Plug
9, 10, 11 SB2KIT O RINGS #111, #227, #357
12 BSXC201CK 2” Clear Body
13 ORX352V70 Piston Lid O-ring
NA HCXCCCC Replacement Cell Cbls, Connector & Grey Cap

SAFETY INSTRUCTION

  • WARNING – Read and follow all instructions in this owner’s manual and on the equipment. Failure to
    follow in structions can cause severe in jury and/or death .

  • WARNING – Suction Entrapment Hazard.

    • Suction in suction outlets and/or suction outlet covers which are, damaged, broken, cracked, missing, or unsecured can cause
      severe in jury an d/or death due to the following entrapment hazards:

    • Hair Entrapment – Hair can become entangled in suction out let cover.

    • Limb Entrapment- A limb inserted into an opening of a suction outlet sump or suction outlet cover that is damaged, broken,
      cracked, missing, or not securely attached can result in a mechanical bind or swelling of the limb.

    • Body Suction Entrapment- A negative pressure applied to a large portion of the body or limbs can result in an entrapment.

    • Evisceration/ Disembowelment – A negative pressure app lied directly to the intestines through an unprotected suction outlet
      sump or suction outlet cover which is, damaged, broken, cracked, missing, or unsecured can result in evisceration/
      disembowelment.

    • Mechanical Entrapment- There is potential for jewelry, swim suit, hair decorations, finger, toe or knuckle to be caught in an
      opening of a suction outlet cover resulting in mechanical entrapment.

  • WARNING -To Reduce the risk of Entrapment Hazards:

    • When outlets are small enough to be blocked by a person, a minimum of two functioning suction outlets per pump must be installed. Suction outlets in the same plane (i.e. floor or wall), must be in stalled a minimum of three feet (3′) (1 meter] apart, as measured from near point to near point.
    • Dual suction fittings shall be placed in such locations and distances to avoid “dual blockage” by a use r.
    • Dual suction fittings shall not be located on sea tin g areas or on the backrest for such seating areas.
    • The maximum system flow rate shall not exceed the flow rating of as listed on Table 1.
    • Never use Pool or Spa if any suction outlet component is damaged, broken, cracked, missing, or not securely attached.
    • Rep lace damaged, broken, cracked, miss in g, or not securely attached suction outlet components immediately.
    • In addition two or more suction out lets per pump installed in accordance wit h latest ASME, APSP Standards and CPSC guidelines, follow all National, State, and Local codes applicable .
    • Installation of a vacuum release or vent system, which relieves entrapping suction, is recommended.
  • WARNING – Failure to remove pressure test plugs and/or plugs used in winterization of the pool/spa from the suction outlets can result in an increase potential for suction entrapment as described above.

  • WARNING – Failure to keep suction outlet components clear of debris, such as leaves, dirt, hair, paper and other materia l can result in an increase potential for suction entrapment as described above.

  • WARNING – Suction outlet components have a finite life, the cover/grate should be inspected frequently and replaced at least every ten years or if found to be damaged, broken, cracked, missing, or not securely attached .

  • CAUTION – Components such as the filtration system, pumps and heater must be positioned so as to prevent their being used as means of access to the pool by young children. To reduce risk of injury, do not permit children to use or climb on this product. Closely supervise children at all times. Components such as the filtration system, pumps, and heaters must be positioned to prevent children from using them as a means of access to the pool.

  • WARNING – Hazardous Pressure. Pool and spa water ci rcu lation systems operate under hazardous pressure during start up, normal operation , and aft er pump shut off. Stand clear of circu lation system equipment during pump start up. Failure to follow safety and operation inst ru ctions co uld result in violent separati on of the pump housing and cover, and/or filter housing and clamp due to pressure in the system, which co uld cause property damage, seve re personal injury, or death. Before servic ing pool and spa water circulation system, all system and pump controls must be in off posi ti on and fi lter manual air relief valve must be in open position. Before starting system pump, all system va lves must be set in a position to allow system waterto return back to the pool. Do not change filter contro l valve position while sys tem pump is ru nning. Before starting system pump, ful ly open filter manua l air re lief va lve. Do not close filter manual air relief valve until a steady stream of water (not air or air and wate r) is discha rged.

  • WARNING – Separation Hazard. Failure to fo llow safety and ope ration instructions could resu lt in violent sepa ration of pump and/or filter components. Strainer cover must be properly secured to pump housing with strainer cover lock ring. Before servicing pool and spa circulation system, filters manua l air re lief valve must be in open pos ition. Do not operate pool and spa circulation system if a system component is not assembled properly, damaged, or missing. Do not operate pool and spa circulation sys tem unless filter manual ai r reli ef va lve body is in locked posi tion in filter upper body. Never operate or test the circulation system at more than 50 PSI.

  • WARNING – Risk of Electric Shock. All electrical wiring MUST be in confo rmance with applicable loca l codes,
    regu lati ons, and the National Electric Code (NEC). Hazard ous voltage can shock, bu rn, and cause death or serious property
    damage. To reduce th e risk of electric shock, do NOT use an exte nsion cord to connect unit to electric supp ly. Provide a properly
    located electri ca l rece ptacle. Before working on any electri ca l equipm en t, turn off power supply to the equipment. To re duce
    the risk of electric shock rep lace damaged wiring immediately. Locate conduit to preven t abuse from lawn mowers, hedge
    trimmers and other eq uipment. Do NOT ground to a gas supply li ne.

  • WARNING – Risk of Electric Shock Failure to ground all elec t rica l equ ipment can cause serious or fata l electri ca l shock hazard. Electrica l ground all electri cal equipmen t befo re connecting to electri ca l power supply.

  • WARNING – Risk of Electric Shock Failure to bond all electrica l equipment to pool structu re wi ll increase ri sk for
    electrocu tion and cou ld resu lt in in jury or death. To reduce the risk of elect ric shock, see in stallation instructions and consult a professiona l electrician on how to bond all electrical eq uipment. Also, contact a licensed elect ri cian for in formation on local electrica l codes for bonding requ irements. Notes to electrician : Use a solid copper conducto r, si ze 8 or larger. Run a con ti nuous wire from external bonding lug to rein forc ing rod or mesh. Connect a No. 8 AWG (8-4 mm2) [No. 6 AWG (13.3 mm2) for Ca nada) so lid cop per bonding wire to the pres su re wire connector provided on the electrica l equipment and to all metal parts of swimm ing poo l, spa, or hot tub, and metal piping (except gas pip ing) , and conduit within 5 ft. (1.5 m) of inside walls of swimm ing pool, spa, or hot tub.
    IMPORTANT – Reference NEC codes for all wiring sta ndards inc luding, but not limited to, groundin g, bonding and other general
    wiring procedures.

  • WARNING – Risk of Electric Shock. The electrical eq uipmen t must be connected on ly t o a supply circuit th at is protected by a ground-fault circu it- inte rrupter (GFCI). Such a GFCI should be provided by the installer and should be tested on a routine basis. To test the GFCI, push the test button. The GFCI sho uld i nte rrup t power. Push reset button . Power should be restored. If the GFCI fails to operate in this manner, the GFCI is defective. If the GFCI in terrupts power to the electrica l equipment without the test button being pushed, a ground cu rrent is flow ing, indi cating the possibility of an electrica l shock. Do not use th is electrical equipment. Disconnect the electrical equipment and have the problem corrected by a qualified service representative before us ing.

  • CAUTION – HAYWARD® pumps are intended for use with permanently-installed pools and may be used with hot tubs and spas if so marked. Do not use with sto rable poo ls. A permanently-in stalled pool is constructed in or on th e ground or in a buildin g such that it can not be rea dily disassembled for sto rage. A storable pool is constructed so that it is capa ble of being readily disassembled for storage and reassemb led to its original integrity.
    SAVE THESE INSTRUCTIONS

WARRNATY

  • To original purchasers of this equipment, Hayward Industries, Inc. warrants its Salt Chlorine Generator HCSC60 to be free from defects in materials and workmanship for a period of Two (2) years from the date of purchase with the following exception. The electrodes carry a One (1) year full warranty and a prorated warranty for the second year.
  • The limited warranty excludes damage from freezing, negligence, improper installation, improper use or care or any Acts of God.
  • Parts that fail or become defective during the warranty period shall be repaired or replaced, at our option, within 90 days of the receipt of defective product, barring unforeseen delays, without charge.
  • Proof of purchase is required for warranty service. In the event proof of purchase is not available, the manufacturing date of the product will be the sole determination of the purchase date.
  • To obtain warranty service, please contact the place of purchase or the nearest Hayward Authorized Service Center. For assistance on your nearest Hayward Authorized Service Center please visit us at www.haywardpool.com.
  • Hayward shall not be responsible for cartage, removal, repair or installation labor or any other such costs incurred in obtaining warranty replacements or repair.
  • The Hayward Pool products warranty does not apply to components manufactured by others. For such products, the warranty established by the respective manufacturer will apply.
  • The express limited warranty above constitutes the entire warranty of Hayward Pool Products with respect to its pool products and is in lieu of all other warranties expressed or implied, including warranties of merchantability or fitness for a particular purpose. In no event shall Hayward Pool products be responsible for any consequential, special or incidental damages of any nature. Some states do not allow a limitation on how long an implied warranty lasts, or the exclusion of incidental or consequential damages, so the above limitation may not apply to you. This warranty gives you specific legal rights, and you may also have other rights, which vary from state to state.
  • Hayward Pool Products
  • 620 Division Street
  • Elizabeth, NJ 07207

FCC Compliance Statement

  • This device complies with part 15 of the FCC rules. Operation is subjected to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
  • This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant of Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in residential installations. This equipment generates, uses, and can radiate radio frequency energy, and if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.
  • However, there is no guarantee that the interference will not occur in a particular installation. If this equipment does cause interference to radio or television equipment reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
    • Reorient or relocate the receiving antenna.
    • Move the equipment away from the receiver.
    • Plug the equipment into an outlet on a circuit different from that to which the receiver is connected.
    • Consult the dealer or an experienced radio/television technician for additional suggestions.

Product Registration

HAYWARD-HCSC60-Saline-C-6.0-Commercial-Salt-Chlorine-Generator-
fig-11

FOR FURTHER INFORMATION OR CONSUMER TECHNICAL SUPPORT, VISIT OUR WEBSITE AT
wwww.haywardcommercialpool.com

ABOUT COMPANY

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals