PHILIPS BY240P Smart Bright Dual Select Highbay Instruction Manual
- June 10, 2024
- Philips
Table of Contents
BY240P Smart Bright Dual Select Highbay
Product Information
- Type Description: BY240P 200W100W/840 850/WB PSR UNV SAA
- Power (W): 100W/150W/200W Selectable
- Voltage (V): 220-240
- Frequency (Hz): 50/60
- CCT (K): 4000K/4500K/5000K Selectable
- D (mm): 380
- H (mm): 143
- Weight: 3.0KG
- Mounting: Hook Mounting or Bracket Mounting
- Safety Cable/Chain Mounting: Required (not provided by Signify)
Product Usage Instructions
- Safety Cable/Chain Mounting:
- The luminaire must be mounted using a safety cable/chain.
- A safety cable/chain is not provided by Signify and should be provided by user. Use the holes provided for safety cable/chain on the luminaire.
- Cable Connection:
- Use the following cable connection: DIM+/Violet, DIM-/Gray, 0-10V dimming cable.
- Ensure basic insulation between LV and control conductors.
- Plug + cablec1.8m
- CCT and Wattage Selection:
- Select the desired CCT (4000K, 4500K, or 5000K) and wattage (100W, 150W, or 200W) using the appropriate switches.
- Inrush Current:
- The inrush current for the luminaire is as follows: Run current – 0.94A, Start(Inrush)current – 65A, Start current/Ipeak – 200us, conductor current – 0.7mA.
- Maximum Number of MCB:
- The maximum number of on MCB 16A Type B (pcs) is 8.
- The maximum number of on MCB 16A Type C (pcs) is 13.
- Product Disposal:
- This product should not be disposed with other household wastes throughout the AU/NZ.
- To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable reuse of material resources.
- To return your used device, please use the return and collection systems or contact the retailer where the product was purchased. They can take this product for environmental safe recycling.
- Warning:
- The external flexible cable or cord of this luminaire cannot be replaced; if the cord is damaged, the luminaire shall be destroyed.
How to use sensor:
- Remove the sensor from its packaging.
- Connect the sensor to the luminaire by screwing it tightly.
- Use either the BY240Z Highbay sensor (911401892082) or BY240Z Remote control (911401892182).
Philips and the Philips shield emblem are registered trademarks of Koninklijke Philips N.V.
Hook Mounting
Bracket Mounting
Safety cable/chain mounting
- Safety cable/chain must be mounted for this luminaire.
- Safety cable/chain is not provided by Signify,and should be provided by user..
Cable connection
Inrush Current
MODEL| Run current| Start(Inrush)current(| Start current| *Touch current or|
Maximum Number of| Maximum Number of
---|---|---|---|---|---|---
(A)| /Ipeak(A)| /T(@50% of Ipeak)(us)| conductor current(mA)| on MCB 16A Type
B (pcs)| on MCB 16A Type C (pcs)
BY240P 200W_100W/840_850| 0.94| 65| 200| 0.7| 8| 13
The leakage current (touch current or protective conductor current) of electrical circuit may be greatly dependent upon electrical supply cables used such as its rating and length, proper connection of electrical supply cables to luminaires and wiring connection topology of luminaires to the supply electrical circuit amongst other site conditions. In some cases referred to as Earth Leakage Current.
Recycling
This marking indicates that this product should not be disposed with other household wastes throughout the AU/NZ. To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable reuse of material resources. To return your used device, please use the return and collection systems or contact the retailer where the product was purchased. They can take this product for environmentally safe recycling.
Warning
- The luminaire shall be installed by a qualified electrician and wired in accordance with the latest IEE electrical regulations or the national requirements.
- Turn power off before inspection, installation or removal.
- Before using, external earthing is must required. Earthing is also must required in its whole life.
- The Luminaire must be used within the applicable product specifications, installation instructions and environmental conditions for storage & operations according to application guidelines provided for product Warranty to be valid.
- The corrosive atmosphere or hazardous materials such as sulfur, chlorine, phthalate, etc must be avoided during the use and storage.
- The manufacturer will not take responsibility caused by improper use or self-modifications of the product.
- Not use as floodlight Power Connection
- The external flexible cable or cord of this luminaire cannot be replaced;if the cord is damaged,the luminaire shall be destroyed. Application
- For Indoor use only.
- The height between luminous surface and ground suggested be more than 5m; the height between bottom of luminaire and mounting surface must be more than 0.3m.
- Luminaire don’t have any evaluation on additional protection measures to prevent luminaire from high-altitude falling and windproof structure, can’t be used as flood and tunnel luminaire.
- Not suitable for use in harsh vibration and often causing vibration or swinging environment. Also, not suitable for area prone to hurricane and extreme winds.
- For Australia and New Zealand, this product is not suitable for household use. Maintenance
- Ensure power supply is switched off before attempting any maintenance work.
- Periodic cleaning of the luminaire optical lens cover will ensure maximum optical efficiency.
- Luminaire shall be cleaned with a dry soft cloth only.
- The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.
- For Indoor use only. This product is not suitable for cold storage areas lower than -30⁰C or areas where obvious temperature gradients are present, such as ventilation opening, door, etc.
- FELV terminals marked “Risk of electric shock” are not safe to touch. Circuits connected to any FELV control terminal shall be insulated for the LV supply voltage of the controlgear and any terminals connected to the FELV circuit shall be protected against accidental contact.
How to use sensor