GREE ME34-44G 24 Volt Adaptor Owner’s Manual
- June 10, 2024
- Gree
Table of Contents
GREE ME34-44G 24 Volt Adaptor
Thank you for choosing our product. Please read this Owner’s Manual carefully
before operation and retain it for future reference. If you have lost the
Owner’s Manual, please contact the local agent or visit
www.gree.com or send an email to
global@cn.gree.com for the electronic version.
GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI
To Users
Thank you for selecting Gree’s product. Please read this instruction manual
carefully before installing and using the product, so as to master and
correctly use the product. In order to guide you to correctly install and use
our product and achieve expected operating effect, we hereby instruct as
below:
(1) This appliance is not intended for use by persons (including
children) with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision or
instruction concerning use of the appliance by a person responsibility for
their safety. Children should be supervised to ensure that they do not play
with the appliance.
(2) This instruction manual is a universal manual; some functions are
only applicable to particular product. All the illustrations and information
in the instruction manual are only for reference, and control interface should
be subject to actual operation.
(3) In order to make the product better, we will continuously conduct
improvement and innovation. We have the right to make necessary revision to
the product from time to time due to the reason of sales or production, and
reserve the right to revise the contents without further notice.
(4) For personal injury or property loss and damage caused by improper
operation such as improper installation and debugging, unnecessary
maintenance, violation of related national laws and rules and industrial
standard, and violation of this instruction manual, etc., we will bear no
liability.
(5) The 24 Volt Adaptor is the universal component. When indoor unit has
connected with the 24 Volt Adaptor , display status of indoor unit is decided
by the indoor unit. Valid status and invalid status are all belong to normal
status.
(6) The 24 Volt Adaptor is a general model, applicable for several kinds
of units. Some functions of the 24 Volt Adaptor are not available for certain
kinds of units, more details please refer to the owner’s manual of unit. The
setting of such unavailable function will not affect unit’s operation.
(7) The final right to interpret for this instruction manual belongs to
Gree Electric Appliances Inc. of Zhuhai.
Safety Notices
(Please be sure to abide)
WARNING: If these safety notices are not abided strictly, it may cause
severe damage to the unit or the people.
NOTE: If these safety notices are not abided strictly, it may cause
slight or medium damage to the unit or the people.
This sign indicates that the items operation must be prohibited.
Improper operation may cause severe damage or death to people.
This sign indicates that the items must be observed. Improper operation
may cause damage to people or property.
**WARNING!**
This product can’t be installed at corrosive, inflammable or explosive
environment or the place with special requirements, such as kitchen.
Otherwise, it will affect the normal operation or shorten the service life of
the unit, or even cause fire hazard or serious injury. As for the above
special places, please adopt special air conditioners with anti-corrosive or
anti-explosion function.
2 Notices for Use
(1) This device use 24VAC for power supply. Do not connect other power to
this device. Otherwise, it may cause fire hazard or damage to the unit.
(2) Before touching the electric components, please be sure the appliance
is disconnected to power.
(3) Never install the appliance in a damp place or allow it to be exposed
to direct sunlight.
(4) Never install the appliance near heat source or a place that may
easily get splashes of water.
(5) Please install the appliance in a place without electromagnetic
interference or dusty particles.
(6) Make sure that the communication wires are connected to the correct
ports, otherwise communication failure will occur and may damage the
appliance.
(7) Once wires are connected, use insulative tape to protect the wires
from oxidation and short circuit.
(8) Working conditions for the appliance: Temperature: -20~+60°C;
Relative humidity: 85%; Install it indoors and avoid direct sunlight, rain and
snow.
(9) Thermostat should be configured for use with a conventional system.
(10) Functions with “*” are optional for indoor units. If a function is
not included in an indoor unit, the adaptor can’t set the function, or setting
of this function is invalid to the indoor unit.
Functions Overview
24 volt adaptor is applicable for Gree split-type unit, cassette unit, duct-
type unit, floor ceiling unit and so on. Transfer the control signal of 24VAC
HVAC Thermostat (such as nest) into the control signal of Gree split-type
unit, cassette unit, duct-type unit, floor ceiling unit and so on to make the
third party 24VAC HVAC Thermostat can control Gree split-type unit, cassette
unit, duct-type unit, floor ceiling unit and so on. The device type should be
set as “24 Volt Adaptor”. As for different type of 24VAC HVAC Thermostat the
output 24VAC signal is different. Please set different interface type for 24
volt adaptor according to the output signal type of your purchased 24VAC HVAC
Thermostat.
NOTE!
- The signal of 24VAC HVAC Thermostat is the control command for controlling compressor, 4-way valve, indoor fan and other loads (set “00” for P01).And the type of 4-way valve (P02) also needs to be set. Refer to “parameter setting” for details.
- The signal of 24VAC HVAC Thermostat is the control command for setting cooling, heating, fan and other operation modes (set “01” for P01).
Please refer to the section of parameter setting for detailed setting operation. Appearance of 24 volt adaptor is shown as below:
Detail Introduction
Interface Function Instruction
Schematic diagram of interface of main board and interface function
instruction are shown as below:
Table 4.1.1 Function instruction of interface of main board
No. | Interface | Instruction |
---|---|---|
1 | H1, H2 | RS485 communication interface, |
connecting the indoor unit
2| O/B| 4-way valve for heat pumps
3| TR| Supply power for adapter (24VAC)
No.| Interface| Instruction
4| R| Supply power for thermostat (24VAC)
5| TC| Supply power for adapter (Common)
6| C| Supply power for thermostat (Common)
7| G| Fan/ indoor fan
8| W| Heating/E-heater
9| Y| Cooling/compressor
10| G1| Low fan speed
11| G2| Medium fan speed
12| G3| High fan speed
Button Instruction
Function instruction for buttons are shown as below:
Table 4.2.1 Function instruction for buttons
No. | Buttons name | Button function |
---|---|---|
SW1 | BACK | Return after parameter setting |
SW2 | DOWN | Decrease parameter setting |
SW3 | UP | Increase parameter setting |
SW4 | ENTER | Enter into project parameter setting and confirm parameter setting |
value
Display Instruction
3-bit nixie tube displays error code and engineering parameter setting.
Table 4.3.1 Display of 3-bit nixie tubeZ
Display content | Meaning |
---|---|
Error code | When there’s malfunction for the unit, please contact the after- |
sales service person. Please refer to the section of “error code” for the detailed error content.
When there’s malfunction for the unit, please contact the after-sales service person. Please refer to the section of “error code” for the detailed error content.
Function Instruction
Mode Setting
(1) When setting the signal of 24VAC as the control command of
compressor, 4-way valve, indoor fan and other loads (set “00” for P01), the
interface meaning is as below:
Table 4.4.1 Interface meaning of 24 Volt Adaptor (load control)
Interface | Meaning |
---|---|
O/B | 4-way valve for heat pumps |
G | Indoor fan |
W | E-heater |
Y | Compressor |
G1 | Low fan speed |
G2 | Medium fan speed |
G3 | High fan speed |
When setting O/B interface as the interface of 4-way valve for cooling, the
corresponding operation modes for the input signals of different interfaces on
the main board is:
Table 4.4.2 Corresponding operation mode for each input signal (set “01”
for P02)
Note: “G” in the below table represents G/G1/G2/G3 signal of
thermostat.
Y | G | O | W | Mode |
---|---|---|---|---|
* | × | * | * | OFF |
× | √ | * | × | Fan |
√ | √ | × | × | Heating |
× | √ | * | √ | Heating and E-heater |
× | × | √ | √ | OFF |
√ | √ | √ | × | Cooling |
√ | √ | × | √ | Heating and E-heater |
√ | √ | √ | √ | OFF |
When setting O/B interface as the interface of 4-way valve for heating the
corresponding operation modes for the input signals of different interfaces on
the main board is:
Table 4.4.3 Corresponding operation mode for each input signal (set “00”
for P02)
Note: “G” in the below table represents G/G1/G2/G3 signal of thermostat.
Y | G | B | W | Mode |
---|---|---|---|---|
* | × | * | * | OFF |
× | √ | * | × | Fan |
√ | √ | × | × | Cooling |
× | √ | * | √ | Heating and E-heater |
√ | √ | √ | √ | OFF |
√ | √ | √ | √ |
√| √| √| √| OFF
√| √| √| √| | Heating and E-heater
(2) When setting 24VAC signal as the control command for cooling, heating, fan and other operation modes (set “01” for P01), the interface meaning is as below:
Table 4.4.4 Interface meaning of 24 Volt Adaptor (mode control)
Interface | Meaning |
---|---|
G | Fan |
W | Heating |
Y | Cooling |
G1 | Low fan speed |
G2 | Medium fan speed |
G3 | High fan speed |
The corresponding operation modes for the input signals of different interfaces on the main board are:
Table 4.4.5 Corresponding operation mode for each input signal (mode
control)
Y | W | G | G1 | G2 | G3 | Mode |
---|---|---|---|---|---|---|
√ | × | * | * | * | * | Cooling |
× | √ | * | * | * | * | Heating |
× | × | √ | * | * | * | Fan |
× | × | * | √ | * | * | Fan |
× | × | * | * | √ | * | Fan |
× | × | * | * | * | √ | Fan |
√ | √ | * | * | * | * | OFF |
× | × | × | × | × | × | OFF |
NOTES!
- ” √ ” indicates ON; “×” indicates OFF; “*”indicates ON or OFF. When mode is Heating and E-heater If the unit supports auxiliary heating,
- when it meets the activation condition of auxiliary heating under heating mode, the auxiliary heating mode will be turned on.
- When G1, G2 and G3 are all OFF, the defaulted fan speed is auto fan speed (change the fan speed by referring to the parameter setting P03 Refer to “parameter setting” for details); When any one interface of G1, G2 and G3 is ON, the fan speed is decided by the signal of G1, G2 and G3. See the table as below:
Table 4.4.6 Control of fan speed
G | G1 | G2 | G3 | Mode |
---|---|---|---|---|
* | * | * | √ | High fan speed |
* | * | √ | × | Medium fan speed |
* | √ | × | × | Low fan speed |
Temperature Setting
(1) When the unit is operating under cooling mode, the adaptor is fixed
to send the set temperature of 16°C to the indoor unit;
(2) When the unit is operating under heating mode, the adaptor is fixed
to send the set temperature of 30°C to the indoor unit;
(3) When the unit is operating under fan mode, the adaptor is fixed to
send the set temperature of 26°C to the indoor unit.
Parameter Setting
(1) Press “ENTER” button to enter into parameter setting page. The nixie
tube displays “P00”.
(2) Press “UP” or “DOWN” button can select parameter code. Press
“ENTER” button to switch to parameter value setting and the nixie tube
flashes to display the parameter value. Press “UP” or “DOWN” button can
adjust the parameter value and then press “ENTER” to complete the setting
and return to previous level.
(3) Press “BACK” button to return to previous level.
NOTE!
After entering the parameter setting state, there will be no operation in 20s,
and the parameter setting state will be exited.
Unit parameters setting list is shown as below:
Table 4.4.7 Unit parameters setting list
Parameter code| Parameter name| Parameter range| Default
value| Remark
---|---|---|---|---
P00| Error code check| The last 5 error codes occurred| –| Check historic
error. When nixie tube displays “P00”, press “ENTER
SW4 ”button to enter historic error
check; press “UP SW3 ”or“DOWN SW2 ”to switch to display 5 historicerrors.
P01| Device type setting| 00: 24 Volt Adaptor(load control)
01: 24 Volt Adaptor(mode
control)
| 00| When set to “00”, “01”, as an adapter for the 24V thermostat, it needs
to be connected to a third-party thermostat.
P02| Energization method of 4-way valve| 00 4-way valve of heating is
energized 01 4-way valve of cooling is energized| 00| “O” is applicable for
the unit which operates under the cooling mode and its 4-way valve is
energized; “B” is applicable for the unit which operates under the heating
mode and its 4-way valve is energized;
P03| Fan speed setting| 00: auto 01: low 02: medium 03: high| 00| When P03 is
set at “00”, the fan speed when the indoor unit is started is subject to the
signal of temperature controller; when P03 is set at other parameter (not
“00”), P03 shall prevail and it can be set
P04| Delay OFF time setting| 00: 0min 01: 5 min 02: 10 min 03: 30 min| 00|
When the third party thermostat has reached to the temperature point (Y and W
signal are all OFF), the adaptor will continue to operate for a period of time
for ensuring the operation effect. The delay OFF time can be set through P04
setting.
Product Installation
Product Dimension
Installation Procedure
(1) Twist off the screws used for fixing the cover, and then open the
cover of 24 volt adaptor.
(2) Check whether the screws used for fixing the screws of main board is
loose. If yes, please tighten the screws until the main board is fixed.
(3) Attach the bottom case of 24 volt adaptor at the in stallation
position (such as wall), and then use the screw to fix the bottom case and the
installation hole on the wall together. Connect the wires to the corresponding
wiring terminal by passing through the rubber ring, and then tighten the
screws on the contact to fix the connection wire.
(4) Press the wires with wire-fixing clamp and then tighten the screws
used for fixing the wire-fixing clamp.
Note: If the wires may loose when fixing them with a wire clip, the wires
once or more times and then fix them with a wire clip. Otherwise, the
communication function may be affected due to the unreliable fixing.
Connection between Adapter and Indoor Unit
Connect H1 and H2 of communication interface of adaptor RS485 to corresponding
position of wired controller of unit to finish the installation.
Communication connection method: Wiring method with the indoor unit’s network,
which is shown as below:
NOTE!
If the indoor unit has 4-core connecting wire, please connect the 2-core
connecting wires of 24 volt adaptor. If the indoor unit has no 4-core
connecting wire, please connect to the mainboard of indoor unit after
connecting 4-core connecting wire with 2-core connecting wire of 24 volt
adaptor. RS485 communication interface of 24 volt adaptor is the non-polar
interface. It’s no need to consider the polar of RS485 interface for wiring.
Connection of Adaptor and Thermostat
The connection between 24 volt adaptor and the third party 24VAC HVAC
thermostat is shown as below:
(1) When the output signal of thermostat is the control command of load,
such as compressor, 4-way valve, indoor fan. The connection method is shown as
below:
NOTE!
The 4-way valve interface of 24VAC HVAC thermostat may only has type “O” or
“B”, and it can also connect O/B of adaptor , while it needs to set adaptor to
ensure that the adaptor has the same meaning with the interface of 24VAC HVAC
thermostat.
(2) When the output single of 24VAC HVAC thermostat is the control
command for operation mode, such as heating, cooling or fan mode. The
connection method is shown as below:
NOTE!
If the thermostat hasn’t G1, G2 and G3 (low, medium and high fan speeds) interfaces, it’s no need to connect wires for these three interfaces of adaptor.
Malfunction Display
When there’s malfunction during operation, the nixie tube of 24 volt adaptor will display the error code. If multiple malfunctions occur at the same time, error codes error codes will be displayed circularly.
CAUTION:
When there’s malfunction, please turn off the unit and ask for professional
person to maintain it.
Table 6.1 Error Code List
Error | Error Code | Error | Error Code |
---|---|---|---|
Return air temperature sensor open/short circuited | F1 | Drive board | |
communication error | P6 |
evaporator temperature sensor open/short
circuited
| F2| Compressor overheating protection| H3
Indoor unit liquid valve temperature sensor
open/short circuited
| b5| Indoor and outdoor units unmatched| LP
Indoor gas valve temperature sensor open/ short circuited| b7| Communication
line misconnected or expansion valve error| dn
IPM temperature sensor open/short circuited| P7| | E7
Outdoor ambient temperature sensor open/ short circuited| F3| Pump-down| Fo
Outdoor unit condenser mid-tube temperature sensor open/short circuited| F4|
Main error at grid connection side| y2
Discharge temperature sensor open/short circuited| F5| Forced defrosting| H1
Indoor and outdoor communication error| E6| Compressor startup failure| Lc
DC bus under-voltage protection| PL| High discharge temperature protection| E4
DC bus over-voltage protection| PH| Overload protection| E8
Compressor phase current sensing circuit error| U1| Whole unit over-current
protection| E5
Compressor demagnetization protection| HE| Over phase current protection| P5
PFC protection| Hc| Compressor desynchronizing| H7
IPM Temperature Protection| P8| IPM Current protection| H5
Over-power protection| L9| Compress or phase loss/ reversal protection| Ld
System charge shortage or blockage protection| F0| Frequency
restricted/reduced with whole unit current protection| F8
Capacitor charging error| PU| Frequency restricted/reduced with IPM
current protection
| En
High pressure protection| E1| Frequency restricted/reduced with high
discharge temperature
| F9
Low pressure protection| E3| Frequency restricted/reduced with anti-
freezing protection
| FH
Compressor stalling| LE| Frequency restricted/reduced with
overload protection
| F6
Over-speeding| LF| Frequency restricted/reduced with IPM
temperature protection
| EU
Drive board temperature sensor error| PF| Indoor unit full water error| E9
AC contactor protection| P9| Anti-freezing protection| E2
Temperature drift protection| PE| AC input voltage abnormal| PP
Sensor connection protection| Pd| Whole unit current sensing circuit error| U5
DC bus voltage drop error| U3| 4-way valve reversing error| U7
Outdoor fan 1 error protection| L3| Motor stalling| H6
Outdoor fan 2 error protection| LA| PG motor zero-crossing protection| U8
compressor inhalation temperature sensor error| dc| Indoor fan tripping error|
U0
Communication error between IDU and grid connection| Ln| IDU network address
error| y3
Communication error between ODU and grid connection| LM| Ip address allocation
overflow| yb
GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI
Add: West Jinji Rd, Qianshan, Zhuhai, Guangdong, China, 519070 Tel: (+86-756)
8522218
Fax: (+86-756) 8669426
E-mail: global@cn.gree.com
Web: www.gree.com