AKO 55323 Trapped Person Alarm User Manual

June 10, 2024
AKO

AKO 55323 Trapped Person Alarm

AKO 55323-Trapped-Person-Alarm-PRODUCT

Product Information

The Trapped Person Alarm AKO-55323 is designed to raise an alarm in case someone is trapped inside a cold room store. The alarm consists of a luminous push-button that is installed inside the cold room store and an acoustic and visual alarm center that must be installed in a location where the regular presence of people who can be alerted to the presence of alarms is guaranteed.

Versions and References

Model Description Power Supply
AKO-55323 Double trapped person station alarm 230 V~ 50/60 Hz
AKO-55123 Station alarm for 1 chamber 120 V~ 50/60 Hz
AKO-55120 Station alarm for 1 chamber 120 V~ + 8% – 12 % 50 – 60 Hz
AKO-55326 Luminous push-button protector for push-button
AKO-58120 Protector for push-button

Warnings

  • The alarm and detectors should be installed in a place protected from vibrations, water, and corrosive gases, where the ambient temperature does not exceed the value indicated in the technical data.
  • The station should be installed in a place where the regular presence of people who can alert to the presence of alarms is guaranteed.
  • Neither the alarm nor the push-button is suitable for areas classified as potentially explosive.

Equipment Description

The Trapped Person Alarm AKO-55323 is made up of a luminous push-button that must be installed inside the cold room store and an acoustic and visual alarm center that must be installed in a location where the regular presence of people who can be alerted by the alarm. The alarm center includes two acoustic alarms, two visual alarms, and an alarm display.

Product Usage Instructions

Before using the Trapped Person Alarm AKO-55323, please read the user manual carefully and follow the instructions provided.

  1. Install the push-button inside the cold room store using the AKO-55326 luminous push-button protector or the AKO-58120 protector for push-button if required.
  2. Install the acoustic and visual alarm center in a location where the regular presence of people who can be alerted by the alarm is guaranteed.
  3. Connect the Trapped Person Alarm AKO-55323 as shown in the Connection diagram provided in the user manual.
  4. After installation, test the system to make sure it is functioning correctly.
  5. In case of a trapped person, press the push-button inside the cold room store to raise an alarm. The alarm center will trigger an acoustic and visual alarm to alert people in the vicinity of the alarm.
  6. Regularly check and maintain the Trapped Person Alarm AKO-55323 as described in the Maintenance section of the user manual.

AKO Electromecànica thanks you and congratulates you on the purchase of our product, the development and manufacture of which involved the most innovative technologies, as well as rigorous production and quality control processes.
Our commitment to achieving customer satisfaction and our continuous efforts to improve day by day are confirmed by the various quality certificates obtained.
This is a high performance, technologically advanced product. Its operation and the final performance achieved will depend, to a great extent, on correct planning, installation, configuration and commissioning. Please read this manual carefully before proceeding to install it and respect the instructions in the manual at all times.
Only qualified personnel may install the product or carry out technical support.
This product has been developed for use in the applications described in the manual. AKO Electromecànica does not guarantee its operation in any use not foreseen in this document and accepts no liability in the case of damage of any type which may result from incorrect use, configuration, installation or commissioning.
Complying with and enforcing the regulations applying to installations where our products are destined to be used is the responsibility of the installer and the customer. AKO Electromecànica accepts no liability for damage which may occur due to failure to comply with these regulations. Rigorously follow the instructions described in this manual.
Whenever a malfunction of the device can cause personal or material damages, the fitter and maintenance staff are responsible for applying the necessary preventive and protection measures to prevent them. In the same way, the correct operation of the device must be periodically checked.
In order to extend the lifetime of our products to the maximum, the following points must be observed:

  • Do not expose electronic equipment to dust, dirt, water, rain, moisture, high temperatures, chemical agents or corrosive substances of any type.
  • Do not subject equipment to knocks or vibrations or attempt to handle them in any way differently to that indicated in the manual.
  • Do not under any circumstances exceed the specifications and limitations indicated in the manual.
  • Respect the indicated environmental conditions for operation and storage at all times.
  • During installation and on completion of this, avoid the presence of loose, broken or unprotected cables or cables in poor condition. These may constitute a risk for the equipment and its users.

AKO Electromecànica reserves the right to make any modification to the documentation and the product without prior notification.

Versions and references

AKO 55323-Trapped-Person-Alarm-FIG-
\(1\)

Warnings

  • The alarm and detectors should be installed in a place protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed the value indicated in the technical data. The station should be installed in a place where the regular presence of people who can alert to the presence of alarms is guaranteed.
  • Neither the alarm or the push-button are suitable for areas classified as potentially explosive.

Equipment description

Trapped person alarm to raise the alarm in case someone is trapped inside a cold room store.
It is made up of a luminous push-button that must be installed inside the cold room store, and an acoustic and visual alarm centre that must be installed somewhere that guarantees the usual presence of people that can be alerted by the alarm.AKO 55323-Trapped-Person-Alarm-FIG- \(2\)

Input indicators

  • Green constant: Trapped person in cold room store push-button.
  • Red flashing quickly: Malfunction/wiring fault in trapped person push-button.
  • Red flashing slowly: Push-button not detected or disconnected.
  • Red constant: Trapped person alarm active.

General alarm indicator

  • Fixed: Alarm active.
  • Flashing: Malfunction/wiring fault in push-button.

Status of power supply and battery

  • Green constant: Power supply at 230 V / 120 V
  • Red flashing: Power supply to battery
  • Green constant: Battery connected
  • Switched off: Battery disconnected

Installation

  • Remove the bezels (1) from the unit.
  • Loosen the screws (2) by turning them a 1/4 turn and open the cover (3).
  • Drill the holes needed for the cable entry glands using the pre-stamped centres on the sides of the housing for guidance. Fix the glands onto the device (4 and 5).
  • Make the 3 holes in the wall using template included.
  • Fix the unit to the wall using the screws and plugs supplied (6).
  • Insert the cables into the glands. Wire the unit following the diagram on page. 14.
  • Connect the battery (7) before closing the cover.
  • Close the cover (3), insert and tighten the screws (2) and replace the bezels (1).AKO 55323-Trapped-Person-Alarm-FIG- \(4\)

Wiring
The wiring between the detector/button and the station should NEVER be installed in a conduit together with power, control or feeder cables.

Always disconnect the power supply to do the wiring.
The power supply circuit should be equipped with a switch for its disconnection of at least 2 A, 230 V, situated near the appliance. The power supply cable will be H05VV-F or NYM-1×16/3. The section to be used will depend on current local regulations, but should never be less than 1.5 mm .
Cables for wiring the relay contact should have an adequate section depending on the unit to be connected.
The 120 / 230 V~ wiring must be kept clear of any other external element.
Make sure you have connected the batteries before starting-up the unit.
Pursuant to RD 138/2011 IF12 (SP) and standard EN-378-1 (EU), the Alarm’s power supply must come from a different circuit than the one used for the cooling and ventilation system.AKO 55323-Trapped-Person-Alarm-FIG-
\(5\)

Configuration

Self-diagnosis function
The equipment includes a self-diagnosis system that informs the user in the event of a malfunction in the detector or push-button or if there are errors in the wiring.
If a malfunction is detected, the alarm emits 3 short beeps every 2 minutes and the corresponding input indicator flashes red.

Operation

  • Without alarms
    The input indicators are green.

  • Alarm active
    The station emits an alarm sound, shows the affected input(s) in red, the general alarm indicator lights up and the visual alarm flashes.

  • Wiring error/malfunction
    The station emits 3 short beeps every two minutes and the input indicator affected flashes red.AKO 55323-Trapped-Person-Alarm-FIG-
\(6\)

The input indicator will turn on.

Maintenance

Clean the surface of the unit with a soft cloth, water and soap. Do not use abrasive detergents, petrol, alcohol or solvents.

Connectivity

The alarms are equipped with a port for connection of RS485 (MODBUS) data, that allows it to remotely manage them using an AKO-5012 webserver.
The MODBUS address is set at the factory and is indicated on the rating plate located on the left side of the alarm. This address must be different for each unit within the same network. The address can be changed using the AKONet software. Once modified, the old address indicated on the plate will not be valid.AKO 55323-Trapped-Person-Alarm-FIG- \(7\)

Technical specifications

  • Power supply AKO-55323 / AKO-55123 ……………………………………………………………230 V~ ± 10% – 50/60 Hz
  • AKO-55120 ……………………………………………………………………..120 V~ + 8% – 12% – 50/60 Hz
  • Maximum input power AKO-55323 Alarm 1 / Alarm 2……………………………………………………..3.1 VA
    • AKO-55123……………………………………………………………………………………..3.1 VA
    • AKO-55120………………………………………………………………………………………..5 VA
  • Accumulators ………………………………………………………………………………………………………………Ni-MH 800 mAh
  • Lighting + alarm duration…………………………………………………………………………………………………> 10 hours (*)
  • No. of inputs AKO-55323 Alarm 1 / Alarm 2…………………………………………………………………………….1
  • AKO-55123 / AKO-55120…………………………………………………………………………………………1
  • Compatibility of inputs……………………………………………………………………………………………….Button AKO-55326
  • Alarm relay …………………………………………………………………………………………………SPDT 230 Vac, 3 A, cos j =1
  • Working ambient temperature ……………………………………………………………………………………………-5 ºC to 50 ºC
  • Storage ambient temperature …………………………………………………………………………………………..-30 ºC to 70 ºC
  • Protection degree ………………………………………………………………………………………………………………………..IP 65
  • Installation category ……………………………………………………………………………………………………..II s/ EN 61010-1
  • Pollution degree …………………………………………………………………………………………………………..II s/ EN 61010-1
  • Double isolation between power supply, secondary circuit and relay output.
  • Sound power…………………………………………………………………………………………………………..90 dB(A) at 1 metre
  • MODBUS address…………………………………………………………………………………………………………..Shown on label
  • Dimensions……………………………………………………………………………….290 mm (W) x 141 mm (H) x 84.4 mm (D)
  • Maximum distance from push-button wiring …………………………………………………………………………………..300 m

Accessories

AKO-58120 protector
Protects push-button from possible impactsAKO 55323-Trapped-Person-Alarm-
FIG- \(8\)

Duration in alarm status up to a temperature of 25 ºC. In AKO-55323, only alarm 1 has a battery

AKO ELECTROMECÁNICA , S.A.L.
Avda. Roquetes, 30-38
08812
Sant Pere de Ribes.
Barcelona
Spain.
www.ako.com
We reserve the right to supply materials that might vary slightly to those described in our Technical Sheets. Updated information is available on our website.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals