IPL T PCS4 IP Link Power Control Interfaces
Product Information
About the IPL T PCS4 and IPL T PCS4i
The IPL T PCS4 and IPL T PCS4i are IP Link Power Control
Interfaces manufactured by Extron. They are designed to provide
power control and management of AV devices through an Ethernet
network.
Features
-
Four individually controlled AC power outlets (IPL T PCS4) or
four relay ports (IPL T PCS4i) -
Supports web-based configuration and management
-
Integrated IP Link technology for easy integration with other
Extron products -
Supports standard network protocols including TCP/IP, HTTP, and
SNMP -
Compatible with Extron GlobalViewer® Enterprise software for
centralized control and monitoring of multiple devices
Application Diagrams
The following diagrams show how the IPL T PCS4 and IPL T PCS4i
can be used in various AV applications:
Product Usage Instructions
Safety Instructions
Before using the IPL T PCS4 or IPL T PCS4i, please read and
follow the safety instructions provided in the user manual. The
product may contain dangerous voltage that can cause electric shock
if mishandled.
Battery Notice
The product contains a battery that should not be replaced by
the user. If the battery needs replacing, please return the entire
unit to Extron for service.
Software Commands
The IPL T PCS4 and IPL T PCS4i can be controlled using software
commands. Refer to the user manual for a list of available commands
and their syntax.
Web-based Configuration
The IPL T PCS4 and IPL T PCS4i can be configured and managed
through a web-based interface. To access the interface, connect the
device to a network and open a web browser. Enter the device’s IP
address to access the configuration page.
Integrating with Other Extron Products
The IPL T PCS4 and IPL T PCS4i integrate easily with other
Extron products using IP Link technology. Refer to the user manual
for instructions on how to configure and control multiple devices
using Extron GlobalViewer® Enterprise software.
Troubleshooting
If you are experiencing issues with the IPL T PCS4 or IPL T
PCS4i, refer to the troubleshooting section of the user manual for
solutions to common problems.
IPL T PCS4 IPL T PCS4i
IP Link Power Control Interfaces
User Guide
IP Link®
68-738-07 Rev. C 11 21
Safety Instructions
Safety Instructions · English
WARNING: This symbol, , when used on the product, is intended to alert the
user of the presence of uninsulated dangerous voltage within the product’s
enclosure that may present a risk of electric shock.
ATTENTION: This symbol, , when used on the product, is intended to alert the
user of important operating and maintenance (servicing) instructions in the
literature provided with the equipment.
For information on safety guidelines, regulatory compliances, EMI/EMF
compatibility, accessibility, and related topics, see the Extron Safety and
Regulatory Compliance Guide, part number 68-290-01, on the Extron website,
www.extron.com.
Sicherheitsanweisungen · Deutsch
WARUNG: Dieses Symbol auf demProdukt soll den Benutzer darauf aufmerksam
machen, dass im Inneren des Gehäuses dieses Produktes gefährliche Spannungen
herrschen, die nicht isoliert sind und die einen elektrischen Schlag
verursachen können.
VORSICHT: Dieses Symbol auf dem Produkt soll dem Benutzer in der im
Lieferumfang enthaltenen Dokumentation besonders wichtige Hinweise zur
Bedienung und Wartung (Instandhaltung) geben.
Weitere Informationen über die Sicherheitsrichtlinien, Produkthandhabung, EMI
/EMF-Kompatibilität, Zugänglichkeit und verwandte Themen finden Sie in den
Extron-Richtlinien für Sicherheit und Handhabung (Artikelnummer 68-290-01) auf
der Extron-Website, www.extron.com.
Instrucciones de seguridad · Español
ADVERTENCIA: Este símbolo, , cuando se utiliza en el producto, avisa al
usuario de la presencia de voltaje peligroso sin aislar dentro del producto,
lo que puede representar un riesgo de descarga eléctrica.
ATENCIÓN: Este símbolo, , cuando se utiliza en el producto, avisa al usuario
de la presencia de importantes instrucciones de uso y mantenimiento estas
estan incluidas en la documentación proporcionada con el equipo.
Para obtener información sobre directrices de seguridad, cumplimiento de
normativas, compatibilidad electromagnética, accesibilidad y temas
relacionados, consulte la Guía de cumplimiento de normativas y seguridad de
Extron, referencia 68-290-01, en el sitio Web de Extron, www.extron.com.
Instructions de sécurité · Français
AVERTISSEMENT : Ce pictogramme, , lorsqu’il est utilisé sur le produit,
signale à l’utilisateur la présence à l’intérieur du boîtier du produit d’une
tension électrique dangereuse susceptible de provoquer un choc électrique.
ATTENTION : Ce pictogramme, , lorsqu’il est utilisé sur le produit, signale à
l’utilisateur des instructions d’utilisation ou de maintenance importantes qui
se trouvent dans la documentation fournie avec l’équipement.
Pour en savoir plus sur les règles de sécurité, la conformité à la
réglementation, la compatibilité EMI/EMF, l’accessibilité, et autres sujets
connexes, lisez les informations de sécurité et de conformité Extron, réf.
68-290-01, sur le site Extron, www.extron.com.
Copyright © 2005-2021 Extron Electronics. All rights reserved. www.extron.com
Trademarks All trademarks mentioned in this guide are the properties of their
respective owners. The following registered trademarks (®), registered service
marks (SM), and trademarks (TM) are the property of RGB Systems, Inc. or
Extron Electronics (see the current list of trademarks on the Terms of Use
page at www.extron.com):
Registered Trademarks (®)
Extron, Cable Cubby, ControlScript, CrossPoint, DTP, eBUS, EDID Manager, EDID
Minder, eLink, Flat Field, FlexOS, Glitch Free, Global Configurator, Global
Scripter, GlobalViewer, Hideaway, HyperLane, IP Intercom, IP Link, Key Minder,
LinkLicense, LockIt, MediaLink, MediaPort, NAV, NetPA, PlenumVault, PoleVault,
PowerCage, PURE3, Quantum, ShareLink, Show Me, SoundField, SpeedMount,
SpeedSwitch, StudioStation, System INTEGRATOR, TeamWork, TouchLink, V-Lock,
VN-Matrix, VoiceLift, WallVault, WindoWall, XPA, XTP, XTP Systems, and ZipClip
Registered Service Mark(SM) : S3 Service Support Solutions
Trademarks (TM)
AAP, AFL (Accu-RATE Frame Lock), ADSP (Advanced Digital Sync Processing),
AVEdge, CableCover, CDRS (Class D Ripple Suppression), Codec Connect, DDSP
(Digital Display Sync Processing), DMI (Dynamic Motion Interpolation), Driver
Configurator, DSP Configurator, DSVP (Digital Sync Validation Processing),
EQIP, Everlast, FastBite, Flex55, FOX, FOXBOX, IP Intercom HelpDesk, MAAP,
MicroDigital, Opti-Torque, PendantConnect, ProDSP, QS-FPC (QuickSwitch Front
Panel Controller), Room Agent, Scope-Trigger, SIS, Simple Instruction Set,
Skew-Free, SpeedNav, Triple-Action Switching, True4K, True8K, VectorTM 4K,
WebShare, XTRA, and ZipCaddy
FCC Class A Notice
This equipment has been tested and found to comply with the limits for a Class
A digital device, pursuant to part 15 of the FCC rules. The Class A limits
provide reasonable protection against harmful interference when the equipment
is operated in a commercial environment. This equipment generates, uses, and
can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a residential area is
likely to cause interference. This interference must be corrected at the
expense of the user. NOTE: For more information on safety guidelines,
regulatory compliances, EMI/EMF
compatibility, accessibility, and related topics, see the Extron Safety and
Regulatory Compliance Guide on the Extron website.
VCCI-A Notice
I
Battery Notice
This product contains a battery. Do not open the unit to replace the battery.
If the battery needs replacing, return the entire unit to Extron (for the
correct address, see the Extron Warranty section on the last page of this
guide).
CAUTION: Risk of explosion. Do not replace the battery with an incorrect type.
Dispose of used batteries according to the instructions.
ATTENTION : Risque d’explosion. Ne pas remplacer la pile par le mauvais type
de pile. Débarrassez-vous des piles usagées selon le mode d’emploi.
Conventions Used in this Guide
Notifications
The following notifications are used in this guide:
CAUTION:
Risk of minor personal injury.
ATTENTION : Risque de blessure mineure.
ATTENTION: · Risk of property damage. · Risque de dommages matériels.
NOTE: A note draws attention to important information.
TIP: A tip provides a suggestion to make working with the application easier.
Software Commands
Commands are written in the fonts shown here: ^AR Merge Scene,,0p1 scene 1,1
^B 51 ^W^C.0 [01] R 0004 00300 00400 00800 00600 [02] 35 [17] [03] E X! X1&
X2) X2# X2! CE} NOTE: For commands and examples of computer or device
responses used in this guide, the character “0” is the number zero and “O” is
the capital letter “o.”
Computer responses and directory paths that do not have variables are written
in the font shown here:
Reply from 208.132.180.48: bytes=32 times=2ms TTL=32 C:Program FilesExtron
Variables are written in slanted form as shown here: ping xxx.xxx.xxx.xxx –t
SOH R Data STX Command ETB ETX Selectable items, such as menu names, menu
options, buttons, tabs, and field names are written in the font shown here:
From the File menu, select New. Click the OK button.
Specifications Availability
Product specifications are available on the Extron website, www.extron.com.
Extron Glossary of Terms
A glossary of terms is available at
http://www.extron.com/technology/glossary.aspx.
Contents
Introduction ……………………………………….. 1 About this Guide………………………………………….. 1 About
the IPL T PCS4 and IPL T PCS4i…………… 1 Features …………………………………………………….. 1
Application Diagrams……………………………………. 2
Installation and Rear Panels …………………. 4 Installation Overview ……………………………………..
4 Rear Panels ………………………………………………… 5 Setting Up the LAN Port ……………………………….. 6
LAN Port Cabling……………………………………… 6 Configuring the LAN Port…………………………… 6
Connecting the Devices………………………………… 7
Front Panel Features and Operation………. 8 Front Panel Features……………………………………..
8 Setting Up the System Using the Front Panel …… 9 Setting Up Power Control
………………………….. 9 Setting Power Level Reference Thresholds …… 9 Grouping
Receptacles …………………………….. 12 Front Panel Security Lockout (Executive
Mode)………………………………………………….. 12 Resetting the Unit ………………………………………. 13 Mode
1…………………………………………………. 14 Mode 3…………………………………………………. 14 Mode
4…………………………………………………. 14 Mode 5…………………………………………………. 15
HTML Configuration and Control …………. 16 Configuring the Hardware …………………………….
16 Setting Up the Computer Using ARP …………. 16 Setting Up the Computer Using a
Web Browser……………………………………………….. 18
Using the Embedded Web Pages…………………. 21 Viewing the System Status ……………………….
22 Configuration …………………………………………. 23 File Management ……………………………………. 33
Custom Web Pages …………………………………… 34 Server Side Includes (SSIs) ………………………. 34
Query Strings…………………………………………. 35 URL Encoding ……………………………………….. 37
A/V Device Power Control …………………………… 38 Custom Web Pages………………………………… 38
Accessing and Using Telnet (Port 23)…………. 39
Troubleshooting …………………………………………. 40 Power Connections ………………………………… 40
Network Connections ……………………………… 40
Downloading Global Configurator Software ……. 41
SIS Programming and Control …………….. 42 Host-to-Interface Communication………………….
42 Messages Initiated by the IPL T PCS4 ……….. 42 Password Information
……………………………… 43 Error Responses…………………………………….. 43 Error Response References
……………………… 43 Using the Command and Response Table ……… 44 Common Symbol
Definitions…………………….. 45 Command and Response Table for SIS Commands
…………………………………………….. 45
Mounting Instructions………………………… 53 Mounting the IPL T PCS4 Interface………………..
53 Tabletop Use …………………………………………. 53 Rack mounting procedure …………… 54 Under-
desk Mounting ……………………………… 55
Glossary…………………………………………… 56
IPL T PCS4 · Contents vii
IPL T PCS4 · Contents viii
Introduction
This section gives an overview of the IPL T PCS4 and IPL T PCS4i Power Control Interfaces and describes their features. The following topics are covered: · About this Guide · About the IPL T PCS4 and IPL T PCS4i · Features · Application Diagrams
About this Guide
This user guide contains information about the Extron IPL T PCS4 and IPL T
PCS4i Power Control Interfaces, including explanations of how to install,
configure, and operate them. Unless otherwise specified, IPL T PCS4 and PCS4
refer to both product versions throughout this guide.
About the IPL T PCS4 and IPL T PCS4i
The Extron IPL T PCS4 and IPL T PCS4i IP Link Power Control Interfaces are
Ethernetbased power management devices that can control power and schedule and
monitor up to four output devices via TCP/IP. The IPL T PCS4i is an
international version, configured for 220 VAC with IEC connectors.
The PCS4 can be a stand-alone control device or one of many nodes in a
distributed control system environment. It lets you remotely power on and off
any attached device and to individually sample and store device power levels.
The PCS4 has its own web pages, stored in flash memory within the device.
Features
· Remotely powering devices on and off — Centralized management features such
as Telnet allow remote powering on and off of projectors, cameras, video
conferencing equipment, switchers, and other audio/video equipment.
· Power level monitoring — Four 3-prong power output receptacles sense the
power level delivered. Each receptacle can sample and store power levels for a
device operating in full or standby mode.
· Individual power threshold settings — User-defined power thresholds can be
set for each receptacle. Each threshold can be associated with one or more
actions, such as activation of the alarm relay, e-mail notification, and so
on. When power exceeds or falls below a stored threshold, the programmed
actions are performed.
· Power-up sequencing — Power-up sequencing eliminates power surges at start-
up. When the IPL T PCS4 restarts, the receptacles are powered on sequentially,
separated by a user-configurable delay. (The factory default delay time is 1
second.) The attached devices are powered up in ascending order from
receptacle 1 through 4.
NOTE: The IPL T PCS4 powers up only those devices that were previously powered
on when the restart occurred.
IPL T PCS4 · Introduction 1
· Grouping of receptacles — To support dual powered devices by controlling
them simultaneously, two or more receptacles can be grouped together. Grouping
and ungrouping can be done via the front panel, TCP ports using Simple
Instruction Set (SIS) commands, or the internal web pages.
· Detection device (alarm relay) — This relay on the rear panel can be
connected to a relay-controllable siren or other detection device, and can be
programmed to react at specified power level thresholds. The alarm relay can
be configured for either normally open or normally closed state, which
activates the attached alarm device when power drops or increases beyond a
specified amount. E-mail messages can be generated based on alarm relay
conditions.
· Internet communication — The PCS4 uses standard Ethernet and TCP/IP
communication protocols, including ARP (Address Resolution Protocol), DHCP
(dynamic host configuration protocol), TCP/IP (Transmission Control
Protocol/Internet Protocol), Telnet, and HyperText Transfer Protocol (HTTP).
· Embedded web page serving — The IPL T PCS4 has 900 KB of internal flash
memory for storing user-customizable web pages and configuration settings.
Nonproprietary programming (HTML and JavaScriptTM) is available, as well as
other programming methods.
· Security — Built-in multilevel security provides user control over access to
devices attached to the PCS4. Appropriate security is provided by password
protection for Administrator and User levels.
NOTE: The factory configured passwords for all accounts on this device have
been set to the device serial number. In the event of an absolute system
reset, the passwords convert to the default, which is extron.
· Mounting — The PCS4 can be placed on a tabletop (four rubber feet are
provided and can be attached). Optional hardware for mounting the unit under a
desktop or podium or on a rack shelf is not included, but can be ordered
separately.
Application Diagrams
The following application diagrams show examples of how devices can be
connected to the IPL T PCS4 in different environments.
TCP/IP Network
Extron
10A 100-120V
IPL T PCS4
50/60 Hz
Power Control with
Sensing Capabilities
100-120V
TOTAL LOAD 10A MAX
LAN ALARM
Alarm
Projector
Figure 1.
CONTROL MODE
RO1OM
RO2OM
DPWISRP
MDUISTPE
5 4
6
7
3
2
1
VOLUME
COLOR
TINT
DETAIL
ADJUST
BRIGHT
CONT
MENU
NEXT DISPLAY
TX
COMPUTER
RX
IRLEARN RX
SYSTEM 7SC
VIDEO
S-VIDEO
INPAUUDTIO7
R L
System 7SC
Switcher
DVD
PC
Diagram for IPL T PCS4 (14 AWG Power Cord Required in US)
IPL T PCS4 · Introduction 2
TCP/IP Network
1
10A 200-240V
4
3
2
200-240V
TOTAL LOAD 10A MAX
LAN ALARM
Extron
50/60 Hz
IPL T PCS4i
Power Control with Sensing Capabilities
Alarm Codec
Figure 2.
Camera
Monitor
Projector
Connection Diagram for IPL T PCS4i
IPL T PCS4 R
1 F
S
2 F
S
3 F
S
4 F
S
SET REFERENCE STANDBY FULL
100 LINK ACT
IPL T PCS4 R
1 F
S
2 F
S
3 F
S
4 F
S
SET REFERENCE STANDBY FULL
100 LINK ACT
Extron IPL T PCS4 Power Control with Sensing Capabilities
Computer DVD VCR Audio Amplifier DSS
Cooling Fans
Figure 3. Illustration of an IPL T PCS4 in a Home Entertainment Center
IPL T PCS4 · Introduction 3
Installation and Rear Panels
This section contains installation and cabling instructions for the PCS4. The
following topics are discussed: · Installation Overview · Rear Panels ·
Setting Up the LAN Port · Connecting the Devices
Installation Overview
To install and set up an IPL T PCS4 interface, follow these steps: 1. Turn off
all of the equipment. Make sure that the video sources (DSS, cable boxes, or
other devices), the IPL interface, the output devices (monitors, VCRs,
projectors, and so on), and the controller are all turned off and disconnected
from the power source. 2. If desired, mount the PCS4 interface (see Mounting
the IPL T PCS4 Interface starting on page 53). 3. Plug the PCS4 power cord
into an AC outlet. For the 120 VAC version, use the supplied 14 AWG IEC power
cord. 4. Connect an active LAN Ethernet cable to the RJ-45 port on the rear
panel to establish a link to the network. 5. Set up an IP address for the PCS4
(see HTML Configuration and Control starting on page 16 or SIS Programming and
Control starting on page 42). 6. Plug the desired devices into the power
receptacles on the PCS4 rear panel. 7. Press the front panel buttons to power
on the receptacles. 8. Turn on the output devices. 9. Configure the PCS4
interface through the front panel, Telnet, or the web pages, then access the
unit using an Internet browser.
IPL T PCS4 · Installation and Rear Panel 4
Rear Panels
100-120V 10A
50/60 Hz
1
2
3
4
S/N XXXXXXXXX E0000 0408 00-05-A6-XX-XX-XX
5
ALARM
LAN
100-120V TOTAL LOAD 10A MAX
1
Figure 4.
2
IPL T PCS4 Rear Panel (120 VAC)
200-240V 10A
1
2
3
4
50/60 Hz
200-240V TOTAL LOAD 10A MAX
34
S/N XXXXXXXXX E0000 0408 00-05-A6-XX-XX-XX
ALARM
LAN
5
1
2
34
Figure 5. IPL T PCS4i Rear Panel (220 VAC)
1 Power connector — Connect a power cord from the AC power supply to this male
IEC power input receptacle. NOTE: For the IPL T PCS4, use the supplied 14 AWG
IEC power cord (part
number 27-407-01).
2 Output receptacles — Connect power cords from up to four devices to these
three-prong female U. S. (IPL T PCS4) or IEC (IPL T PCS4i) power output
receptacles.
3 Alarm relay — Connect a relay-controllable detection device to this single-
pole,
single-throw relay connector. (The default condition for this relay is
normally open.)
4 LAN connector and LEDs — An Ethernet connection can be used on an ongoing
basis to monitor and control the PCS4 (and the devices connected to it).
· RJ-45 port — Plug a patch cable into this RJ-45 female
LAN
socket, and connect the other end to a network switch, hub,
router, or PC.
· Link LED — This green LED lights to indicate a good network
connection. · Activity LED — This yellow LED blinks to indicate network
Activity LED
activity.
RJ-45 Port
Link LED
5 UID # label — Contains the unique User ID number (MAC address) of the unit
(for
example, 00-05-A6-00-00-01).
IPL T PCS4 · Installation and Rear Panel 5
Setting Up the LAN Port
LAN Port Cabling
· For 10Base-T (10 Mbps) networks, use a Category 3 or better cable.
· For 100Base-T networks, use a Category 5 cable.
· Use a straight-through cable to connect to a switch, hub, or router.
· Use a crossover cable to connect directly to a PC. Wire the connector as shown in the tables below.
Pins: 12345678
Crossover Cable
End 1 Pin Wire Color
End 2 Wire Color
Straight-through Cable
End 1 Pin Wire Color
End 2 Wire Color
Insert Twisted Pair Wires
RJ-45 Connector
Figure 6.
1 White-orange White-green
2 Orange 3 White-green 4 Blue 5 White-blue 6 Green 7 White-brown 8 Brown
Green White-orange Blue White-blue Orange White-brown Brown
T568A
T568B
A cable that is wired as T568A at one end
and T568B at the other (Tx and Rx pairs
reversed) is a “crossover” cable.
RJ-45 Connector Wiring
1 White-orange White-orange
2 Orange
Orange
3 White-green
White-green
4 Blue
Blue
5 White-blue
White-blue
6 Green
Green
7 White-brown
White-brown
8 Brown
Brown
T568B
T568B
A cable that is wired the same at both ends is called a “straight-through” cable, because no pin or pair assignments are swapped.
Configuring the LAN Port
You need to configure the LAN port before using it. You can configure the
settings via either SIS commands or the embedded web pages (see HTML
Configuration and Control starting on page 16 or SIS Programming and Control
starting on page 42 for details).
LAN port factory defaults: Link speed and duplex: Unit IP address: Subnet Mask: Gateway IP address: DHCP:
Auto Detect 192.168.254.254 255.255.0.0 0.0.0.0 Off
IPL T PCS4 · Installation and Rear Panel 6
Connecting the Devices
Connect the cables to the rear panel as follows: 1. Plug the Ethernet cable
from your network into the LAN port on the rear panel. 2. Plug the IPL T PCS4
power cord into a wall outlet. All front panel LEDs flash on briefly;
only the power and Ethernet LEDs remain lit. (No receptacle lights should
remain lit.) NOTE: A label covers the power receptacle on the IPL T PCS4 (US
version),
reminding you that you must use the supplied 14 AWG power cord for the PCS4 to
function properly. Remove this label before connecting the power cord to the
unit. 3. Plug the power cord of each device to be monitored into one of the
receptacles on the back panel of the PCS4. 4. If desired, connect a relay-
controllable siren or other detection device to the Alarm relay on the rear
panel. NOTE: The alarm relay cannot be set up from the front panel. You must
use either SIS commands or the web pages to configure it (see Power Receptacle
Monitoring and Alarm Functions SIS commands on page 46).
IPL T PCS4 · Installation and Rear Panel 7
Front Panel Features and Operation
This section contains a description of the IPL T PCS4 and IPL T PCS4i front
panel features and instructions for setting up the PCS4 using the front panel.
The following topics are discussed: · Front Panel Features · Setting Up the
System Using the Front Panel · Resetting the Unit
Front Panel Features
7 67 67 67 6
IPL T PCS4 1
1
F R
S
2 F
S
3 F
S
4 F
S
SET REFERENCE STANDBY FULL
100 LINK ACT
5
2
3
4
Figure 7. IPL T PCS4 and IPL T PCS4i Front Panel
1 Power LED (green) — When this LED is lit, the PCS4 or PCS4i power control
interface
is receiving power and is running. When the unit is being reset, this LED
blinks the appropriate number of times to indicate the reset mode that has
been entered.
2 Reset button (recessed) — Use the tip of a Phillips screwdriver or a pointed
stylus to
press this recessed button to reset the unit in one of four reset modes (see
Resetting the Unit on page 13 for details on reset modes and on using this
button).
NOTE: The factory configured passwords for all accounts on this device have been set to the device serial number. In the event of an absolute system reset, the passwords convert to the default, which is extron.
3 Power control buttons 1-4 — Press these buttons to switch power on and off
to the
output receptacle with the corresponding number on the rear panel. These
buttons are
also used, along with the Set Reference buttons (4), to set the Full and
Standby power
thresholds.
4 Set Reference (Power threshold) buttons — Press these buttons to set the
indicator
LEDs for each receptacle to indicate whether the attached devices are
operating at Full or Standby power level.
IPL T PCS4 · Front Panel Features and Operation 8
5 LAN status LEDs — These three LEDs show the status of the Ethernet
connection as
follows:
· 100 — When lit, indicates a 100 Mbps connection speed. Otherwise, the
connection speed is 10 Mbps.
· Link — Indicates that the interface has an active network connection.
· Act — (Activity) Blinks while data is being sent or received.
6 Power LEDs (red) — (One for each receptacle) (see figure 7 on page 8)
Indicate
that power is being supplied to the attached device.
7 Power Management (threshold) LEDs — (Set of two for each receptacle) After
the
power thresholds have been set, these LEDs indicate the status of the attached
device as follows:
· F — Indicates that power is at or above the Full reference threshold.
· S — Indicates that power is at or above the Standby reference threshold, and
below the Full threshold.
Setting Up the System Using the Front Panel
The PCS4 can be set up and operated by using:
· The front panel controls
· A computer or other device using an Ethernet connection and IP protocol
(Telnet or a web browser)
The following system setup procedures can be performed using the front panel,
the embedded web pages, or the SIS commands. Some settings can be adjusted
only through a host computer, either using SIS commands via Telnet or using
the PCS4 embedded web pages. For details on setup and control via Ethernet,
see SIS Programming and Control starting on page 42 or the HTML Configuration
and Control starting on page 16.
Setting Up Power Control
To set up control of power to the devices plugged into the PCS4 receptacles, do the following for each device:
1. On the PCS4 front panel, press and release the power control button for
the receptacle into which the device is plugged.
The Power LED at the right of the button lights and remains lit while the
receptacle is powered on. It is unlit when the receptacle is powered off.
1 F
S
2. Power on the device, using its own power switch.
Setting Power Level Reference Thresholds
Power LED
You can set the PCS4 to notify you when the power level of a connected device drops from Full to Standby or to None. For each device, you can use front panel controls to set the reference threshold (Full or Standby) at which a notification is triggered.
Until a threshold is set for a receptacle the first time, the status displayed for the receptacle on the web page or given in response to SIS queries is Not Set. Once a threshold has been set, the receptacle status defaults to None if all thresholds are cleared (see None and Not Set thresholds on page 11).
IPL T PCS4 · Front Panel Features and Operation 9
There are two common types of power for electronic devices: soft and hard.
· Soft power devices normally have three power states: On, Standby, and Off.
Such devices include projectors, DVD players, and VCRs.
Example: On soft power devices, the Standby mode allows the unit to be powered
to its Full power mode via RS-232 commands or a remote. Pressing a PCS4
receptacle button to Off when the receptacle is connected to a device that
supports Standby power causes the device to power off.
· Hard power devices normally have two power states: On and Off. These devices
include Extron switchers and interfaces.
Example: On Extron switchers, there is no power button or Standby condition,
and the unit power can be set only to On and Off from the PCS4 front panel.
Therefore, when the power is on, it is at Full power, and can be set for Full
reference threshold.
The Full and Standby reference thresholds must be configured with the device
attached to the PCS4 receptacle. The thresholds must be set in the correct
order, with Full being set first. Follow these steps to set the threshold for
each device, using the front panel. (These thresholds also can be configured
using the web pages or SIS commands.)
NOTE: The Full threshold must be set first. If Standby is set first, the
Standby reference setting is removed by the setting of the Full reference
threshold.
1. Connect a device to a power output receptacle on the IPL T PCS4. Make a
note of the receptacle number to which you connected it (1 through 4).
2. Press the corresponding front panel button to activate the receptacle.
Check to ensure that the Power LED for the receptacle is lit.
Setting the Full power threshold
1. Power on the attached device.
2. Press and hold the Full button on the PCS4 front panel (see the image at
right).
SET REFERENCE STANDBY FULL
3. While holding the Full button, press and release the button for the receptacle into which the device is plugged. Both the F (Full) LED and the S (Standby) LED for the selected receptacle blink twice. Only the Full LED remains lit.
Green Full LED
1 F
S
Receptacle Button
4. Release the Full button. The Full threshold for the receptacle is now set.
Setting the Standby power threshold 1. Power off the attached device. 2. Press and hold the Standby button (shown at right).
SET REFERENCE STANDBY FULL
IPL T PCS4 · Front Panel Features and Operation 10
3. While holding down the Standby button, press and
release the receptacle button for the same device for which Yellow you set the
Full threshold (see the illustration at right). The Standby Standby LED for
the selected receptacle blinks twice and LED
remains lit.
1 F
S
Receptacle Button
4. Release the Standby button.
5. Repeat steps 1 through 9 for any other receptacles to which you have connected devices to be controlled through the PCS4.
NOTE: Settings that are made via the front panel for power output receptacles and reference thresholds take approximately two minutes to be stored in memory. If you recycle power too soon after settings have been made, the settings are lost.
These threshold settings are preserved if the PCS4 AC power is recycled or if power is removed from an attached device. For example:
If the receptacle is set to…
And the power level…
Full
drops below the stored threshold
Standby
drops below the stored Standby threshold
exceeds the stored Standby threshold
The receptacle…
F (Full) led shuts off, and the S (Standby) LED lights.
S LED shuts off.
F LED lights.
To indicate that the configuration has been saved, both the Standby LED and the Full LED light and remain lit when those thresholds are selected.
None and Not Set thresholds
When a Full or Standby reference threshold has been set for a receptacle at
some time, and neither threshold is detected, a threshold status of None
appears on the web page or can be the response to SIS queries. None also
appears if the receptacle is powered off. The None threshold is a state that
is detected; it cannot be set manually.
If a receptacle has never been set to a Full or Standby reference threshold,
its threshold status is shown as Not Set on the web page and in response to
SIS queries. Not Set is the default setting for reference thresholds.
Clearing thresholds
To remove the reference threshold settings from any receptacle:
1. Shut off power to the receptacle that you want to clear by pressing its
button on the front panel. The red LED to the right of the button shuts off.
2. Press and hold the Standby or Full button while pressing and releasing the
receptacle button. All three receptacle LEDs flash twice, indicating that the
settings have been cleared.
3. Release the Standby or Full button that you were holding.
If desired, you can now turn power to the receptacle on again by pressing its
button.
IPL T PCS4 · Front Panel Features and Operation 11
Grouping Receptacles
Two or more power receptacles can be grouped so that both their connected
devices can be controlled simultaneously. To group receptacles using the front
panel, follow these steps for each receptacle: 1. Place the receptacle in
configuration mode by pressing and holding its receptacle
button for 2 seconds. The green Power LED on the front panel flashes
continually, indicating that the unit is in configuration mode. 2. Press each
receptacle button repeatedly to cycle through the available group selections,
indicated by the LEDs beside the button, until you arrive at the setting you
want for the receptacle: · No LEDs lit — No groups (The receptacle will not be
part of any grouping.) · S LED lit — Group 1 · F LED lit — Group 2 · Red
(power) LED lit — Group 3 3. Press either the Standby or the Full button to
exit configuration mode.
Ungrouping receptacles To remove a receptacle from a grouping: 1. Place the
receptacle in configuration mode by pressing and holding its button for two
seconds, until the green power LED flashes continually. 2. Press the
receptacle button repeatedly until none of its LEDs are lit (indicating no
groups). 3. Press the Standby or Full button to exit configuration mode.
Front Panel Security Lockout (Executive Mode)
When the PCS4 is in executive mode, it does not accept commands from the front
panel. If any button is pressed while the unit is in executive mode, the Power
LED flashes three times, indicating that the input from the front panel is not
being accepted. To enter or exit executive mode, press and hold the Standby
and Full buttons simultaneously for 2 seconds. The front panel Power LED
flashes three times to indicate that the mode has been switched. NOTE: If
power to the PCS4 is recycled while the unit is in executive mode, the PCS4
remains in executive mode.
IPL T PCS4 · Front Panel Features and Operation 12
Resetting the Unit
There are four ways to reset the PCS4 unit (called modes 1, 3, 4, and 5 for
the sake of comparison with other Extron IPL products). Reset the unit by
pressing the Reset button on the front panel (see Front Panel Features on page
8 for the button location). This button is recessed; it can be accessed with a
pointed stylus or small Phillips screwdriver.
ATTENTION:
· The reset modes described on the following pages break all TCP/IP
connections by closing all sockets to the unit.
· Les modes de réinitialisation décrits aux pages suivantes annulent toutes
les connexions TCP/IP en fermant tous les ports de l’unité.
IPL T PCS4 R F1
S
F2 S
F3 S
F4 S
Recessed Reset Button
STSAENTDRBEYFERFEUNLCLE L1IN0K0 ACT
Figure 8. Reset Button
ATTENTION:
· Review the reset modes carefully. Use of the wrong reset mode may result in
unintended loss of flash memory programming or a unit reboot.
· Analysez minutieusement les différents modes de réinitialisation. Appliquer
le mauvais mode de réinitialisation peut causer une perte inattendue de la
programmation de la mémoire flash, une reconfiguration des ports ou une
réinitialisation du processeur.
NOTES:
· If the Reset button is continually held in, the LEDs pulse (blink) every 3
seconds, and the PCS4 is put in a different mode, corresponding to the
underscored notes in modes 3 through 5. The mode 5 LED blinks three times, the
third blink indicating that it is the last mode.
· The reset modes are separate functions, not a progression from mode 1 to
mode 5.
· The factory configured passwords for all accounts on this device have been
set to the device serial number. In the event of an absolute system reset
(mode 5), the passwords convert to the default, which is extron.
IPL T PCS4 · Front Panel Features and Operation 13
Mode 1 Mode 3 Mode 4
Activation Result
Purpose and notes
Hold in the Reset button while applying power to the unit.
Returns the unit to the default base firmware that was shipped with the PCS4
from the factory. Event scripting does not start when the unit is powered on
in this mode.
Use mode 1 to remove a version of firmware if incompatibility issues arise.
All user files and settings are maintained. User web pages may not work if you
are using an earlier firmware version.
NOTE: After a mode 1 reset, the factory-installed firmware version remains in effect only until the unit is powered off. After a power cycle, the PCS4 returns to the firmware that was installed prior to the mode 1 reset.
Activation
Hold the Reset button in until the Power LED blinks once (approximately 3
seconds). Release it, then immediately press it again momentarily (for less
than 1 second).
NOTE: Nothing happens if the momentary press does not occur within 1 second.
Result Purpose and notes
Turns events on or off, depending on their current state. During resetting,
the reset LED flashes two times if events are starting and three times if
events are stopping.
This mode is used for troubleshooting.
Activation
Hold the Reset button in until the Power LED blinks twice (approximately 6
seconds). Release it, then immediately press it again momentarily (for less
than 1 second). The Power LED blinks four times in quick succession,
confirming a mode 4 reset.
NOTE: Nothing happens if the momentary press does not occur within 1 second.
Result Purpose and notes
Reset mode 4 does the following: · Enables ARP program capability. · Sets the IP address back to factory IP settings. · Sets the subnet mask back to factory default. · Sets the gateway address back to factory default. · Sets port mapping back to factory default. · Turns DHCP off. · Turns events off. Mode 4 enables you to set IP address information using ARP and the MAC address.
IPL T PCS4 · Front Panel Features and Operation 14
Mode 5
Activation
Hold in the Reset button until the Power LED blinks three times (approximately
9 seconds). Release it, then immediately press it again momentarily (for less
than 1 second). The power LED blinks four times in quick succession,
confirming a mode 5 reset.
NOTE: Nothing happens if the momentary press does not occur within 1 second.
Result Purpose and notes
Performs a complete reset to factory defaults (except for the firmware).
Mode 5 is useful if you want to start over with control software configuration
and to replace events.
This reset also removes the initial serial number passwords and sets them to
extron.
IPL T PCS4 · Front Panel Features and Operation 15
HTML Configuration and Control
The IPL T PCS4 must be configured before use, or it cannot control other
devices. In addition to using the buttons on the PCS4 front panel, you can
configure and control the PCS4 via any computer attached to a LAN by using the
embedded web pages or SIS commands. This section describes the web pages and
provides instructions for using them to configure the IPL T PCS4 series
interfaces. Topics include: · Configuring the Hardware · Using the Embedded
Web Pages · Custom Web Pages · A/V Device Power Control
Configuring the Hardware
To function together, both the computer and the PCS4 must be configured
correctly. The computer must be network-capable with the proper protocols, and
the PCS4 must be set up so it can be connected to a LAN (local area network).
Note that some settings can be configured only via Internet protocol. For your
computer to communicate with the PCS4, it must be equipped with an network
interface card and an HTML browser. To allow your computer to work with Extron
Ethernetcontrolled products, the TCP/IP protocol must be installed and
properly configured.
Setting Up the Computer Using ARP
The Address Resolution Protocol (ARP) command provides a quick way to set up
an IP address for the PCS4, using your computer. The ARP commands tell your
computer to associate the PCS4 Media Access Control (MAC) address with an IP
address that you assign. After entering the ARP command, enter a ping command
to access the PCS4 at its new address to confirm the address has been
successfully changed. 1. Obtain a valid IP address for your PCS4 from your
network administrator. 2. Obtain the PCS4 MAC address (UID#) from the label on
its rear panel. The MAC
address should have the following format: 00-05-A6-xx-xx-xx where x can be a
letter or a number. 3. If the PCS4 has never been configured and is still set
for factory defaults, skip to step 4. If not, perform a mode 4 system reset to
restore the factory-set values (see Resetting the Unit on page 13 for the
resetting procedure). NOTE: The PCS4 must be configured with the factory
default IP address
(192.168.254.254) before you execute the ARP command, as described below.
IPL T PCS4 · HTML Configuration and Control 16
4. On the computer, access the command prompt, then enter arp -s, the desired
new IP address for the PCS4, a space, and finally the PCS4 MAC address (taken
from the label on the rear panel). For example: arp -s 10.13.170.15
00-05-A6-00-0A-90 A space must separate arp from the hyphen (-).
Figure 9. ARP-S Command Screen NOTE: After the arp -s command is issued, the
PCS4 changes to the new address
and starts responding to ping requests, as described in the next step. 5. To
verify that the new address has been set, execute a ping command by entering
ping, followed by the new IP address, at the command prompt. NOTE: Ping is a
utility or diagnostic tool that tests network connections. It is used
to determine if the host has an operating connection and is able to exchange
information with another host. Example: ping 10.13.170.15 Ping is a utility or
diagnostic tool that tests network connections. It is used to determine if the
host has an operating connection and is able to exchange information with
another host. The response should be the new IP address of the PCS4, as shown
below.
Figure 10. Screen Showing the Ping Command You can reconnect using either
Telnet or a web browser to verify that the update was successful.
IPL T PCS4 · HTML Configuration and Control 17
6. After verifying that the IP address change was successful, issue the arp
-d command at the DOS prompt to remove the address from the ARP table. For
example: arp -d 10.13.170.15 A space must separate arp from the hyphen (-).
Setting Up the Computer Using a Web Browser
To set up the PCS4 using a web browser, you must temporarily configure the
computer to communicate with the interface. Then you can change the PCS4
default settings (IP address, subnet mask, and [optionally] administrator name
and password) in order to use the unit on an intranet (LAN) or on the Internet
(WAN). After you have set up the PCS4 for network communication, you can reset
the computer to its original network configuration. NOTE: The factory
configured passwords for all accounts on this device have been
set to the device serial number. In the event of an absolute system reset, the
passwords convert to the default, which is extron. IPL T PCS4 LAN port
defaults: · PCS4 IP address: 192.168.254.254 · Gateway IP address: 0.0.0.0 ·
Subnet mask: 255.255.0.0 · DHCP: Off · Link speed and duplex level: Auto
detected If you use an existing Ethernet LAN intranet, your network
administrator can provide you with a unique IP address for the PCS4 or confirm
whether you need to set up the PCS4 for Dynamic Host Configuration Protocol
(DHCP) to have an address assigned automatically when you sign on.
Setting up the computer for IP communication Follow these steps to set up
communication between your computer and the PCS4. NOTE: The procedure and
illustrations in this section are for Windows XP. For other
Windows versions, the screens may appear slightly different. 1. Open the
Network Connections page as follows:
a. From the Start menu, select My Network Places. b. From the Network Tasks
left side-bar menu, select View Network connections. 2. Right-click Local Area
Connection, then select Properties from the pop-up menu.
Figure 11. Network Connections Dialog Box IPL T PCS4 · HTML Configuration and
Control 18
3. Select Internet Protocol (TCP/IP), and click the Properties button. If
Internet Protocol (TCP/IP) is not on the list, it must be added (installed).
See your Windows user manual or the Windows online help system for information
on how to install the TCP/IP protocol.
Figure 12. Internet Connection 4. Write down the current IP address of your
computer and its subnet mask below. You
will need to restore these settings to the computer later. If an IP address
automatically has been selected, make a note of that. If not, write down the
following: IP address: __ Subnet mask:
__ 5. Change the IP address of the computer
temporarily so that it can communicate with the PCS4. a. Select the Use the
following IP address: radio button. b. Enter the following values as shown
below:
IP address: 192.168.254.253 Subnet mask: 255.255.0.0 Default gateway: Blank or
0.0.0.0 (The temporary IP address differs from the PCS4 factory default by one
digit.)
IPL T PCS4 · HTML Configuration and Control 19
Figure 13. Enter the IP Address
c. Click OK to save the changes, and exit the network setup.
d. Reboot the computer if required for the changes to become effective.
6. Plug one end of a Category 5, 6, or 6E Ethernet crossover cable into the
Ethernet (LAN) connector on the PCS4 rear panel (see Setting Up the LAN Port
on page 6 and Rear Panels on page 5 for information on the RJ-45 LAN connector
wiring). Plug the other end of the Ethernet cable into the Ethernet port on
the computer. NOTE: If you are using a network hub or switch between the
computer and the PCS4, use a straight-through Category 5 cable instead of a
crossover cable.
7. Set up the PCS4 IP address (see Configuring the IPL T PCS4 using a web
browser for the procedure).
After the PCS4 has been reconfigured, an Ethernet (intranet or Internet)
connection can subsequently be used to configure or control it.
NOTE: Both your computer and the PCS4 must be connected to the same LAN.
Alternatively, you may use a crossover Ethernet cable to connect the interface
directly to your computer Ethernet card.
8. After setting the PCS4 IP address, restore the previous IP configuration
of the computer by following steps 1, 2, 3, and 5 but using the original IP
address settings that you wrote down in step 4.
Configuring the IPL T PCS4 using a web browser The default web pages that are
preloaded on the PCS4 are compatible with popular web browsers such as
Internet Explorer (version 5.5 or higher). NOTE: The following instructions
assume that you have already configured the
Windows-based computer, connected it to the PCS4 LAN port, and powered on the
interface.
1. Obtain a valid IP address, subnet mask, and gateway address for the PCS4
from your network administrator.
2. Launch a web browser (such as Internet Explorer) on the connected computer
(for which you set up the network configuration earlier), and enter the PCS4
default address, http://192.168.254.254, in the address box. The PCS4 default
web page is displayed.
IPL T PCS4 · HTML Configuration and Control 20
3. Select the Configuration tab, then select System Settings from the side
bar menu on the left of the screen. A configuration System Settings web page
appears. A typical settings screen is shown below.
Figure 14. Example of a Default System Settings Page 4. IP, gateway, and
subnet mask addresses follow standard naming and numbering
conventions and protocol (nnn.nnn.nnn.nnn). The IP network administrator
should provide the addresses to be used with this interface. Enter the new IP
address assigned for the PCS4, the corresponding subnet mask, and gateway
address, then click Submit. The PCS4 takes approximately 2 minutes to store
the new settings. After the IP address is changed, your computer loses
communication with the PCS4 and a screen appears, indicating that the page
cannot be displayed. 5. Close the browser. 6. After changing the PCS4 IP
settings, change your computer TCP/IP settings back to their original
configuration, and reboot if necessary. You are now able to access the PCS4
web pages to configure the front panel.
Using the Embedded Web Pages
The PCS4 features an embedded web server, which includes factory set web
pages. These pages can be replaced with user-designed files, but the default
web pages provide many basic features for monitoring, configuring, and
controlling the PCS4 via a web browser. This section provides an overview of
the embedded web pages. To access the web pages: 1. Launch a web browser (for
example, Internet Explorer®) on your connected computer. 2. On the browser
Address line, enter the PCS4 IP address. If a password has been set,
the Enter Network Password dialog box opens. NOTE: The factory configured
passwords for all accounts on this device have been
set to the device serial number. In the event of an absolute system reset, the
passwords convert to the default, which is extron.
IPL T PCS4 · HTML Configuration and Control 21
If no password has been set, the PCS4 web page opens, displaying the System
Status page. Skip steps 3 and 4. 3. In the User Name field on the password
window, enter text of your choice, or leave the User Name field blank.
Figure 15. Password Prompt Window 4. Enter the administrator password in the
Password field, and click OK. The PCS4 web
page is displayed. NOTES:
· Passwords must contain 4 to 12 alphanumeric characters. Symbols and spaces
are not allowed, and the passwords are case sensitive.
· Administrators have access to all of the web pages and are able to make
changes to settings. Users can access only the System Status page.
Viewing the System Status
The System Status web page, accessed by clicking the Status tab, provides
information on the current settings. Changes must be made via the
Configuration web pages or SIS commands (see SIS Programming and Control on
page 42). Personnel who have user access can view this page but cannot access
the Configuration or File Management pages to make changes. Figure 17 shows an
IPL T PCS4 System Status web page.
Figure 16. System Status Web Page IPL T PCS4 · HTML Configuration and Control
22
The System Status page displays information in the following categories: ·
System Description: Includes product model, a brief description, part number,
and
firmware version, plus the current date and time. · IP Settings: Displays the
unit name, IP address, MAC address, and all other current IP
settings. · AC Receptacles: For each receptacle, shows whether the receptacle
is turned on or
off; the current power level threshold setting (Full, Standby, Not Set, or
None); whether the receptacle is part of a group; and the alarm state. ·
Current Schedule: Shows the day of the week and the time that any receptacle
has been scheduled to power on and off.
Configuration
There are seven Configuration web pages, which only administrators can access.
They are listed in the side-bar menu at the left of the Configuration screen.
The following sections discuss the tasks that you can perform on these
screens. Specifying system settings On the System Settings screen, you can set
the date and time, and change the IP address information for the PCS4. To
change the available system settings:
Figure 17. System Settings Screen on the Configuration Tab 1. On the
Configuration page, select System Settings from the side-bar menu at the left
edge of the screen. The System Settings screen appears, displaying either the
factory default information for your PCS4, or the settings submitted most
recently. 2. Enter your new information in the IP Settings section or select
the date and time from the menus in the Date/Time Settings section.
IPL T PCS4 · HTML Configuration and Control 23
IP settings
The following settings are available in the IP Settings section:
· Unit Name: The default is the product name followed by the last six digits
of the MAC address. You can give the unit a new name (such as LightsOn&Off or
BoardroomA-PCS4) consisting of up to 24 alphanumeric characters including the
hyphen (-). NOTE: The first character must be an alpha character, and the last
character cannot be a hyphen. The unit name is not case-sensitive.
· DHCP: DHCP is a communications protocol that assigns addresses on the local
network automatically. Select the On or Off radio button to enable or disable
DHCP.
· IP Address: You can enter a new network address consisting of four sets of
up to three digits, separated by periods (nnn.nnn.nnn.nnn).
· Gateway IP Address: A gateway is a device that connects your network with
others that may be using different, incompatible communications protocols. You
can enter your gateway address (obtained from your network administrator),
using the same format that is used for the IP Address. (If there is no
gateway, this field defaults to 0.0.0.0.)
· Subnet mask: The subnet mask is used to split IP networks into a series of
subgroups (subnets). The mask is a binary pattern that is matched up with the
IP address to turn part of the host ID address field into a field for subnets.
You can enter a new subnet mask address using the same format that is used for
the IP Address.
Date and time settings
The following settings are available in the Date/Time Settings section. NOTE:
This section lets you set the date and time on your PCS4 unit. However,
the passage of time is not reflected in the Date and Time fields on the web
page. The screen continues to display the settings you entered and does not
increment them as time passes. However, the PCS4 itself continues to keep the
correct time internally, enabling you to schedule power on and off for the
receptacles.
· Date: Select month, day, and year from the pull-down menus.
· Time: Select hours, minutes, and AM or PM from the pull-down menus.
· Zone: From the pull-down menu, select the time zone for the PCS4 location
(number of hours offset from Greenwich mean time).
· Daylight Savings: Daylight savings time (DST) is a one-hour offset that is
observed in some countries. You can select a radio button to set the PCS4 for
daylight savings time for the US, Europe, or Brazil; or select Off to disable
it.
The following daylight savings periods are observed:
· US — Starts the second Sunday in March and ends the first Sunday in
November.
· Europe — Starts the last Sunday in March and ends the last Sunday in
October.
· Brazil — Starts the third Sunday in October and ends the third Sunday in
February. (Equatorial Brazil does not observe DST.)
3. When you have made all the desired changes in one section, click the
Submit button at the bottom of the section. The new IP settings are displayed
at the right of the fields in which you entered them. The new date and time
settings are displayed in the fields in which you entered or selected them.
4. Follow steps 2 and 3 to make changes in the other section, if desired.
Clicking Cancel in either section restores the previous settings, if the
values you entered have not been submitted.
IPL T PCS4 · HTML Configuration and Control 24
Assigning passwords The Passwords screen allows you to assign passwords to the
administrator and user access levels. The administrator password gives access
to all IPL T PCS4 web pages, enabling the administrator to configure the PCS4.
The user password provides access only to the System Status web page. If you
are logged in as user, you see only the Status tab with the System Status
screen. You cannot make any configuration changes. NOTE: The factory
configured passwords for all accounts on this device have been set
to the device serial number. In the event of an absolute system reset, the
passwords convert to the default, which is extron.
To assign passwords: 1. On the Configuration page, select Passwords from the
side-bar menu. 2. Enter the new administrator password in the Administrator
Password field.
NOTE: Passwords must contain 4 to 12 alphanumeric characters. Symbols and
spaces are not allowed, and the passwords are case sensitive.
3. In the Re-enter Admin Password field, enter the same password again to
confirm it. 4. If you want to assign a user password, enter it in the User
Password field.
NOTE: You cannot assign a User password unless an administrator password has
either been assigned or is being assigned at the same time.
5. Reenter the same user password in the Re-enter User Password field.
Figure 18. Passwords Screen with Administrator and User Passwords Entered
6. Click Submit to set the passwords.
Removing passwords NOTE: Deleting the administrator password also deletes the
user password. To remove a password: 1. On the Configuration page, select
Passwords from the sidebar menu. 2. In the Administrator Password, the User
Password, or both fields, delete the
characters that are there, and press the
IPL T PCS4 · HTML Configuration and Control 25
Entering e-mail addresses for alerts If you have created scheduled events or
monitoring tasks on the PCS4, you can write an e-mail alert with a message
corresponding to that event or task (for example, a change in power level for
one of the attached devices). The e-mail alert can notify up to 48 recipients
at one time; the Email Alerts screen lets you enter up to 48 e-mail addresses.
Figure 19. E-mail Alerts Screen (Upper Portion) To edit notification e-mail
addresses: 1. On the side-bar menu on the Configuration tab, click Email
Alerts. 2. On the Email Alerts screen, click the Edit button located to the
right of the Mail
IP Address and Domain Name fields. The screen goes into Edit mode, and the
Edit button changes to Save. 3. Enter your mail server IP address and your
domain name in the appropriate fields (this information is available from your
network administrator). 4. Click Save to save the information. 5. Click the
Edit button at the end of the first address row in which you want to enter a
new address or edit the existing one. The Edit button changes to Save (see
figure 20). 6. Enter the e-mail address of the alert recipient in the numbered
box in the Email Address column. 7. In the File Name column, enter the name
(seven characters maximum) of the file containing the alert message. The
message file name must have the extension .eml. NOTE: Due to the seven-
character limit for full file names, it is recommended that
you use numeric file names (for example, 1.eml, 24.eml, and so forth). Numeric
titles reduce the characters in the file name and assist in keeping the alert
files organized. However, alphabetic titles are permitted.
IPL T PCS4 · HTML Configuration and Control 26
8. Click the Save button beside the file name that you entered. The e-mail
alert information is saved on the PCS4, and the Save button becomes Edit
again.
9. Repeat steps 5 through 8 for each e-mail recipient address that you want
to add or edit.
Upgrading firmware The Firmware Upgrade screen lets you browse to locate and
upload a new version of firmware for your unit. The uploaded file must have
the file extension .S19. NOTE: The PCS4 .S19 file is not the same as the .S19
files of other products and is not
interchangeable with the firmware upgrade files of any other product.
Figure 20. Firmware Upgrade Screen To upload a new version of firmware: 1. On
the side-bar menu of the Configuration tab, click Firmware Upgrade. The
Firmware Upgrade screen is displayed, showing the version of firmware that is
currently loaded. 2. Click Browse to open a Windows file selection window. 3.
On the file selection window, locate the new firmware version file on your
server and double-click it. (Firmware files must have the extension .S19.) The
firmware file name and path are displayed in the Current Firmware Version
section on the Firmware Upgrade screen. 4. Click Upload. When the firmware
upgrade is complete, the Power LED on the unit blinks three times. NOTE: If
you attempt to upload a file with an extension other than .S19, the PCS4
recognizes it as invalid and ignores it, reverting to the factory installed
firmware version.
Managing receptacles On the Switching/Grouping screen, you can switch power on
and off to each individual receptacle, group the receptacles together, and
power each group on and off. You can also view the threshold settings (Full,
Standby, None, or Not Set) indicating the device power level at which the
alarm relay will be activated for each receptacle. NOTE: You cannot set the
reference thresholds on this screen. This can be done
only from the IPL T PCS4 front panel or via SIS commands. See Setting Power
Level Reference Thresholds on page 9 or SIS Programming and Control on page 42
for information on setting thresholds from the front panel or via SIS
commands.
IPL T PCS4 · HTML Configuration and Control 27
Figure 21. Switching/Grouping Screen
Switching power to receptacles on and off To turn power to receptacles on and
off: 1. On the Configuration tab, select Switching/Grouping from the side-bar
menu. 2. In the Power column, select the On or Off radio button beside the
number of each
receptacle that you want to switch. If you want to switch a group of
receptacles, select On or Off for one of the receptacles in that group (see
Grouping receptacles, below). 3. Click Submit to put your changes into effect.
NOTE: If you turn power on by pressing the receptacle button on the front
panel
while this screen is displayed, the screen does not change to reflect your
actions until you click Refresh.
Grouping receptacles You may want to group two or more receptacles together to
ensure that they are switched on or off at the same time. You can create up to
three groups. To group receptacles: 1. Locate the number of the first
receptacle that you want to group. 2. In the Group Number column, select the
radio button for the group number (1, 2, or 3)
to which you want to assign the receptacle. 3. Repeat steps 1 and 2 for the
rest of the receptacles that you want to group with the first
one. 4. When you have made all desired grouping selections, click Submit.
NOTE: After receptacles have been grouped, any power selection that you make
for one of the grouped receptacles is also performed on the others in that
group when you click Submit.
If you do not want to group a receptacle with any others, select None for it.
IPL T PCS4 · HTML Configuration and Control 28
Monitoring the receptacles and setting the alarm The Monitor screen on the
Configuration tab lets you monitor each receptacle for any change in its power
or its reference threshold condition (full or standby power). You can also
configure the alarm relay and set up the alarm to sound, send an e-mail
notification, or both if any condition at a receptacle changes. This screen is
updated continually. In addition, you can update it by clicking Refresh.
Refresh also removes any settings that have been entered but have not been
submitted, and returns the entire screen to the settings that were saved
previously.
Figure 22. Monitor Screen To set up receptacle monitoring and configure the
alarm, follow these steps: 1. On the side-bar menu on the Configuration tab,
click Monitor. 2. In the Monitoring Settings, the Alarm Relay Settings
section, or both, enter your
selections (described in the following sections). 3. When you are finished
making selections in one section, click the Submit button at the
bottom of the section to implement your changes. If you want to undo all the
entries you made in this section, click Cancel instead of Submit. Monitoring
Settings section In this section, you can specify the following settings for
each receptacle by making selections in the row beside its number. · Enable:
Select the check box in this column to initiate monitoring of the receptacle.
If this box is not checked, all the other fields in the row are unavailable
for selection. · Condition: From the pull-down menu, select the condition that
will be monitored. Options include receptacle or device power on or off; Full,
Standby, or None power threshold levels; or any change in conditions at the
receptacle. · Send E-mail: Enter an e-mail address to which the PCS4 will send
a preconfigured notification if the selected condition is met.
IPL T PCS4 · HTML Configuration and Control 29
· Activate Relay: Select this check box to specify that the relay alarm will
sound (activate) if the selected condition is met. If this box is not
selected, any changes you make to the alarm relay settings are ignored.
· Alarm status: Indicates whether or not the PCS4 has detected the condition
that is being monitored. This column can display the following: · Inactive —
Appears when the receptacle is not being monitored, or the condition being
monitored has not been detected. · Active — Appears in red when the PCS4
detects the condition for which the receptacle is being monitored. In
addition, a Silence button appears at the right of the status, and a pulsing
red light icon appears by the number of the receptacle for which the condition
was met. · Silenced — Appears in red when you click the Silence button to
clear the monitored condition. In addition, the pulsing red light icon is
replaced by an exclamation point icon (!). To reset the alarm status, deselect
and reselect the Enable check box for the receptacle being monitored, then
click Submit. The Alarm Status column displays inactive again and the ! icon
is removed.
Alarm Relay Settings section In this section, you can configure the alarm
relay by making selections in the following fields. NOTE: The Activate Relay
check box must be selected for these settings to take
effect.
· Initial State: Select Open or Closed from the pull-down menu for the initial
state of the alarm relay. (The default is Open.)
· Action: From the pull-down menu, select the way in which the alarm will
respond when activated. This depends on the relay setting in the Initial State
column. · Activate — Steady tone if the initial state of the relay is set to
On. If the initial state is set to Off, this option turns the alarm relay off.
· Pulse — Alarm turns on for the selected duration of seconds, then stops. ·
Oscillate — The alarm is on for a specified duration of seconds, then off for
a specified period, producing an intermittent tone.
· Duration (seconds): From the pull-down menus, select the length (in seconds)
of the alarm tone action selected in the Action section (Pulse or Oscillate
only). · For Pulse, you can set the length of the single tone (On menu). · For
Oscillate, you can set the length of the repeating tone (On menu) and the
amount of time between tones (Off menu).
· Cancel Alarm when: From one of the following menus, select the condition
that will stop the alarm tone. · Condition Changes — Select the type of change
in conditions that will make the alarm stop sounding. (Selecting Manual
specifies that the tone will not stop without user intervention via the front
panel, the powered device, or SIS commands.) · Duration — Select the number of
minutes the alarm will continue to sound before it shuts off.
IPL T PCS4 · HTML Configuration and Control 30
Scheduling power to receptacles The Schedule screen on the Configuration tab
lets you schedule when power to the receptacles is turned on and off. You can
schedule receptacles individually to turn on or off at desired times, or you
can select a group of receptacles to turn on or off at one time. Clicking the
Clear Schedule button deletes all schedules. You may want to set up your
schedule for a week at a time, or a day at a time. To access the Schedule
screen, click Schedule on the side-bar menu on the Configuration screen.
Figure 23. Schedule Screen Showing Fields for Individual Receptacle Scheduling
Scheduling an individual receptacle To schedule power on and off to an
individual receptacle, follow these steps: 1. Locate the number of the
receptacle that you want to schedule, and click On or Off
in the Power column beside it. A Set Schedule For section opens, displaying
the selected receptacle number, the power selection (On or Off), and menus
from which to select the hour, minute, and AM or PM. (figure 24 shows the
Schedule screen with a Set Schedule For section displayed for receptacle 2,
with power on at 1:00 pm Monday and Thursday.) 2. From the pull-down menus,
select the time (hour and minutes and AM or PM) at which you want power turned
on or off to the selected receptacle. 3. Select the check boxes for the days
of the week you want the receptacle to be turned on, off, or both at the time
you specified. 4. When finished, click Set to save your settings for that
receptacle. 5. Repeat steps 1 through 4 for the remaining power schedule
setting for the receptacle you just scheduled, or for other receptacles that
you want to schedule.
IPL T PCS4 · HTML Configuration and Control 31
Scheduling receptacles by day of the week There are two types of schedules
that you can set up for one day of the week. The two setup procedures are
described below. All receptacles on and off: Follow this procedure to select
both the powering on and powering off times for all desired receptacles on one
day of the week. 1. Click on a day of the week at the top of a column in the
scheduling table. Two Set
Schedule For sections open, one for Power On and one for Power Off. These
sections contain pull-down menus for selecting powering on and off times as
well as check boxes for selecting the receptacles you want to schedule.
Figure 24. Schedule Screen Showing Fields for Daily Receptacle Scheduling 2.
In either the Power On or Off section, select the hours, minutes, and AM or PM
from the
menus; and select the check boxes for the receptacles that you want to
schedule. 3. In the section in which you made your selections, click Set to
enter your choices. The
section closes. 4. If desired, repeat steps 2 and 3 in the other Set Schedule
For section.
If you do not want to make selections in the remaining Set Schedule For
section, click Refresh to close the section. NOTE: If you do not click Set
before making any selections in the other field, the
second field selections override those that you entered in the first. 5.
Repeat steps 1 through 4 for any additional days that you want to schedule.
IPL T PCS4 · HTML Configuration and Control 32
One receptacle, power on or off: Follow this procedure if you want to schedule
only powering on or powering off of only one receptacle on one day. 1. In the
scheduling table, click on the time displayed or the – symbol in the cell
beside
On or Off for the receptacle number that you want to set, in the column for
the day you want to schedule. A Set Schedule For section appears. In the
following illustration, the red box indicates the cell that was selected:
receptacle 2, powering off, on Tuesday.
Figure 25. Set Schedule For Field to Set Powering Off for a Single Receptacle
2. In the Set Schedule For section, select the hour, minutes, and AM or PM
from the
drop-down menus. 3. Click Set to enter your settings. The time that you
entered appears in the cell that you
selected on the Scheduling table.
File Management
The File Management web page allows you to upload and delete files from the
server. File names must contain valid alphanumeric characters and underscores;
spaces and special characters (symbols) are not allowed. Only personnel with
administrator access can view these pages and make changes.
Figure 26. File Management Screen with Two Files Uploaded IPL T PCS4 · HTML
Configuration and Control 33
Uploading files to the web page The IPL T PCS4 has approximately 900 KB of
space for user files to be uploaded. The Bytes Left field shows how much space
remains for uploading files. To upload files: 1. Select the File Management
tab on the IPL T PCS4 web page. 2. On the File Management screen, click Browse
to open a Windows file selection window. 3. On the file selection window,
locate and select a file to upload. (Only one file at a time
can be selected.) The file name and directory path appear in the Browse field
on the File Management screen. 4. Click Upload File while the file is
uploading, the button label changes to Uploading… . When the uploading is
complete, the uploaded file name appears in the Files list with a time stamp
showing GMT time, and the button returns to its original state. (Files are
listed separately under headings of their extensions.)
Adding a directory To add a directory or folder to the IPL T PCS4 file system:
- Enter a name for the directory in the Dir: field, following the slash (/).
- Click Add Dir. 3. With the directory name displayed, perform the uploading
files procedure described in
the previous section to add a file to the directory. The directory name appears at the top of the Files column, preceded by a slash (/). If no files are added to the new directory, it is deleted. To add more files to the directory, click the directory name to open it, then use the uploading files procedure. To exit the directory, click (root).
Other file management functions On the File Management screen, you can also do the following: · Open and view an uploaded file by clicking on its name. · Delete an uploaded file by clicking the Delete button beside it. · Delete all uploaded files and directories by clicking the Delete All button.
Custom Web Pages
On the PCS4, custom web pages are supported. You can determine the layout and appearance of the pages displayed on your screen. Server side includes (SSIs) enable you to obtain information from the unit and display the information on web pages. Query strings allow you to send information and commands to the unit to change its configuration or provide you with feedback (see Query Strings on page 35).
Server Side Includes (SSIs)
Server sides includes are a type of HTML comment that directs the web server to dynamically generate data for a web page whenever it is requested. SSIs typically use SIS commands to communicate with the products or attached control devices. Using SSIs, you can design and display custom pages, with PCS4 information provided by the SIS commands.
IPL T PCS4 · HTML Configuration and Control 34
The basic format for an Extron SSI is:
<!–#echo var=x–> where x is the SIS command to be executed.
When a web page is requested, the web server removes the SSI and replaces it
with the answer to the SIS command within quotes.
Server Side Include Using the Host SIS command
SIS Command
<!–#echo var=”
N
“–>
*Type with no spaces
SIS command to be processed
by the IP Link
Figure 27. Example of SSI Command
In the figure 28, the N command is used to request the PCS4 part number.
Query Strings
A query string is the portion of a URL that appears after the question mark.
The query string contains parameters or instructions for the web server to
execute. The basic format for a query string within a link is:
<a href=index.html?cmd=x>Receptacle 1
where x is the SIS command to be executed.
When a link is accessed on a web page, the URL is passed to the web server to
tell it which web page to return to the browser. The portion of the URL after
the question mark is the query string, which contains the SIS command that the
IPL T PCS4 will remove and execute.
Like SSI formatted commands, query strings can use any valid SIS command.
The query string in figure 29 turns off DHCP on the IP Link device. URL with a
Query String Using an SIS Command
SIS Command
<a href=”index.html
? cmd=
HTML Code for a Link
Starts query string.
Tells web server that SIS
command follows.
W1*1PC|
“> Receptacle on
SIS Command To Be Processed
by the IP Link
HTML Code for a Link
Linked Text
Closes link.
Figure 28. Example of a Query String Command
*Enter with no spaces.
IPL T PCS4 · HTML Configuration and Control 35
Code example
Figure 30 shows a practical use for both SSIs and query strings. In this
example, the HTML source code contains three SSI commands.
HTML Example #1
The following lines demonstrate how to read status from the IPLink Product:
IPLink Product Name: <!–#echo var=”1I”–>
SSI
IPLink Product Description: <!–#echo var=”2I”–>
commands
IPLink Product Part Number: <!–#echo var=”N”–>
Figure 29. Web Page HTML Source Code Document Showing SSIs
The SSI commands in figure 31 request the product name, product description, and product part number of an IP Link device.
HTML Example #1
The following lines demonstrate how to read status from the IPLink Product: IPLink Product Name: IPL T PCS4IPLink Product Description: Four Switched 110v AC Receptacles with Current Threshold Sensing
IPLink Product Part Number: 60-544-07 Figure 30. Resulting HTML Source Code Served by an IP Link web Server In figure 32 the commands executed by the PCS4 in response to SSI references have been replied to, and were implemented when the web page was served to the browser.
Figure 31. Browser View of Previous HTML Source Code IPL T PCS4 · HTML Configuration and Control 36
URL Encoding
URL (Universal Resource Locator) encoding is a method of using ASCII
hexadecimal characters to display specific characters in a URL. It is used for
several reasons. On some operating systems, certain characters are unsafe or
not available, and others are reserved by the HTML or URL specification. URL
encoding is used to insure compatibility and functionality with most Internet
browsers. As a general rule, use the hexadecimal encoding method shown below
when these characters appear in your URLs.
The following types of characters do not require encoding in a URL:
Alphanumerics
0-9 a-z A-Z
Special characters
$ . + ! * ( ) ,
Reserved characters
; / ? : @ = &
When used for their reserved purposes, these characters do not require
encoding within a URL.
Figure 32. Characters that Do Not Require Encoding
Reserved characters
Reserved characters should not be encoded when they appear in their
conventional meaning in a URL. For example, do not encode the slash (/) when
using it as part of the URL syntax. Only encode unsafe characters (defined in
the table in the next section) in your URLs.
The following table lists reserved characters.
Characters $ Dollar & Ampersand + Plus , Comma / Forward slash (virgule) : Colon ; Semi-colon = Equal ? Question mark @ At symbol
Hex Dec 24 36 26 38 2B 43 2C 44 2F 47 3A 58 3B 59 3D 61 3F 63 4O 64
Figure 33. Reserved Characters
IPL T PCS4 · HTML Configuration and Control 37
Unsafe characters
URLs use some characters for special use in defining their syntax and these characters should be encoded. For various reasons, these characters may possibly be misunderstood within a URL. The following table lists unsafe characters.
Characters Space Quotation marks
< Less than symbol > More than symbol # Pound % Percent { Left brace } Right brace | Vertical bar (pipe) Backslash ^ Caret ~ Tilde [ Left square bracket ] Right square bracket ` Grave accentHex Dec 20 32 22 34 3C 60 3E 62 23 35 25 37 7B 123 7D 125 7C 124 5C 92 5E 94 7E 126 5B 91 5D 93 60 96
Figure 34. Unsafe Characters
A/V Device Power Control
Power control of A/V devices may be accomplished once the PCS4 interface has
been connected and configured. These include web pages and Telnet.
Custom Web Pages
These pages can either be modified versions of the existing web pages, or new
web pages developed in the field.
Web page development can be done with a web site development tool such as
FrontPage or Dreamweaver. Custom web pages can be loaded using the embedded
File Management web page (see File Management on page 33).
IPL T PCS4 · HTML Configuration and Control 38
Accessing and Using Telnet (Port 23)
Telnet, short for Telecommunications Network, provides a way for you to
connect to a computer or server (in this case, the PCS4 interface) on a
network. Once connected via Telnet, you can send ASCII serial commands to
configure and monitor the PCS4 settings (see Command and Response Table for
SIS Commands on page 45) . 1. Click Start, then Run, then enter Telnet, and
click OK. The Telnet program starts (see
figure 35 on page 39).
Figure 35. Telnet Command Prompt 2. At the command prompt, enter open. 3. At
the
192.168.254.254. If the address was changed in the setup or configuration
process, use the new address.) Telnet defaults to port 23.
Figure 36. Connecting to the IP Address 4. If passwords were set up for the
connected system, you are prompted to log in as an
administrator or a user. Otherwise, the system responds with a carriage return
and line feed (<cr/lf>). NOTE: The factory configured passwords for all
accounts on this device have been
set to the device serial number. In the event of an absolute system reset, the
passwords convert to the default, which is extron. 5. Once you are connected,
you can enter SIS commands as desired. 6. When you are finished entering
commands to the interface, press < Ctrl + ] > at the command prompt to exit
Telnet.
IPL T PCS4 · HTML Configuration and Control 39
Troubleshooting
Turn on the equipment in the following order: 1. The PCS4 power control
interface 2. The power receptacles on the PCS4 3. The connected output devices
If the output A/V device cannot be powered on, check the following:
Power Connections
1. Make sure that the receptacle for each device is receiving power. The red
Power LED of the receptacle lights if the receptacle is powered on. If
necessary, press the receptacle button to apply power.
2. Ensure that all devices are plugged in properly to the rear panel of the
PCS4 and switched on if applicable.
Network Connections
1. Check the network connections and make adjustments as needed. The Link LED
is solid green if a network connection is detected. The yellow ACT LED blinks
if there is activity on the network. If these LEDs are not lit, either the
cable is faulty or not plugged in, or the wrong type of cable is being used
(see Connecting the Devices on page 7).
2. At the DOS command prompt, try to ping the unit by entering ping and the
IP address assigned to your PCS4 (see Setting Up the Computer Using ARP on
page 16). If the PCS4 is connected, you receive the following response to your
Ping command:
Figure 37. Successful Ping Command Response
IPL T PCS4 · HTML Configuration and Control 40
If the connection was not made, the following response appears:
Figure 38. Response to an Unsuccessful Ping Command If you get a response
indicating that the ping was unsuccessful, do the following: · Make sure your
unit is using the appropriate subnet mask (check with your system
administrator). · Make sure your computer does not have a software firewall
program which might
block the IP address of the unit. 3. If contact is established with the unit,
but the unit web pages cannot be accessed by
your web browser, verify (in the Options or Preferences menu) that your web
browser is configured for direct network connection and not set up to use a
proxy server. If you are still experiencing problems, contact the Extron S3
Sales & Technical Support Hotline (see Extron Warranty on page 60).
Downloading Global Configurator Software
The Global Configurator (GC) software is an alternative to using the web pages
to configure and monitor the PCS4. GC is a free asset management software that
enables flexible, centralized, web-based power management for A/V systems.
Using Global Configurator software, administrators can view the immediate
status and power levels of all connected devices, schedule powering on and off
of the devices, and configure the alarm triggers. You can download the latest
version of Global Configurator from the Extron website (www.extron.com) as
follows: 1. Select the Products tab on the Extron website home page. 2. From
the sidebar menu at the left of the screen, select Software. 3. On the
software products page, click Control Software. 4. On the Control Software
page, scroll to locate Global Configurator and click the
Download link at right. A login screen appears 5. On the login screen, enter
your e-mail address and password.
If you do not have a password, click the click here link and fill in the
requested information to obtain a password. When you receive your password,
proceed to step 6. 6. On the Download Center screen, fill in the requested
information and click Download GVConfigInstallvn.exe. Follow the instructions
on the subsequent screens to complete the download.
IPL T PCS4 · HTML Configuration and Control 41
SIS Programming and Control
This section provides instructions on using the Extron Simple Instruction Set (SIS) commands, which you can use to set up and control the IPL T PCS4 from a host computer or other control system attached to the rear panel LAN port. The following topics are discussed:
· Host-to-Interface Communication
· Using the Command and Response Table
· Command and Response Table for SIS Commands
As shipped, the PCS4 works as a standalone interface, but cannot control any other devices until it is configured. You can set up and control the PCS4 by using the front panel, the web pages, or SIS commands. Both the web pages and the SIS methods are accessed via Ethernet LAN connection. The LAN port defaults are:
IPL T PCS4 IP address:
192.168.254.254
Gateway IP address:
0.0.0.0
Subnet mask:
255.255.0.0
DHCP:
Off
Host-to-Interface Communication
SIS commands consist of one or more characters per field. No special
characters are required to begin or end a command sequence. When the PCS4
determines that a command is valid, it executes the command and sends a
response to the host device. All responses from the interface to the host end
with a carriage return and a line feed (CR/ LF = ]), which signals the end of
the response character string. (A string is one or more characters.)
Messages Initiated by the IPL T PCS4
When a local event such as a front panel selection or adjustment takes place,
the PCS4 responds by sending a message to the host. No response is required
from the host. The following PCS4-initiated messages are sent (underlined):
© Copyright 20nn, Extron Electronics, IPL T PCS4 [or -PCS4i], Vn.nn, 60-544-nn
] Www, DD Mmm 2011 HH:MM:SS] The PCS4 sends the boot and copyright messages
when it first powers on and is connected via Telnet or TCP/IP. Vn.nn is the
firmware version number; 60-544-nn is the product part number. The current
date and time are displayed. If you are using a Telnet connection, the
copyright message, date, and time are followed by a password prompt.
IPL T PCS4 · SIS Programming and Control 42
Password Information
NOTE: The factory configured passwords for all accounts on this device have
been set to the device serial number. In the event of an absolute system
reset, the passwords convert to the default, which is extron.
The ] Password: prompt is displayed only if there is a password defined in the
unit. It requires a password (administrator level or user level) followed by a
carriage return. The prompt is repeated if the correct password is not
entered. If the correct password is entered, the unit responds with ] Login
Administrator ] or ] Login User ], depending on the password entered. If the
passwords are the same for both administrator and user, the unit defaults to
administrator privileges.
Error Responses
When the PCS4 receives a valid SIS command, it executes the command and sends
a response to the host device. If the PCS4 is unable to execute the command
because the command is invalid or it contains invalid parameters, it returns
an error response to the host. The error response codes and their descriptions
are as follows: E12 Invalid port number E13 Invalid value (the number is
out of range/too large) E14 Not valid for this configuration E17 System
timed out E22 Busy E24 Privilege violation E25 Device is not present E26
Maximum number of connections has been exceeded E27 Invalid event number
E28 Bad filename or file not found
Error Response References
The following superscripted numbers are used within the command descriptions
in the Command and Response table to identify commands that may respond as
shown: 14 Commands that give an E14 (invalid command for this configuration)
response if
sent to an IPL product whose power configuration does not support the command
24 Commands that give an E24 (privilege violation) response if you are not
logged in at
the administrator level 27 Commands that may yield an E27 (invalid event
number) response 28 Commands that may give an E28 (file not found) response
IPL T PCS4 · SIS Programming and Control 43
Using the Command and Response Table
The PCS4 can be controlled via either a Telnet connection (port 23) or a web
browser connection (port 80). The ASCII commands listed in the tables perform
the same functions, but they are encoded differently to meet the requirements
of each port (Telnet or browser). The ASCII to hexadecimal (HEX) conversion
table below is for use with the command and response tables.
Figure 39. ASCII to Hex Conversion Table
The command and response table lists valid ASCII (for Telnet) command codes, the corresponding URL (universal resource locator) encoded (for web browsers) command codes, the interface responses to the host, and a description of the command function or the results of executing the command.
· Upper- and lowercase characters can be used interchangeably in the command field unless otherwise specified.
· Commands may be sent back-to-back without spaces (for example, 2!65V1Z).
· Numbers can be entered as 1, 2, or 3 digits (for example, 8V = 08V = 008V).
· There are a few differences in how to enter the commands, depending on whether you are using Telnet or a web browser.
· When using these commands through a web browser, you can use the URL reference to shorten the examples. URL refers to the full address of the control interface and web page reference, including all path information (that is, http://192.168.100.10/myform.htm).
· To send any of the commands using a web browser you must prefix them with the full URL followed by ?cmd=.
· For control via a web browser, all non-alphanumeric characters must be represented as the hexadecimal equivalent, %xx, where xx represents the twocharacter hex byte. For example, a comma (,) would be represented as %2C. Characters such as %, +, and the space character must be encoded as hex bytes, or they will be misinterpreted by the interface.
· Some characters differ depending on the method you use to send the commands:
Telnet
Web Browser
Escape (hex 1B) Carriage return (hex 0D)
W (must not be hex encoded) Pipe character (|) (must not be hex encoded)
IPL T PCS4 · SIS Programming and Control 44
NOTES:
· With Telnet you can use either an Escape command or a W command, and the
carriage return or the pipe character. With the web browser, you are required
to use a W command and the pipe character.
· In either method, Data = Data that will be directed to a specified port and
must be hex encoded if non-alphanumeric.
Common Symbol Definitions
Common Symbol Definitions
] = Carriage return with line feed (hex 0D 0A)
} or ¦ = Carriage return or pipe symbol (no line feed, hex 0D)
} = Carriage return with no line feed (no line feed, hex 0D) (for URL-encoded commands, use the pipe character, | , instead)
E = Escape key, or hex 1B (use W instead of E for web browsers, or at any time)
|
= Pipe (vertical bar) character (URL equivalent to carriage return)
·
= Space
= Asterisk character (which is a command character, not a variable)
Command and Response Table for SIS Commands
Command
ASCII (Telnet) (Host to Switcher)
URL Encoded (Web) (Host to Switcher)
Response (Switcher to Host)
Power Receptacle Control / Current Sense
Turn receptacle power on
E X!*1PC}
Turn receptacle power off
E X!*0PC}
View receptacle power status View receptacle current status Group receptacles Ungroup receptacles View receptacles grouping Set power up delay
E X! PC} E X! PS} E X1)1 X1)2 X1)3 X1)4 GP} E 0000GP} E GP} E X1^ DT}
View power up delay
E DT}
Set individual full threshold Set individual standby threshold
E X!2TH} E X!1TH}
Clear individual threshold
E X!*0TH}
View threshold setting for all E TH} ports
W X! %2A 1PC| W X! %2A 0PC| W X! PC| W X! PS| W X1)1 X1)2 X1)3 X1)4 GP| W
0000GP| W GP| W X1^ DT| W DT| W X! %2A 2TH| W X! %2A 1TH|
W X! %2A 0TH| W TH|
Cpn X!·Ppc1] Cpn X!·Ppc0] X% ] X( ] Pgp X1)1 X1)2 X1)3 X1)4 ] Pgp0000] X1)1 X1)2 X1)3 X1)4 ] Pdt X1^ ] X1^ ] Ptf X! ] Pts X! ] Ptc X! ] X(1,X(2,X(3,X(4 ]
KEY:
X! = Port Receptacle
1 – 4
X% = On or Off status
0 = off or disabled
1 = on or enabled
X( = Current threshold sense
0 = clear or none 1 = standby
2 = full (Full threshold must be set before standby.)
X1) = Group number
0 = none
1 = yellow 2 = green
3 = red
The exponent designates the port number. The color relates to setting groups via the front panel.
X1^ = Power-up delay between ports in 1/3-second increments. 1-255 permitted. Default = 3, which equals 1 second.
IPL T PCS4 · SIS Programming and Control 45
Command
ASCII (Telnet) (Host to Switcher)
URL Encoded (Web) (Host to Switcher)
Response (Switcher to Host)
Power Receptacle Control / Current Sense (continued)
Set Executive mode on
1X
1X
Set Executive mode off
0X
0X
View Executive mode
X
X
Exe1] Exe0] X% ]
Power Receptacle Monitoring and Alarm Functions
Set alarm conditions
E X!X70!X70@*X70# SA}
W X! %2A X70! %2A X70@ %2A X70# SA|
View alarm conditions Monitoring enable or disable Set Alarm mode
View Alarm mode
Ast X!X70!X70@X70#X70$*X70% ]
E X!SA}
W X! SA|
X70!X70@X70#X70$X70% ]
E X!*X70$ SA}
W X! %2A X70$ SA|
Ast X!X70!X70@X70#X70$*X70% ]
E X70^X70&X70X70X71) MA}
W X70^ %2A X70& %2A X70 %2A X70 %2A X71) MA|
Arl X70^X70&X70X70X71) ]
E MA }
WMA|
X70^X70&X70X70X71) ]
KEY:
X!
= Port Receptacle
1 – 4
X% = On or Off status
0 = off or disabled
1 = on or enabled
X70! X70@
= Condition that is monitored
= Use alarm relay
0 = receptacle off 1 = receptacle on
0 = no or disable
2 = reference: None 3 = reference: Standby
1 = yes or enable
4 = reference: Full 5 = any change
X70# = E-mail to use
61-64
X70$ = Enable and disable monitoring
0 = disable monitoring
1 = enable monitoring
2 = enable with e-mail
X70% = Alarm status
0 = inactive
1 = active
2 = silenced
X70^ = Clear value X70& = Relay polarity
0 = condition no longer met 1 = clear with output off 2 = clear with output on
0 = normally open
3 = clear with no threshold 4 = clear with standby threshold 5 = clear with
full threshold
1 = normally closed
6 = clear with any change 7 = manual
X70* X71)
= Time to hold alarm active before canceling
= Off timed value
0 = never times out
1-7 = 1 to 7 minutes
00-15 (in 250 ms increments)
Power Receptacle Scheduling
Set scheduling View scheduling
E X!X71!X%X71@ SS} E X!X71!*X% SS}
W X! %2A X71! %2A X% %2A X71@ SS W X! %2A X71! %2A X% SS|
Set X!X71!X%*X71@ ] X71@ ]
KEY:
X! = Port Receptacle 1 – 4
X% = On or Off status 0 = off or disabled
1 = on or enabled
X71! = Day of the week 1 = Sunday
2 = Monday
3 = Tuesday 4 = Wednesday
5 = Thursday 6 = Friday
7 = Saturday
X71@ = Time in minutes 0 = 00:00 am (midnight) 1440 = clear schedule
(0-1440)
Example: 1439 = 11:59 Use the following formula (in 24-hour time format): (hour x 60) + minutes = time in minutes
IPL T PCS4 · SIS Programming and Control 46
Command
Alarm Relay Functions Turn alarm relay ON Turn alarm relay OFF View alarm
relay state Pulse relay
ASCII (Telnet) (Host to Switcher)
11O} 10O} 1O} 13X6# O}
URL Encoded (Web) (Host to Switcher)
1 %2A 1O| 1 %2A 0O| 1O| 1 %2A 3 %2A X6# O|
Toggle relay
1*2O }
Ethernet Data Port Commands
Set current connected port timeout View current connected port timeout Set global IP port timeout View global IP port timeout
E 0X6( TC} E 0TC}
E 1X6( TC} E 1TC}
W0 %2A X6( TC| W0TC|
W1 %2A X6( TC| W1TC|
Firmware Version, Part Number, and Information Requests
Response (Switcher to Host)
Cpn1·Rly1] Cpn1·Rly0] X% ] Cpn1·Rly1] or Cpn1·Rly0] Cpn1·Rly1] or Cpn1·Rly0]
Pti0X6( ] X6( ] Pti1X6( ] X6( ]
NOTE: An asterisk (*) after a version number indicates the version that is
currently running. Question marks (?.??) indicate that only the factory
firmware version is loaded. A caret (^) indicates the firmware version that
should be running; however, a mode 1 reset was executed and the factory
default firmware version is currently loaded. An exclamation point (!)
indicates corrupted firmware.
Query firmware version
Q
Q
Query firmware information 1Q
1Q
Query bootstrap version
2Q
2Q
Query factory firmware version 3Q
3Q
Query updated firmware
4Q
4Q
version
Query verbose version
0Q
0Q
information
Request interface part number N
N
Request model name
1I
1I
Request model description 2I
2I
Request system memory
3I
3I
usage
Request user memory usage 4I
4I
X1! ] X1! ] X1! ] X1! plus (web version model UL date and time) ] X1! plus (web version model UL date and time) ] Sum of responses from 2Q, 3Q, and 4Q ] 60-544-07 or 60-544-09] IPL T PCS4 or IPL T PCS4i] Lists four switched 110 VAC or 220 VAC receptacles with current threshold sensing.] Number of bytes and Kbytes used out of the number of total Kbytes] Number of bytes and Kbytes used out of the number of total Kbytes]
KEY:
X1! = Version (typically listed to two decimal places, that is, n.nn)
X% = On or Off status
0 = off or disabled
1 = on or enabled
X6# = Pulse time in 20 ms If this parameter is missing or = 0, then pulse
length = default (25 = 500 ms). 35565 ms = max. pulse time.
per count
X6( = (Ethernet only) Number of seconds before timeout on IP connections (min.
= 1, max. = 6500, and default = 30 = 300 seconds).
If no data is received during the timeout period, the Ethernet connection is
closed. Each step is 10 seconds. The response is returned with leading zeros.
IPL T PCS4 · SIS Programming and Control 47
Command
ASCII (Telnet) (Host to Switcher)
URL Encoded (Web) (Host to Switcher)
Response (Switcher to Host)
E-mail Commands
Configure e-mail events (mailbox)24 Example:
E X4%,X4^,X4& CR}
W X4% %2C X4^ %2C X4& CR|
E 5,jdoe@extron.com,7.emlCR}
Ipr X4%,X4^,X4& ]
W5%2Cjdoe%40extron%2Ecom%2C7%2EemlCR|
Ipr5,jdoe@extron.com,7.eml]
View e-mail events (mailbox) E X4% CR}
W X4% CR|
X4^,X4& ]
Send e-mail events (file named E X4% SM} in mailbox)24
W X4% SM|
Eml X4^ ]
Send e-mail (using different file)24
E X4%,X7),X4& SM}
W X4% %2C X7) %2C X4& SM|
Eml X4^ ]
Web Browser-specific Commands
Read response from last URL E UB} cmd
Mail Server Setup Commands
W UB|
Response from command]
Set mail server IP, unit domain name24 View mail server IP, unit domain name
IP Setup Commands
E X1$,X1% CM} E CM}
W X1$ %2C X1% CM| W CM|
Ipm·X1$,X1% ] X1$,X1% ]
Set the unit name24 Set unit name to factory default24 View unit name24 Set date and time24
E X1@ CN} E·CN}
E CN} E X1# CT}
W X1@ CN| W %20 CN|
Ipn·X1@ ] Ipn·X4( ] X1@ ] Ipn·X1# ] Example: 11/16/10-10:54:00 ]
KEY:
X1@ = Unit name. The name of the PCS4 is a text string of up to 24 characters
drawn from the alphabet (A-Z), digits (0-9), and minus sign or
hyphen (-). No blank or space characters are permitted as part of a name. No
distinction is made between upper and lower case.
NOTE: The first character must be a letter. The last character must not be a minus sign or hyphen (-).
X1# = Local date and time format Set format (MM/DD/YY-HH:MM:SS). Example:
11/18/03-10:54:00.
Read format (day of week, day month year HH:MM:SS). Example: Tue, 18 Nov 2011
18:19:33.
X1$ = IP address
(nnn.nnn.nnn.nnn)
Leading zeros in each of four fields are optional in setting values, and they are suppressed in returned values.
X1% = E-mail domain name (for example: extron.com)
X4% = E-mail event number
(1 – 64)
X4^ = E-mail recipient address (for example, JDoe@extron.com) for the person to whom messages will be sent.
X4& = Name (numeral) of e-mail file to be sent; for example: 1.eml, 2.eml, … 64.eml
X7) = The number (as an optional parameter) that is inserted into the e-mail
message if the .eml file has an embedded command (with no
parameters).
IPL T PCS4 · SIS Programming and Control 48
Command
ASCII (Telnet) (Host to Switcher)
IP Setup Commands (continued)
View date and time
E CT}
Set GMT offset24 View GMT offset
E X# CZ} E CZ}
Set daylight savings time24 View daylight savings time
E X3$ CX} E CX}
Set DHCP on24 Set DHCP off24 View DHCP mode Set IP address24 View IP address View hardware (MAC) address Set subnet mask24 View subnet mask Set gateway IP address24 View gateway IP address Set verbose mode24
E 1 DH] E 0 DH] E DH] E X1$ CI} E CI} E CH} E X1( CS} E CS} E X1$ CG} E CG} E X2@ CV}
URL Encoded (Web) (Host to Switcher)
W CT|
W X# CZ| W CZ| W X3$ CX| W CX| W 1 DH| W 0 DH| W DH| W X1$ CI| W CI| W CH| W
X1( CS| W CS| W X1$ CG| W CG| W X2@ CV|
Response (Switcher to Host)
X1# ] Example: Tues, 16 NOV 2011 10:10:54:00 ] Ipz X# ] X# ] Ipx X3$ ] X3$ ]
Idh 1] Idh 0] X% ] Ipi· X1$ ] X1$ ] X1* ] Ips· X1( ] X1( ] Ipg·X1$ ] X1$ ] Vrb
X2@ ]
NOTE: The IPL T PCS4 can send out unsolicited information (such as notice of a
power level change). This is called a verbose (wordy) relationship
between the interface and a connected device. When the IPL T PCS4 is connected
to the computer via Ethernet, verbose mode is disabled (by default) in order
to reduce the amount of communication traffic on the network. If you want to
use the verbose mode with the PCS4 connected via Ethernet, this mode must be
set to On each time you reconnect to the network.
View verbose mode status Get connection listing
E CV} E CC}
W CV| W CC|
X2@ ] Number of connections
KEY:
X#
= Greenwich Mean Time (GMT) offset value (-12.00 to +14.00) represents the time difference in hours and minutes (±hh:mm) relative to
Greenwich, England. The plus sign and leading zero are optional. For example, 5:30 = +05:30.)
X% = On or Off status
0 = off or disabled
1 = on or enabled
X1# = Local date and time format Set format (MM/DD/YY-HH:MM:SS).
Example: 11/18/03-10:54:00.
Read format (day of week, day month year HH:MM:SS).
Example: Tue, 18 Nov 2011 18:19:33.
X1$ = IP address
(nnn.nnn.nnn.nnn)
Leading zeros in each of four fields are optional in setting values, and they are suppressed in returned values.
X1* = Hardware (MAC) address (xx-xx-xx-xx-xx-xx).
X1( = Subnet mask (nnn.nnn.nnn.nnn). Leading zeros are optional in setting
values in each of four fields, and they are suppressed in
returned values.
X2@ = Verbose response mode
0 = None (default)
1 = verbose mode
2 = tagged responses to queries
3 = verbose mode and tagged responses to queries
X3$ = Daylight saving time (DST) is a 1-hour offset to reflect the time during
which clocks are set one hour or more ahead of local standard
time, to provide more daylight at the end of the working day. Supported for
the U. S. and parts of Brazil and Europe.
Example: Time in California is GMT -8:00 from March to November and GMT -7:00
from November to March. DST should be turned off in Hawaii, American Samoa,
Guam, Puerto Rico, the Virgin Islands, the eastern time zone portion of the
state of Indiana, and the state of Arizona (excluding the Navajo Nation).
IPL T PCS4 · SIS Programming and Control 49
Command
ASCII (Telnet) (Host to Switcher)
URL Encoded (Web) (Host to Switcher)
Response (Switcher to Host)
Password and Security Settings
NOTE: The factory configured passwords for all accounts on this device have been set to the device serial number. In the event of an absolute system reset, the passwords convert to the default, which is extron.
Set administrator password24
Clear administrator password24
E X3# CA} E·CA}
W X3# CA| W %20 CA|
Ipa·X4! ] Ipa·]
NOTE: A user password cannot be assigned if an administrator password does not
exist. If the administrator password is cleared (removed), the user
password is also removed.
View administrator password24 E CA}
W CA|
X4! ]
Set user password14 24 Clear user password24
E X3# CU} E·CU}
W X3# CU| W %20 CU|
Ipu·X4! ] Ipu·]
View user password24 Query session security level
E CU} E CK}
W CU| W CK|
X4! ] X5@ ]
KEY:
X3# = Password
Minimum length = 4 characters, maximum length = 12 characters. No special characters are allowed.
X4! = Reading password.
Responds with four asterisks (****) in place of the password, if a password exists. For the user password, responds with an empty space if no password exists.
X5@ = Connection security level If this parameter is missing or = 0, then
pulse length = default (25 = 500 ms). 35565 ms = max. pulse time.
11 = user 12 = administrator
Remapping Port Designations
NOTE: Duplicate port number assignments are not permitted, that is, Telnet and
web cannot be the same). Entering duplicate port assignments
results in an E13 (invalid parameter) error message.
Set Telnet port map24 Reset Telnet port map24 Disable Telnet port map24 View
Telnet port map Set web port map24 Reset web port map24 Disable web port map24
View web port map
Directory Commands
Change or create a directory
E port# MT} E 23MT} E 0MT} E MT} E port# MH} E 80MH} E 0MH} E MH}
W port# MT| W 23MT| W 0MT| W MT| W port# MH| W 80MH| W 0MH| W MH|
E path/directory/CJ} W path/directory/CJ|
Pmt port#] Pmt 00023] Pmt 00000] port#] Pmh port#] Pmh 00080 ] Pmh 00000 ] port#] Dir·path/directory/]
NOTE: A directory does not truly exist until a file has been copied into the path.
Move back to root directory Move up one directory
E /CJ} E..CJ}
W %2F CJ| W %2E %2E CJ|
Dir·/]
IPL T PCS4 · SIS Programming and Control 50
Command
ASCII (Telnet) (Host to Switcher)
URL Encoded (Web) (Host to Switcher)
Response (Switcher to Host)
File Erase Commands
Erase user-supplied web page or file24, 28
E filename EF}
Erase current directory and its E /EF} files24, 28
Erase current directory and subdirectories24, 28
E //EF}
W filename EF| W %2F EF|
W %2F %2F EF|
Del·filename] Ddl] Ddl]
File Listing Commands
List files from current directory
E DF}
W DF|
(See below.)
Telnet text responses: filename x · date/time · length] filename x · date/time
· length] filename x · date/time · length] …
space_remaining · Bytes Left] ] Web responses — HTML sample code:
Var file new Array (); File [1] = filename1, date1, filesize1′; File [2] =
filename2, date2, filesize2′;
… File [n] = filename n, date n, filesize n’; File [n+1] =
space remaining,
Bytes left’
List files from current directory E LF} and below
W LF|
(See below.)
Telnet text responses: path/directory/filename x · date/time · length]
path/directory/filename x · date/time · length] path/directory/filename x ·
date/time · length] …
space_remaining · Bytes Left] Web responses — HTML sample code:
Var file new Array (); File [1] = filename1, date1, filesize1′; File [2] =
filename2, date2, filesize2′;
… File [n] = filename n, date n, filesize n’; File [n+1] =
space remaining,
Bytes left’
NOTE: The response to this command is the same as for the List files from current directory command (DF), except that path/directory precedes filenames for files from subdirectories below the current directory.
Stream Files via Port 80
Load file to user flash memory24 28 Retrieve files from user flash memory24 28
Example:
Use a POST on port 80 followed by the delimited data to be written to the flash file memory.
Send a page GET on port 80 followed by WSF| http://192.168.254.254/mypage.html?cmd=WSF
Raw unprocessed data in file
IPL T PCS4 · SIS Programming and Control 51
Command Stream Files via Telnet
ASCII (Telnet) (Host to Switcher)
URL Encoded (Web) (Host to Switcher)
Response (Switcher to Host)
Load file to user memory24 28 E + UF filesize, filename}
Raw unprocessed data in file up to file size
Retrieve file from user flash memory24 28
E filename SF}
Reset (Zap) and Erase Commands
Erase the user flash memory24 (files only) Reset all device settings to factory default24 Absolute system reset24
E ZFFF} E ZXXX} E ZQQQ}
1B filename SF 0D
W ZFFF| W ZXXX| W ZQQQ|
Upl] Four bytes of file size + raw unprocessed data in file
Zpf] Zpx] Zpq]
NOTE: The factory configured passwords for all accounts on this device have been set to the device serial number. In the event of an absolute system reset, the passwords convert to the default, which is extron.
IPL T PCS4 · SIS Programming and Control 52
Mounting Instructions
This section contains the mounting information for the IPL T PCS4 and IPL T
PCS4i.
Mounting the IPL T PCS4 Interface
The IPL T PCS4 can be set on a table, mounted on a rack shelf, or mounted
under furniture such as a desk, podium, or tabletop.
Tabletop Use
Four self-adhesive rubber feet are included with the PCS4. For tabletop use,
attach one foot at each corner of the bottom side of the unit, and place the
PCS4 in the desired location.
UL Rack Mounting Guidelines
The following Underwriters Laboratories (UL) guidelines pertain to the safe
installation of the IPL T PCS4 or IPL T PCS4i in a rack.
CAUTION: · Elevated operating ambient temperature — If the equipment is
installed in a closed or multi-unit rack assembly, the operating ambient
temperature of the rack environment may be greater than room ambient
temperature. Therefore, install the equipment in an environment compatible
with the maximum ambient temperature (TMA = +122 °F, +50 °C) specified by
Extron. · Reduced air flow — Install the equipment in a rack so that the
amount of air flow required for safe operation of the equipment is not
compromised. · Mechanical loading — When mounting the equipment in the rack,
ensure that uneven mechanical loading does not cause a hazardous condition. ·
Circuit overloading — When connecting the equipment to the supply circuit,
consider the effect that circuit overloading might have on overcurrent
protection and supply wiring. Consider equipment nameplate ratings when
addressing this concern. · Reliable earthing (grounding) — Maintain reliable
grounding of rack-mounted equipment. Pay particular attention to supply
connections other than direct connections to the branch circuit (for example,
use of power strips).
IPL T PCS4 · Reference Material 53
Consignes UL pour le montage en rack
Les consignes UL (« Underwriters Laboratories ») suivantes concernent
l’installation en rack d’un boîtier IPL T PCS4 ou IPL T PCS4i :
ATTENTION :
· Température ambiante élevée — En cas d’installation de l’équipement dans un
rack fermé ou composé de plusieurs unités, la température du rack peut être
supérieure à la température ambiante. Par conséquent, il est préférable
d’installer l’équipement dans un environnement qui respecte la température
ambiante maximale (Tma) spécifiée par Extron.
· Réduction du flux d’air — Si l’équipement est installé dans un rack, veillez
à ce que le flux d’air nécessaire pour un fonctionnement sécurisé de
l’équipement soit respecté.
· Charge mécanique — Installez l’équipement en rack de manière à éviter toute
situation dangereuse causée par le déséquilibre de la charge mécanique.
· Surcharge électrique — Lorsque vous connectez l’équipement au circuit
d’alimentation, observez la connexion de l’équipement et étudiez les effets
possibles d’une surcharge du circuit sur les protections contre les
surintensités et les conducteurs d’alimentation. Consultez à cet égard les
indications de la plaque d’identification de l’équipement.
· Mise à la terre — Assurez-vous que l’équipement est correctement mis à la
terre. Accordez une attention particulière aux connexions électriques autres
que les connexions directes au circuit de dérivation (ex. : les multiprises).
Rack mounting procedure
Rack mount the interface, if desired, using the RSU 129 Universal Rack Shelf
Kit) as follows:
Half-rack false front panel uses 2 front holes
IPL T PCS4 R F1
S
F2 S
F3 S
F4 S
STSAENTDRBEYFERFEUNLCLE L1IN0K0 ACT
(2) 4-40 x 3/16″ screws Use 2 mounting holes on opposite corners
Figure 40. Mounting the IPL T PCS4 on a Rack Shelf
1. If rubber feet have been installed on the bottom of the unit, remove them.
2. Mount the PCS4 on the rack shelf, using two 4-40 x 3/16 inch screws in opposite (diagonal) corners to secure the unit to the shelf.
3. Attach a blank panel or other units to the rack shelf.
IPL T PCS4 · Reference Material 54
4. Insert the shelf into the rack, aligning the holes in the shelf with those
in the rack. 5. Secure the shelf to the rack using the supplied machine
screws. This shelf can be
mounted in the front or in the rear of the rack.
Under-desk Mounting
The PCS4 can also be mounted under furniture, such as a table or podium
surface, using the optional under-desk mounting brackets.
LAN ALARM
10A 200-240V
50/60 Hz
200-240V
TOTAL LOAD 10A MAX
Figure 41. Mounting the IPL T PCS4 under Furniture
1. If rubber feet were previously installed on the bottom of the unit, remove
them. 2. Attach the mounting brackets to the unit with the provided machine
screws. 3. Insert #8 wood screws into the four pilot holes. Tighten each screw
into the mounting
surface until slightly less than ¼ inch of the screw protrudes. 4. Align the
mounting screws with the slots in the brackets, and place the PCS4 against
the surface with the screws through the bracket slots. 5. Slide the unit
slightly forward or back, then tighten all four screws to secure it in place.
IPL T PCS4 · Reference Material 55
Glossary
This section contains a list of terms that appear in this user guide, with their definitions.
10/100Base-T
Ethernet that uses unshielded twisted pair (for example, UTP – Cat 5) cable, in which the amount of data transmitted between two points in a given amount of time is equal to either 10 Mbps or 100 Mbps.
A
Address Resolution Protocol (ARP) A protocol for assigning an IP address to a device based on the MAC (Media Access Control), or physical machine address of the device, that maintains a table showing the correlation between the two.
Alarm relay
A single pole, single throw relay, which can be used with a relay-controllable audible siren or any other alarm.
Alarm status
On the PCS4 web page, reflects the state of the monitored condition. It may be inactive, active, or silenced.
AWG (American Wire Gauge) A standard measurement for wire conductor diameter.
C
Condition
Custom web page
A state for which the PCS4 is being monitored. When a monitored condition is
met, the PCS4 may sound an alarm or send an e-mail message, depending on how
the system has been configured (via the front panel or the Monitor web page).
Examples of conditions that can be monitored include Receptacle Off, Any
Change, or Reference: None.
Any file that can be loaded into an IPL T PCS4 and served by the PCS4 internal
web server. The web page provides a way to control and monitor the PCS4 output
power receptacles. This is true with or without an accompanying event script.
Any number and size of graphics can be used, but if they are too large to fit
in the PCS4 nonvolatile memory, you can create web pages so that they can be
served from another web server. If you install Microsoft Internet Information
Services (IIS) on your desktop, you can serve any page on its hard disk. The
IPL T PCS4 functions like a little computer with a web server — you can use it
for various web-based tasks.
IPL T PCS4 · Reference Material 56
D
DHCP (Dynamic Host Configuration Protocol) A standardized client-server IP networking protocol that enables network administrators to centrally and automatically manage the assignment of IP addresses in an organization’s network.
Driver
A package of commands that generates or is the event script that controls devices.
E
Edison power receptacle Is a standard power connector. The rear panel of the IPL T PCS4, U. S. version, has four female Edison receptacles into which devices are plugged in order to be monitored, scheduled, and powered on and off by the PCS4.
Ethernet
A network protocol that uses MAC addresses to exchange data between computers. Using ARP, with TCP/IP support, Ethernet devices can be connected to the Internet. An Ethernet LAN typically uses unshielded twisted pair (UTP) wires. Ethernet systems provide transmission speeds of 10 Mbps or 100 Mbps. Ethernet is mostly based on the IEEE 802.3 standard.
Executive mode
An operating mode in which the IPL T PCS4 does not accept commands from the front panel. Also called front panel security lockout.
F
Firmware
Embedded software that is stored permanently in read-only memory (ROM) and contains basic instructions for how the PCS4 operates. Firmware upgrades are periodically made available for uploading via the IPL T PCS4 Firmware Upgrade web page.
Full reference threshold The point at which a device starts to operate at full power.
H
HTTP (HyperText Transfer Protocol) A web protocol based on TCP/IP that is used
to retrieve hypertext objects from remote web pages.
I
IEC power receptacle Is a standard power connector. The IPL T PCS4i rear panel has four female IEC receptacles into which devices are plugged in order to be monitored, scheduled, and powered on and off by the PCS4i.
IP (Internet Protocol) The protocol or standard used to send information from one computer to another on the Internet.
IP address
A unique, 32-bit binary number (12 digit decimal number — nnn.nnn.nnn.nnn) based on version 4 of the internet protocol (IPv4) that identifies each sender and each receiver of information connected to a LAN, WAN, or the Internet. IP addresses can be static (see Static IP) or dynamic (see DHCP).
IPL T PCS4 · Reference Material 57
IP net mask/subnet mask A 32-bit binary number (12 digit decimal number — nnn.nnn.nnn.nnn) used on subnets (smaller, local networks) to help the router determine which network traffic gets routed internally to local computers and which network traffic goes out on the Internet.
M
Media Access Control (MAC) Address A unique hardware number given to devices
that connect to the Internet. When your computer or networking device (router,
hub, interface, and so on) is connected to the Internet, a table relates the
device IP address to its corresponding physical (MAC) address on the LAN.
P
Ping (Packet Internet Groper) A command that is used to test connectivity between IP devices. The Internet Control Message Protocol (ICMP) echoes Ethernet packets to determine whether a network device is active and what the bidirectional delay is in communicating with it.
Port number
A preassigned address within a server that provides a direct route from the application to the Transport layer or from the Transport layer to the application of a TCP/IP system.
Power level reference threshold (See Reference threshold.)
R
Reference threshold Receptacle
The point at which the power level (full or standby) at which a device is
operating changes. This threshold is recognized by the IPL T PCS4, which can
be configured to sound an alarm whenever a connected device passes this
threshold.
A connector on a power supply that is equipped to receive a plug. The IPL T
PCS4 has four receptacles into which devices can be plugged, enabling the PCS4
to monitor and schedule power for the connected devices.
S
SIS (Simple Instruction Set) commands A set of commands developed by Extron that allows control of the PCS4 via the keyboard of a PC with an Ethernet connection. A minimal number of characters are used in these commands and responses.
Standby reference threshold The point at which a device starts to operate at standby power.
Static IP
An IP address that has been specifically, instead of dynamically (see DHCP), assigned to a device or system in a network configuration. This type of address requires manual configuration of the actual network device or system and can only be changed manually or by enabling DHCP.
Subnet
(See Subnetwork.)
Subnet address
The portion of an IP address that is specifically identified by the subnet mask as the subnetwork.
IPL T PCS4 · Glossary 58
Subnet mask Subnetwork
A 32-bit address mask used in IP to identify the bits of an IP address that
are used for the subnet address. Using a mask, the router does not need to
examine all 32 bits, only those selected by the mask.
A network that is part of a larger IP network and is identified by a subnet
address. Networks can be segmented into subnetworks to provide a hierarchical,
multilevel routing structure.
T
TCP (Transmission Control Protocol) A connection-oriented protocol defined at the Transport layer of the OSI reference model. It provides reliable delivery of data.
TCP/IP (Transmission Control Protocol/Internet Protocol) The communication protocol (language) of the Internet. Computers and devices with direct access to the Internet are provided with a copy of the TCP/IP program to allow them to send and receive information in an understandable form.
Telnet
A standard terminal emulation utility/protocol that allows a computer to
communicate with a remote user/client. A user who wishes to access a remote
system initiates a Telnet session using the address of the remote client. The
user may be prompted to provide a user name and password if the client is set
up to require them. Telnet enables users to log in on remote networks and use
those resources as if they were locally connected.
NOTE: The factory configured passwords for all accounts on this device have
been set to the device serial number. In the event of an absolute system
reset, the passwords convert to the default, which is extron.
Threshold Threshold status
(See Reference threshold.)
Reported on the IPL T PCS4 System Status screen in the AC Receptacles section.
It indicates the current reference threshold (Full, Standby, None, or Not Set)
for each PCS4 receptacle.
U
UID (User ID)
An optional user name, for which a field is provided on the Enter Password
window that opens if a password has been assigned to the PCS4.
NOTE: The factory configured passwords for all accounts on this device have
been set to the device serial number. In the event of an absolute system
reset, the passwords convert to the default, which is extron.
URL (Universal Resource Locator) The address that lets a resource on the internet be identified, located, and accessed.
IPL T PCS4 · Glossary 59
Extron Warranty
Extron Electronics warrants this product against defects in materials and workmanship for a period of three years from the date of purchase. In the event of malfunction during the warranty period attributable directly to faulty workmanship and/or materials, Extron Electronics will, at its option, repair or replace said products or components, to whatever extent it shall deem necessary to restore said product to proper operating condition, provided that it is returned within the warranty period, with proof of purchase and description of malfunction to:
USA, Canada, South America, and Central America:
Extron Electronics 1230 South Lewis Street Anaheim, CA 92805 U.S.A.
Asia:
Extron Asia Pte Ltd 135 Joo Seng Road, #04-01 PM Industrial Bldg. Singapore
368363 Singapore
Japan:
Extron Electronics, Japan Kyodo Building, 16 Ichibancho Chiyoda-ku, Tokyo
102-0082 Japan
Europe: Extron Europe Hanzeboulevard 10 3825 PH Amersfoort The Netherlands
Africa: Extron South Africa 3rd Floor, South Tower 160 Jan Smuts Avenue
Rosebank 2196, South Africa
China:
Extron China 686 Ronghua Road Songjiang District Shanghai 201611 China
Middle East:
Extron Middle East Dubai Airport Free Zone F13, PO Box 293666 United Arab
Emirates, Dubai
This Limited Warranty does not apply if the fault has been caused by misuse,
improper handling care, electrical or mechanical abuse, abnormal operating
conditions, or if modifications were made to the product that were not
authorized by Extron.
NOTE: If a product is defective, please call Extron and ask for an Application
Engineer to receive an RA (Return Authorization) number. This will begin the
repair process.
USA:
Europe: Africa:
714.491.1500 or 800.633.9876 31.33.453.4040 or 800.3987.6673 27.11.447.6162
Asia: Japan: Middle East:
65.6383.4400 81.3.3511.7655 971.4.299.1800
Units must be returned insured, with shipping charges prepaid. If not insured,
you assume the risk of loss or damage during shipment. Returned units must
include the serial number and a description of the problem, as well as the
name of the person to contact in case there are any questions.
Extron Electronics makes no further warranties either expressed or implied
with respect to the product and its quality, performance, merchantability, or
fitness for any particular use. In no event will Extron Electronics be liable
for direct, indirect, or consequential damages resulting from any defect in
this product even if Extron Electronics has been advised of such damage.
Please note that laws vary from state to state and country to country, and
that some provisions of this warranty may not apply to you.
Contact Information
Worldwide Headquarters: Extron USA West, 1025 E. Ball Road, Anaheim, CA 92805, 800.633.9876